FIREFILM®III  

FIRE TEST DESIGN SUMMARY

Construction Type

Ratings, hours

Minimum

W/D (M/D)

Design No.

3/4

1

1.5

2

3

ULI

ULC

ITS

FM

Columns - W Shapes

X

X

-

-

-

0.59 (34)

X669

Z626

-

Method 6

Columns - W Shapes

-

-

-

-

X

1.28 (74)

X670

Z627

-

Method 7

Columns - W Shapes

-

-

-

-

X

2.26 (130)

X639

Z608

AD/CA 180-01

-

Columns - W Shapes

X

X

X

X

-

refer to design

X641

Z610

AD/CA 120-03

-

Columns - W Shapes

-

 

-

 

X

 

-

X

-

 

0.66 (38)

1.64 (95.2)

X643

Z612

-

Columns - W Shapes

-

-

-

X

-

1.28 (74)

X645***

Z617

***

AD/CA 120-04

***

Method 5

***

Columns - HSS Shapes

-

-

X

X

-

A/P≥0.30 (59)

X671

Z628

-

Method 8

Columns - HSS Shapes

X

X

X

X

-

refer to design

X642

Z611

AD/CA 90-02

-

Columns - HSS Shapes

X

X

X

X

X

A/P≥0.46 (90)

X672

Z629

-

Method 9

Columns - HSS Shapes

X

X

-

-

-

A/P≥0.22 (44)

X673

Z630

-

Method 10

Columns ***

 HSS Shapes

-

-

-

X

-

A/P≥0.57 (113.9)

X645***

Z617

***

AD/CA 120-04

***

Method 5

***

Beams / Floors

B

B

R

R

-

0.51 (30)

-

F906

AD/FCA 120-01

-

Beams / Floors

-

B

R

R

-

0.82 (48)

D948

F910

-

Beams / Floors

-

 

-

 

U

 

R

B

-

 

0.80 (46)

0.84 (48)

D941

F912

-

No. 31

R = Restrained Assembly     U = Unrestrained Beam + Unrestrained Assembly Rating     B = Restrained Assembly +Unrestrained Assembly and Beam


      ***X645, Z617 and AD/CA 120-04 and Method 5 require glass cloth.

ITS = Intertek Testing Services (Warnock Hersey) UL = Underwriters Laboratories Inc.
ULC = Underwriters' Laboratories of Canada FM = Factory Mutual Research
 

This summary contains information we believe to be accurate and current as of October 19, 2007. New designs are being developed and existing designs are being updated continuously. Please contact your A/D FIREFILM III representative for the latest design information

 