A/D FIREBARRIER FIRESTOP SYSTEMS

Head of Wall - Application Designs and Reference Guide

Movement Capablilites

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE/CONCRETE ON STEEL DECK/GYPSUM WALLBOARD CONSTRUCTION

Class II

20% Compression or Extension

1 & 2

Floor – Concrete

 

A/D Firebarrier

 Acrylic

_____________

Rock Wool Mfg

Delta Board or

Foam bakker rod

Min. 1/2 inch thick, installed on each side of the wall. _____________

Min 3/4” thick mineral wool t, compressed 50% & firmly packed in gap on top of wallboard & bottom of floor,on both sides

HW-D-0467

 

Class II

20% Compression or Extension

1

Floor – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D Firebarrier

 Seal NS _____________

A/D Firebarrier

Mineral Wool

Min. 1/8 inch wet  thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto gypsum board and steel deck.

_____________

Length equal to the overall width of the wall. Additional 5/8 inch wide strips to fill gap between gypsum board & bottom of steel floor units on both sides of wall.

HW-D-0282

 

Class II

18.75% Compression or Extension

2

Floor  or Roof – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D Firebarrier

 Seal NS _____________

A/D Firebarrier

Mineral Wool

Min. 1/8 inch wet  thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto gypsum board and steel deck.

_____________

Length equal to the overall width of the wall. Additional 1 Ό inch wide strips to fill gap between gypsum board & bottom of steel floor units on both sides of wall.

HW-D-0247

 

N.A.

1 & 2

N.A.

Floor – Concrete

 &

Wall -Gypsum

Board

A/D Firebarrier

 Seal NS

Min, bead diameter of 3/8” cauked into the corner between ends of gypsum wallboard around the entire perimeter of the fire rated wall assembly.

AD/PHV 120-02

 

N.A.

1

5/8”

Floor – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D Firebarrier

 Silicone _____________

A/D Firebarrier

Mineral Wool

Min. 1/4 “ and  5/8” thickness (see fire test design) _____________

Fitted within fluted openings with a Ό” recess from the wall.

AD/PV 60-01

 

N.A.

2

5/8”

Floor – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D Firebarrier

 Silicone _____________

A/D Firebarrier

Mineral Wool

Min. 1/4 “  and  1”  thickness

 (see fire test design) 

_____________

Fitted within fluted openings with a Ό” recess from the wall.

AD/PV 120-01

 

N.A.

1 & 2

N.A.

Floor – Concrete

 &

Wall -Gypsum

Board

A/D Firebarrier

 Silicone

Min, bead diameter of 3/8” cauked into the corner between ends of gypsum wallboard around the entire perimeter of the fire rated wall assembly.

AD/PHV 120-02

 

Back 

Head of Wall - Application Designs and Reference Guide

Movement Capabilities

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

Class II & III

25% Compression or Extension

2

Floor – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D Firebarrier

 SprayAcrylic _____________

Rock Wool Mfg.

Mineral Wool

Min. 1/8 inch. wet  thickness, sprayed on each side of the wall. And ½” overlap

_____________

See design for installation instructions.

HW-D-0468

 

Class II & III

18.75% Compression or Extension

2

Floor – Concrete on Steel Deck

 

(Spray Fireproofing on Deck Optional)

 &

Wall -Gypsum

Board

A/D Firebarrier

SprayAcrylic

_____________

Rock Wool Mfg.

Delta Board

Mineral Wool

Min. 1/8 inch wet  thickness, sprayed on each side of the wall. Overlap a min. 1inch onto gypsum board and steel deck. When Spray Fireproofing is applied overlap a min. 2” on both sides onto fireproofing

_____________

Nom. 4” cut U shape with overall height & width equal to notched opening in wall, min compression 50%

HW-D-0471

 

CONCRETE CONSTRUCTION

Class II

20% Compression or Extension

2

3 5/16”

Floor – Concrete or Precast

&

Wall – Concrete or Concrete Block

A/D Firebarrier

 Silicone _____________

A/D Firebarrier

Mineral Wool

Min. 1/4 inch thick applied within the joint, flush with each surface of wall.

------------------------------------

Inserted into opening between the top of the wall and underside of floor, recessed Ό” on both sides of wall

HW-D-1017

 

Class II

18.75% Compression or Extension

2

Floor  or Roof – Concrete on Steel Deck

 &

Wall –Concrete or Concrete Block

A/D Firebarrier

 Seal NS _____________

A/D Firebarrier

Mineral Wool

Min. 1/8 inch wet  thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto concrete wall and steel deck.

----------------------------------------

Inserted into opening between the top of the wall and steel floor deck flush with both sides of wall.

HW-D-0250

 

Class II

14% Compression or Extension

2

3 ½”

Floor – Concrete

&

Wall – Concrete or Concrete Block

A/D Firebarrier

 Seal NS _____________

A/D Firebarrier

Mineral Wool

Min. 1/8 inch wet thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto the bottom surface of the floor and each side of wall

_____________

Inserted into opening between the top of the wall and floor flush with both sides of wall

HW-D-1029

 