FIREBARRIER Firestopping Materials

Index of Firestop Systems and Designs – by Trade

        HOME                                                                                                                                    GO UP ONE LEVEL

Quick Links to Electrical Trade Applications

CONDUIT & EMT

NON-METALLIC CONDUIT

MULTIPLE PENETRATIONS

CABLES/ LARGER OPENINGS

WALL OPENING PROTECTION MATERIALS

 

A/D FIREBARRIER FIRESTOP SYSTEMS

Electrical - Application Designs and Reference Guide

 

CONDUIT & EMT

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

6" Conduit

& 4” EMT or

smaller

3

0" to 2"

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. ¼” thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4¼” thick packed into opening  (wall both sides)

C-AJ-1557

 

6" Conduit

& EMT or

smaller

3

0" to 1-1/8”

annulus

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER

Silicone

__________

A/D FIREBARRIER

Mineral Wool

Min. ½“ thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4” thick packed into opening  (wall both sides)

C-AJ-1497

 

4" Conduit

and 6" EMT

or smaller

 

 

2

0" to 3¼”

annulus

Floor - Concrete

Wall - Concrete,

Concrete Block

or Precast Units

A/D FIREBARRIER

Silicone or

Silicone SL

____________

A/D FIREBARRIER

Mineral Wool

Min. ½” thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4” thick packed into opening (wall both sides)

C-AJ-1299

 

1½" Conduit

& EMT or

smaller

3

3/8” to ¾"

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast Conc.

A/D FIREBARRIER Putty II

Min. 2” thick within annulus flush with top of floor or both surfaces of wall

C-AJ-1559

 
GYPSUM WALLBOARD CONSTRUCTION

4 " diameter

or smaller

1 & 2

0" to 1-7/8"

annulus

Wall  - Gypsum

Board as rated for 1 & 2 hr

A/D FIREBARRIER

Intumescent Sealant

Min. ½” or 5/8” thick within annulus, flush both surfaces

of wall

Foam Backer optional

W-L-1416

 

6 " conduit

or smaller

4” EMT

2

0" to 7/8”

annulus

Wall  - Gypsum

Board

A/D FIREBARRIER

Intumescent

Sealant or Acrylic

_____________

A/D FIREBARRIER

Mineral Wool

Min. ½“ thick within annulus, flush both surfaces of wall

_____________

Min. ½ “ thick packed into opening both sides of wall

W-L -1417

 

2" Conduit

& EMT or

smaller

1 & 2

0" to 1- 7/8"

annulus

Wall - Gypsum

Board

A/D FIREBARRIER

Silicone

Min. 5/8” thick within annulus, flush both surfaces of wall

W-L -1198

 
WOOD CONSTRUCTION

4" Conduit

& EMT or

smaller

1

¼"

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

Silicone

Min.1-1/8” thick within annulus on top of floor

Min. ½” thick within annulus on bottom surface of ceiling

F-C-1011

 

6" Conduit

& 4” EMT or

smaller

1 & 2

0" to 7/8"

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant

Min. 5/8” thick within annulus

on top at floor

Min. 5/8” thick within annulus

on bottom surface ceiling-

½” crown

F-C-1149

 

4" Conduit

& EMT or

smaller

1

¼”

annulus

Floor - Lumber

Ceiling - Gypsum

Board - In Wall

A/D FIREBARRIER

Silicone

Min.1-1/8” thick within annulus on top of floor generous bead,

flush with bottom surface lower top plate

F-C-1034

 

top of page

NON-METALLIC CONDUIT

Max. Size

Penetration

Diameter

Rating

(h)

Max Size

Opening

Floor or Wall

System

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

2”, PVC, CPVC &

Rigid Conduit

& 1½" ENT

or smaller

2

¾" to 1-3/8"

annulus

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER

Silicone or

Silicone SL

___________

A/D FIREBARRIER

Mineral Wool

Min. 1” thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4” thick packed into opening (wall both sides)

C-AJ-2150

 

3” PVC, CPVC

& rigid conduit or smaller

2

¾" to 7/8”

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant   _____________

Foam Backer optional

Min. 2” thick within annulus flush with top of floor or both surfaces of wall

_______________

Foam Backer Optional

C-AJ-2581

 

4”, PVC, CPVC,

& rigid conduit or smaller

1

0” to 1½”

annulus

Floor - Concrete

(4½" min. thick Concrete)

 

A/D FIREBARRIER

Intumescent Sealant

Foam Backer optional

Min. ½” thick within annulus flush with top of floor add

½” crown

Foam Backer Optional

 

F-A-2168

 

6“ Conduit

or

4“ EMT

2

0” to 2”

Wall concrete

(steel sleeve optional)

A/D FIREBARRIER

Intumescent Sealant

___________

A/D FIREBARRIER

Mineral Wool

Min. 1“ thick within annulus flush with one surface of wall

_____________

Min. 5“ thick packed into opening recessed from one side

W-J-1204

 
GYPSUM WALLBOARD CONSTRUCTION

2”, PVC, CPVC &

rigid conduit

or smaller

2

½" to 1-1/8"

annulus

 

Wall  - Gypsum

Board Wood

A/D FIREBARRIER

Silicone

____________

A/D FIREBARRIER

Mineral Wool

Min. ¾” thick within annulus, flush on both surfaces of wall

_____________

Min. 2” thick packed into opening each side of wall

W-L-2157

 

2”, PVC, CPVC, ABS

rigid NM conduit

or smaller.

1 & 2

¼” to 1-3/8” annulus

Wall  - Gypsum

Board

 

A/D FIREBARRIER

Intumescent Sealant

Min.5/8” thick within annulus flush on both surfaces of wall

Plus a ¼” crown around

W-L-2486

 
WOOD CONSTRUCTION

4" Metallic tubing & 6” steel conduit

or smaller

1

0” to 7/8”

Floor - Lumber

Ceiling - Gypsum

Board

(chase wall optional)

A/D FIREBARRIER Intumescent Sealant

Foam Backer optional

Min. 5/8” thick within annulus flush with top at floor

Added. ½” thick crown & 1¼” lapping beyond opening

Optional Foam Backer

F-C-1149

 

4" EMT or conduit

or smaller

1

0” to 7/8”

Floor - Lumber

Ceiling - Gypsum

Board

(chase wall)

A/D FIREBARRIER Intumescent sealant

Foam Backer optional

Min. ½“ thick within annulus on top at floor

Min. ½” thick within annulus on bottom surface ceiling and ¼” at point of contact

Foam Backer

F-C-1150

 

4”, PVC,

CPVC, ABS

4” NM conduit or smaller

 

1

0” to ½"

annulus

Floor - Lumber

Ceiling - Gypsum

Board

(water closet Config C only)

A/D FIREBARRIER

Intumescent Sealant  & Acrylic

Foam Backer optional

Min. ¾” thick within annulus - top

Min. 5/8“ thick within annulus - bottom

F-C-2347

 

top of page

MULTIPLE PENETRATIONS

Type of

Penetration

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

3" Conduit &

EMT or smaller,

Cables & Cable Tray

3

2.2 sq. ft.

Floor - Concrete

Wall - Concrete

Concrete Block

or Precast Units

A/D FIREBARRIER

Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. ¼” thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4” thick packed into opening (wall both sides)

C-AJ-8028

 

3" Conduit &

EMT or smaller,

Cables & Cable Tray

3

2.2 sq. ft.

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER

Mortar

Min. 3” thick flush with top of floor & both sides of wall

C-AJ-8029

 

2" Conduit

or smaller,

Cables & Cable Tray

3

24 sq. ft.

Floor / Wall /

Concrete

A/D FIREBARRIER

Mortar

Fill opening to min. depth 3”

AD/PHV 180-01

 

¾”, conduit, EMT or smaller

+ cables

 

2

 

3½” max opening with ½” between pipes & cables

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant

________________

A/D FIREBARRIER Mineral Wool

Min. 1” thick within annulus, flush top of floor, both surfaces of wall-force sealant into interstices to max. possible, when floor hollow core, fill both sides of floor flush

__________________

Min. 3½" thick packed into opening and into interstices, with hollow core pack both surfaces of floor

C-AJ-8183

 

4” Steel, iron,

 

4” Conduit

 

2” Copper pipe & tubing

3

112.5 sq/in

_________

Annulus non-insul

0” to 3-3/8” & periphery

Annulus for

Insulated

½” to 1”

Annulus between  all penetrants ½” to 5/8”

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER

Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. ½” thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4” thick packed into opening  (wall both sides)

C-AJ-8184

 
GYPSUM WALLBOARD CONSTRUCTION

4" Conduit &

EMT or smaller,

Cables & Cable Tray

1 & 2

1.9 sq. ft.

Wall  - Gypsum

Board

A/D FIREBARRIER

Mortar

2 hr- min. 4½” flush with

 both surfaces of wall

__________________

1 hr - min. 3½” flush with

both surfaces of wall

W-L-8005

 

 top of page

CABLES/ LARGER OPENINGS

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

Coaxial, Fiber

Optic & 24 AWG

3

288 sq. in.

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER

Pillows

Installed with 8” dimension projecting through floor or wall & centered within opening

C-AJ-4046

 

Coaxial, Fiber

Optic & 24 AWG

& Data Cable

3

288 sq. in.

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER

Pillows

Installed with 8” dimension projecting through floor or wall & centered within opening

C-AJ-4052

 

C-2/0 AWG

24 AWG

350 kcmil

62.5/48 fiber optic

2

 

½" to 1"

annulus

Floor - Concrete

Wall - Concrete

or Concrete Block

Pre-Cast

A/D FIREBARRIER Putty II

A/D FIREBARRIER Mineral Wool

Min. 1” thick within annulus flush with top or bottom of floor or both surfaces of wall

Min. 3½” mineral wool packed into opening

C-AJ-3274

 

24 AWG &

Romex

4

3/8”" to 5/8"

annulus

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER

Putty II

 

Min. 3” thick within annulus flush with top of floor or both surfaces of wall

C-AJ-3275

 

Cable tray-

24” X 6”

Cables- fiber optic, coaxial, 24 AWG,metal clad cable

2

Max opening 300 sq in

(max dimension 30 in)

Wall -Concrete

or Concrete Block

A/D FIREBARRIER Intumescent Sealant

A/D FIREBARRIER

Putty II

 

Min 1” by 1¼” depth around outer diameter or each optic raceway

Min ¾” thick packed against all four sides of opening and between each layer of cables

W-J-4064

 

500 KCMIL,

24, 12, 10 AWG or smaller,

RG / U

2

¼" nom.

annulus

Wall -Concrete

or Concrete Block

A/D FIREBARRIER

Silicone

_____________

A/D FIREBARRIER

Mineral Wool

Min. ¾” thick within annulus, flush with both surfaces of wall

_____________

Min. 2” thick packed into opening on both sides of wall

W-J-3087

 
GYPSUM WALLBOARD CONSTRUCTION

24, 12, 8, 6 &

2 AWG

Metal clad, flexible metal conduit

1 & 2

¼” to 1” max annulus within sleeve

Wall – Gypsum Board

A/D FIREBARRIER Intumescent Sealant

Foam Backer optional

Min. 5/8 inch thick within annulus, flush each surface of wall, fill all interstices between cables, add 3/8” crown & 3/8” beyond periphery

W-L-3322

 

500 KCMIL,

24 AWG,

RG 11/ U

1 & 2

¼" nom.

annulus

Wall -Gypsum

Board

A/D FIREBARRIER

Silicone

2 hr- min. 1” within annulus on

both surfaces of wall __________________

1 hr - min. ½” within annulus on both surfaces of wall

W-L-3042

 

500 KCMIL,

24, 12, 10 AWG or smaller,

RG / U

1 & 2

¼" nom.

annulus

Wall -Gypsum

Board

A/D FIREBARRIER

Silicone

_____________

A/D FIREBARRIER

Mineral Wool

Min. ¾” thick within annulus, flush on both surfaces of wall

_____________

Min. 2 inch thick packed into opening on both sides of wall

W-L-3207

 

 

24, 12, 3/0, 2/0 AWG, fiber optic, 8 AWG, coaxial,

350 kcmil.

1 & 2

¼” to 1½”

Wall-Gypsum

Board

(metal sleeve)

A/D FIREBARRIER

Intumescent Sealant

or Acrylic

_____________

A/D FIREBARRIER

Mineral Wool

Min. ½ “ thickness applied within annulus, flush with each end of sleeve

_____________

Min. 1” thick packed into opening in 1 or 2 hr walls, flush both surfaces of wall

W-L-3324

 

WOOD CONSTRUCTION

500 KCMIL,

10, 12, 40,24 AWG &

RG 11/ U

1

1/8" nom.

annulus

Floor - Lumber

Ceiling - Gypsum

Board -Out of Wall

A/D FIREBARRIER

Silicone

Min.1-1/8” thick within annulus on top of floor

Min. ½” thick within annulus on bottom surface of ceiling

F-C-3014

 

500 KCMIL,

24, 12 AWG,

RG 11/ U

1

1/8" nom.

annulus

Floor - Lumber

Ceiling - Gypsum

Board -In Wall

A/D FIREBARRIER

Silicone

Min.1-1/8” thick within annulus flush with top of floor

A generous bead within annulus flush bottom surface of lower top plate

F-C-3027

 

CABLES

2

¼" to ½”

annulus

Floor / Lumber

Ceiling / Gypsum

Board

A/D FIREBARRIER

 Intumescent Sealant

______________

Foam Backer optional

Min.5/8” thick within annulus flush with top of floor

F-C-3099

 

 

METALLIC or NON-METALLIC ELECTRICAL BOXES

Single or Double Boxes

1 & 2

See CLIV Report

Wall -Gypsum

Board

A/D FIREBARRIER

Putty Pads II

See CLIV Report

CLIV

 

Single Box Metallic

1 & 2

See CLIV Report.

Wall -Gypsum

Board

A/D FIREBARRIER

Inserts (Single)

See CLIV Report

CLIV

 

Double Box Metallic

1 & 2

See CLIV Report

Wall -Gypsum

Board

A/D FIREBARRIER Inserts (Double)

See CLIV Report

CLIV

 