Quick Links to Electrical Trade Applications
WALL OPENING PROTECTION MATERIALS
|
A/D FIREBARRIER FIRESTOP SYSTEMS |
|||||||
Electrical - Application Designs and Reference Guide |
|||||||
|
|
|||||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
CONCRETE CONSTRUCTION |
|||||||
|
6" Conduit & 4” EMT or smaller |
3 |
0" to 2" annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. ¼” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4¼” thick packed into opening (wall both sides) |
||
|
6" Conduit & EMT or smaller |
3 |
0" to 1-1/8” annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone __________ A/D FIREBARRIER Mineral Wool |
Min. ½“ thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
||
|
4" Conduit and 6" EMT or smaller
|
2 |
0" to 3¼” annulus |
Floor - Concrete Wall - Concrete, Concrete Block or Precast Units |
A/D FIREBARRIER Silicone or Silicone SL ____________ A/D FIREBARRIER Mineral Wool |
Min. ½” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
||
|
1½" Conduit & EMT or smaller |
3 |
3/8” to ¾" annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast Conc. |
A/D FIREBARRIER Putty II |
Min. 2” thick within annulus flush with top of floor or both surfaces of wall |
||
GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
4 " diameter or smaller |
1 & 2 |
0" to 1-7/8" annulus |
Wall - Gypsum Board as rated for 1 & 2 hr |
A/D FIREBARRIER Intumescent Sealant |
Min. ½” or 5/8” thick within annulus, flush both surfaces of wall Foam Backer optional |
||
|
6 " conduit or smaller 4” EMT |
2 |
0" to 7/8” annulus |
Wall - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant or Acrylic _____________ A/D FIREBARRIER Mineral Wool |
Min. ½“ thick within annulus, flush both surfaces of wall _____________ Min. ½ “ thick packed into opening both sides of wall |
||
|
2" Conduit & EMT or smaller |
1 & 2 |
0" to 1- 7/8" annulus |
Wall - Gypsum Board |
A/D FIREBARRIER Silicone |
Min. 5/8” thick within annulus, flush both surfaces of wall |
||
WOOD CONSTRUCTION |
|||||||
|
4" Conduit & EMT or smaller |
1 |
¼" annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Silicone |
Min.1-1/8” thick within annulus on top of floor Min. ½” thick within annulus on bottom surface of ceiling |
||
|
6" Conduit & 4” EMT or smaller |
1 & 2 |
0" to 7/8" annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant |
Min. 5/8” thick within annulus on top at floor Min. 5/8” thick within annulus on bottom surface ceiling- ½” crown |
||
|
4" Conduit & EMT or smaller |
1 |
¼” annulus |
Floor - Lumber Ceiling - Gypsum Board - In Wall |
A/D FIREBARRIER Silicone |
Min.1-1/8” thick within annulus on top of floor generous bead, flush with bottom surface lower top plate |
|
|
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
CONCRETE CONSTRUCTION |
|||||||
|
2”, PVC, CPVC & Rigid Conduit & 1½" ENT or smaller |
2 |
¾" to 1-3/8" annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL ___________ A/D FIREBARRIER Mineral Wool |
Min. 1” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
||
|
3” PVC, CPVC & rigid conduit or smaller |
2 |
¾" to 7/8” annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Foam Backer optional |
Min. 2” thick within annulus flush with top of floor or both surfaces of wall _______________ Foam Backer Optional |
||
|
4”, PVC, CPVC, & rigid conduit or smaller |
1 |
0” to 1½” annulus |
Floor - Concrete (4½" min. thick Concrete) |
A/D FIREBARRIER Intumescent Sealant Foam Backer optional |
Min. ½” thick within annulus flush with top of floor add ½” crown Foam Backer Optional
|
||
|
6“ Conduit or 4“ EMT |
2 |
0” to 2” |
Wall concrete (steel sleeve optional) |
A/D FIREBARRIER Intumescent Sealant ___________ A/D FIREBARRIER Mineral Wool |
Min. 1“ thick within annulus flush with one surface of wall _____________ Min. 5“ thick packed into opening recessed from one side |
W-J-1204 |
|
GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
2”, PVC, CPVC & rigid conduit or smaller |
2 |
½" to 1-1/8" annulus
|
Wall - Gypsum Board Wood |
A/D FIREBARRIER Silicone ____________ A/D FIREBARRIER Mineral Wool |
Min. ¾” thick within annulus, flush on both surfaces of wall _____________ Min. 2” thick packed into opening each side of wall |
||
|
2”, PVC, CPVC, ABS rigid NM conduit or smaller. |
1 & 2 |
¼” to 1-3/8” annulus |
Wall - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant |
Min.5/8” thick within annulus flush on both surfaces of wall Plus a ¼” crown around |
||
WOOD CONSTRUCTION |
||||||||
|
4" Metallic tubing & 6” steel conduit or smaller |
1 |
0” to 7/8” |
Floor - Lumber Ceiling - Gypsum Board (chase wall optional) |
A/D FIREBARRIER Intumescent Sealant Foam Backer optional |
Min. 5/8” thick within annulus flush with top at floor Added. ½” thick crown & 1¼” lapping beyond opening Optional Foam Backer |
|||
|
4" EMT or conduit or smaller |
1 |
0” to 7/8” |
Floor - Lumber Ceiling - Gypsum Board (chase wall) |
A/D FIREBARRIER Intumescent sealant Foam Backer optional |
Min. ½“ thick within annulus on top at floor Min. ½” thick within annulus on bottom surface ceiling and ¼” at point of contact Foam Backer |
|||
|
4”, PVC, CPVC, ABS 4” NM conduit or smaller
|
1 |
0” to ½" annulus |
Floor - Lumber Ceiling - Gypsum Board (water closet Config C only) |
A/D FIREBARRIER Intumescent Sealant & Acrylic Foam Backer optional |
Min. ¾” thick within annulus - top Min. 5/8“ thick within annulus - bottom |
|||
|
Type of Penetration |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
CONCRETE CONSTRUCTION |
||||||||
|
3" Conduit & EMT or smaller, Cables & Cable Tray |
3 |
2.2 sq. ft. |
Floor - Concrete Wall - Concrete Concrete Block or Precast Units |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. ¼” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
|||
|
3" Conduit & EMT or smaller, Cables & Cable Tray |
3 |
2.2 sq. ft. |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Mortar |
Min. 3” thick flush with top of floor & both sides of wall |
|||
|
2" Conduit or smaller, Cables & Cable Tray |
3 |
24 sq. ft. |
Floor / Wall / Concrete |
A/D FIREBARRIER Mortar |
Fill opening to min. depth 3” |
|||
|
¾”, conduit, EMT or smaller + cables
|
2
|
3½” max opening with ½” between pipes & cables |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant ________________ A/D FIREBARRIER Mineral Wool |
Min. 1” thick within annulus, flush top of floor, both surfaces of wall-force sealant into interstices to max. possible, when floor hollow core, fill both sides of floor flush __________________ Min. 3½" thick packed into opening and into interstices, with hollow core pack both surfaces of floor |
|||
|
4” Steel, iron,
4” Conduit
2” Copper pipe & tubing |
3 |
112.5 sq/in _________ Annulus non-insul 0” to 3-3/8” & periphery Annulus for Insulated ½” to 1” Annulus between all penetrants ½” to 5/8” |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. ½” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
||
GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
4" Conduit & EMT or smaller, Cables & Cable Tray |
1 & 2 |
1.9 sq. ft. |
Wall - Gypsum Board |
A/D FIREBARRIER Mortar |
2 hr- min. 4½” flush with both surfaces of wall __________________ 1 hr - min. 3½” flush with both surfaces of wall |
|
|
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
CONCRETE CONSTRUCTION |
|||||||
|
Coaxial, Fiber Optic & 24 AWG |
3 |
288 sq. in. |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Pillows |
Installed with 8” dimension projecting through floor or wall & centered within opening |
||
|
Coaxial, Fiber Optic & 24 AWG & Data Cable |
3 |
288 sq. in. |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Pillows |
Installed with 8” dimension projecting through floor or wall & centered within opening |
||
|
C-2/0 AWG 24 AWG 350 kcmil 62.5/48 fiber optic |
2
|
½" to 1" annulus |
Floor - Concrete Wall - Concrete or Concrete Block Pre-Cast |
A/D FIREBARRIER Putty II A/D FIREBARRIER Mineral Wool |
Min. 1” thick within annulus flush with top or bottom of floor or both surfaces of wall Min. 3½” mineral wool packed into opening |
||
|
24 AWG & Romex |
4 |
3/8”" to 5/8" annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Putty II
|
Min. 3” thick within annulus flush with top of floor or both surfaces of wall |
||
|
Cable tray- 24” X 6” Cables- fiber optic, coaxial, 24 AWG,metal clad cable |
2 |
Max opening 300 sq in (max dimension 30 in) |
Wall -Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant A/D FIREBARRIER Putty II
|
Min 1” by 1¼” depth around outer diameter or each optic raceway Min ¾” thick packed against all four sides of opening and between each layer of cables |
||
|
500 KCMIL, 24, 12, 10 AWG or smaller, RG / U |
2 |
¼" nom. annulus |
Wall -Concrete or Concrete Block |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Mineral Wool |
Min. ¾” thick within annulus, flush with both surfaces of wall _____________ Min. 2” thick packed into opening on both sides of wall |
||
GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
24, 12, 8, 6 & 2 AWG Metal clad, flexible metal conduit |
1 & 2 |
¼” to 1” max annulus within sleeve |
Wall – Gypsum Board |
A/D FIREBARRIER Intumescent Sealant Foam Backer optional |
Min. 5/8 inch thick within annulus, flush each surface of wall, fill all interstices between cables, add 3/8” crown & 3/8” beyond periphery |
||
|
500 KCMIL, 24 AWG, RG 11/ U |
1 & 2 |
¼" nom. annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone |
2 hr- min. 1” within annulus on both surfaces of wall __________________ 1 hr - min. ½” within annulus on both surfaces of wall |
||
|
500 KCMIL, 24, 12, 10 AWG or smaller, RG / U |
1 & 2 |
¼" nom. annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Mineral Wool |
Min. ¾” thick within annulus, flush on both surfaces of wall _____________ Min. 2 inch thick packed into opening on both sides of wall |
||
|
24, 12, 3/0, 2/0 AWG, fiber optic, 8 AWG, coaxial, 350 kcmil. |
1 & 2 |
¼” to 1½” |
Wall-Gypsum Board (metal sleeve) |
A/D FIREBARRIER Intumescent Sealant or Acrylic _____________ A/D FIREBARRIER Mineral Wool |
Min. ½ “ thickness applied within annulus, flush with each end of sleeve _____________ Min. 1” thick packed into opening in 1 or 2 hr walls, flush both surfaces of wall |
||
|
WOOD CONSTRUCTION |
|||||||
|
500 KCMIL, 10, 12, 40,24 AWG & RG 11/ U |
1 |
1/8" nom. annulus |
Floor - Lumber Ceiling - Gypsum Board -Out of Wall |
A/D FIREBARRIER Silicone |
Min.1-1/8” thick within annulus on top of floor Min. ½” thick within annulus on bottom surface of ceiling |
||
|
500 KCMIL, 24, 12 AWG, RG 11/ U |
1 |
1/8" nom. annulus |
Floor - Lumber Ceiling - Gypsum Board -In Wall |
A/D FIREBARRIER Silicone |
Min.1-1/8” thick within annulus flush with top of floor A generous bead within annulus flush bottom surface of lower top plate |
||
|
CABLES |
2 |
¼" to ½” annulus |
Floor / Lumber Ceiling / Gypsum Board |
A/D FIREBARRIER Intumescent Sealant ______________ Foam Backer optional |
Min.5/8” thick within annulus flush with top of floor |
||
|
|
|||||||
|
Single or Double Boxes |
1 & 2 |
See CLIV Report |
Wall -Gypsum Board |
A/D FIREBARRIER Putty Pads II |
See CLIV Report |
||
|
Single Box Metallic |
1 & 2 |
See CLIV Report. |
Wall -Gypsum Board |
A/D FIREBARRIER Inserts (Single) |
See CLIV Report |
||
|
Double Box Metallic |
1 & 2 |
See CLIV Report |
Wall -Gypsum Board |
A/D FIREBARRIER Inserts (Double) |
See CLIV Report |
||