A/D FIREBARRIER
FIRESTOP SYSTEMS |
|||||||
Electrical - Application Designs and Reference Guide |
|||||||
|
|
|||||||
|
CONDUIT & EMT |
|||||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D Firebarrier Product Required |
Application Thickness |
System No. |
|
CONCRETE CONSTRUCTION |
|||||||
|
6"
Conduit & 4" EMT or smaller |
3 |
0"
to 2" annulus |
Floor
- Concrete Wall
- Concrete or Concrete Block |
A/D
Firebarrier Intumescent Sealant _____________ A/D
Firebarrier Mineral
Wool |
Min.
1/4 in. thick within annulus flush with top of floor or both surfaces of wall _____________ Min.
4-1/4 in. thick packed into opening
(wall both sides) |
||
|
6"
Conduit & EMT or smaller
|
3 |
0"
to 1 1/8” annulus |
Floor
- Concrete Wall
- Concrete or Concrete Block |
A/D
Firebarrier Silicone -----------------
A/D
Firebarrier Mineral
Wool |
Min.
1/2 inch thick within annulus flush
with top of floor or both surfaces of
wall _____________ Min.
4 inch thick packed into opening
(wall both sides) |
||
|
4"
Conduit and
6" EMT or
smaller |
2 |
0"
to 3-1/4" annulus |
Floor
- Concrete Wall
- Concrete, Concrete
Block or
Precast Units |
A/D
Firebarrier Silicone or Silicone
S L ____________ A/D
Firebarrier Mineral
Wool |
Min.
1/2 inch thick within annulus flush with top of floor or both surfaces
of wall _____________ Min.
4 inch thick packed into opening (wall both sides) |
||
|
1-1/2"
Conduit & EMT or smaller |
3 |
3/8 to 3/4" annulus |
Floor
- Concrete Wall
- Concrete |
A/D
Firebarrier Putty |
Min.2 in. thick within annulus flush with top of floor or both surfaces
of wall |
||
|
|
|||||||
GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
4" dia. or smaller |
1 & 2 |
0"
to 1-7/8" annulus |
Wall
-Gypsum Board
|
A/D
Firebarrier Intumescent Sealant
|
Min.
5/8 inch thick within annulus flush both surfaces of wall _____________ Min.
2 inch thick packed into opening on both sides of wall |
||
|
6"
Conduit or smaller |
2 |
0 to
7/8" annulus |
Wall
-Gypsum Board
|
A/D
Firebarrier Intumescent Sealant or Acrylic ____________ A/D
Firebarrier Mineral
Wool
|
Min.1/2 in. thick within annulus, flush both surfaces of wall ______________
Min.
1/2 inch thick packed into opening on both sides of wall |
||
|
2"
Conduit & EMT or smaller |
1
& 2 |
0"
to 1- 7/8" annulus |
Wall
-Gypsum Board
|
A/D
Firebarrier Silicone |
Min.5/8
inch thick within annulus, flush both surfaces of wall |
||
WOOD CONSTRUCTION |
|||||||
|
4"
Conduit & EMT or smaller |
1 |
1/4" annulus |
Floor
- Lumber Ceiling
- Gypsum Board
|
A/D
Firebarrier Silicone |
Min.1
1/8 inch thick within annulus on top of floor Min.
1/2 inch thick within annulus on bottom surface of ceiling |
||
|
6"
Conduit & 4" EMT or smaller |
1 |
0"
to 7/8" annulus |
Floor
- Lumber Ceiling - Gyp Board
|
A/D
Firebarrier Intumescent Sealant |
Min.5/8" thick within annulus on top of floor Min.
5/8 inch thick within annulus on bottom surface of ceiling |
||
|
4"
Conduit & EMT or smaller |
1 |
1/4" annulus |
Floor
- Lumber Ceiling
- Gypsum Board
- In Wall |
A/D
Firebarrier Silicone |
Min.1
1/8 inch thick within annulus on top of floor generous bead, flush
with bottom surface lower top plate |
||
|
A/D FIREBARRIER FIRESTOP SYSTEMS |
|||||||
Electrical - Application Designs and Reference Guide |
|||||||
|
|
|||||||
|
NON-METALLIC CONDUIT |
|||||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D Firebarrier Product Required |
Application Thickness |
System No. |
|
CONCRETE CONSTRUCTION |
|||||||
|
2", PVC,
CPVC & Rigid
Conduit &
1-1/2" ENT or
smaller |
2 |
3/4"
to 1-3/8" annulus |
Floor
- Concrete Wall
- Concrete or Concrete Block |
A/D
Firebarrier Silicone or Silicone
S L ___________ A/D
Firebarrier Mineral
Wool |
Min.
1 inch thick within annulus flush with top of floor or both surfaces of wall _____________ Min.
4 inch thick packed into opening (wall both sides) |
||
|
3", PVC,
CPVC & |
2 |
3/4"
to
7/8" annulus |
Floor
- Concrete Wall
- Concrete, Concrete Block |
A/D
Firebarrier Intumescent Sealant __________ Foam backer optional |
Min.
2 inch thick within annulus flush with top of floor or both surfaces of wall _____________ Foam backer optional |
||
|
4", PVC,
CPVC & |
1 |
0"
to
1-1/2" annulus |
Floor
- Concrete
|
A/D
Firebarrier Intumescent Sealant __________ Foam backer optional |
Min. 1/2 inch thick within annulus flush with top of floor add 1/2" crown _____________ Foam backer optional |
||
|
6" Conduit 4" EMT |
2 |
0"
to
2" |
Wall - Concrete
steel sleeve optional
|
A/D
Firebarrier Intumescent Sealant __________ A/D
Firebarrier Mineral
Wool |
Min. 1 inch thick within annulus flush with one surface of wall _____________ Min. 5 inch thick packed into opening |
W-J-1204 | |
GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
2,PVC,
CPVC & Rigid
Conduit or
smaller |
2 |
1/2"
to 1-1/8"
annulus |
Wall
-Gypsum Board
Wood |
A/D
Firebarrier Silicone ____________ A/D
Firebarrier Mineral
Wool |
Min.
3/4 inch thick within annulus, flush on both surfaces of wall _____________ Min.
2 inch thick packed into opening each
side of wall |
||
|
2",
PVC, CPVC, ABS,
rigid NM Conduit or
smaller |
1 & 2 |
1/4"
to 1-3/8"
annulus |
Wall
-Gypsum Board |
A/D
Firebarrier Intumescent Sealant |
|||