A/D FIREBARRIER FIRESTOP SYSTEMS |
|||||||
Head of Wall - Application Designs and Reference Guide |
|||||||
|
Movement Capablilites |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D Firebarrier Product Required |
Application Thickness |
System No. |
|
CONCRETE/CONCRETE ON STEEL DECK/GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
Class II 20% Compression or Extension |
1 & 2 |
1 |
Floor Concrete
|
A/D Firebarrier Acrylic _____________ Rock Wool Mfg Delta Board or Foam bakker rod |
Min. 1/2 inch thick, installed on each side of the wall. _____________ Min 3/4 thick mineral wool t, compressed 50% & firmly packed in gap on top of wallboard & bottom of floor,on both sides |
|
|
|
Class II 20% Compression or Extension |
1 |
1 |
Floor Concrete on Steel Deck & Wall -Gypsum Board |
A/D Firebarrier Seal NS _____________ A/D Firebarrier Mineral Wool |
Min. 1/8 inch wet thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto gypsum board and steel deck. _____________ Length equal to the overall width of the wall. Additional 5/8 inch wide strips to fill gap between gypsum board & bottom of steel floor units on both sides of wall. |
||
|
Class II 18.75% Compression or Extension |
2 |
1 |
Floor or Roof Concrete on Steel Deck & Wall -Gypsum Board |
A/D Firebarrier Seal NS _____________ A/D Firebarrier Mineral Wool |
Min. 1/8 inch wet thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto gypsum board and steel deck. _____________ Length equal to the overall width of the wall. Additional 1 Ό inch wide strips to fill gap between gypsum board & bottom of steel floor units on both sides of wall. |
||
|
N.A. |
1 & 2 |
N.A. |
Floor Concrete & Wall -Gypsum Board |
A/D Firebarrier Seal NS |
Min, bead diameter of 3/8 cauked into the corner between ends of gypsum wallboard around the entire perimeter of the fire rated wall assembly. |
||
|
N.A. |
1 |
5/8 |
Floor Concrete on Steel Deck & Wall -Gypsum Board |
A/D Firebarrier Silicone _____________ A/D Firebarrier Mineral Wool |
Min. 1/4 and 5/8 thickness (see fire test design) _____________ Fitted within fluted openings with a Ό recess from the wall. |
||
|
N.A. |
2 |
5/8 |
Floor Concrete on Steel Deck & Wall -Gypsum Board |
A/D Firebarrier Silicone _____________ A/D Firebarrier Mineral Wool |
Min. 1/4 and 1 thickness (see fire test design) _____________ Fitted within fluted openings with a Ό recess from the wall. |
||
|
N.A. |
1 & 2 |
N.A. |
Floor Concrete & Wall -Gypsum Board |
A/D Firebarrier Silicone |
Min, bead diameter of 3/8 cauked into the corner between ends of gypsum wallboard around the entire perimeter of the fire rated wall assembly. |
|
|
Head of Wall - Application Designs and Reference Guide |
|||||||
|
Movement Capabilities |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D Firebarrier Product Required |
Application Thickness |
System No. |
|
|
Class II & III 25% Compression or Extension |
2 |
3 |
Floor Concrete on Steel Deck & Wall -Gypsum Board |
A/D Firebarrier SprayAcrylic _____________ Rock Wool Mfg. Mineral Wool |
Min. 1/8 inch. wet thickness, sprayed on each side of the wall. And ½ overlap _____________ See design for installation instructions. |
|
|
|
Class II & III 18.75% Compression or Extension |
2 |
2 |
Floor Concrete on Steel Deck
(Spray Fireproofing on Deck Optional) & Wall -Gypsum Board |
A/D Firebarrier SprayAcrylic _____________ Rock Wool Mfg. Delta Board Mineral Wool |
Min. 1/8 inch wet thickness, sprayed on each side of the wall. Overlap a min. 1inch onto gypsum board and steel deck. When Spray Fireproofing is applied overlap a min. 2 on both sides onto fireproofing _____________ Nom. 4 cut U shape with overall height & width equal to notched opening in wall, min compression 50% |
|
|
CONCRETE CONSTRUCTION |
|||||||
|
Class II 20% Compression or Extension |
2 |
3 5/16 |
Floor Concrete or Precast & Wall Concrete or Concrete Block |
A/D Firebarrier Silicone _____________ A/D Firebarrier Mineral Wool |
Min. 1/4 inch thick applied within the joint, flush with each surface of wall. ------------------------------------ Inserted into opening between the top of the wall and underside of floor, recessed Ό on both sides of wall |
|
|
|
Class II 18.75% Compression or Extension |
2 |
1 |
Floor or Roof Concrete on Steel Deck & Wall Concrete or Concrete Block |
A/D Firebarrier Seal NS _____________ A/D Firebarrier Mineral Wool |
Min. 1/8 inch wet thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto concrete wall and steel deck. ---------------------------------------- Inserted into opening between the top of the wall and steel floor deck flush with both sides of wall. |
|
|
|
Class II 14% Compression or Extension |
2 |
3 ½ |
Floor Concrete & Wall Concrete or Concrete Block |
A/D Firebarrier Seal NS _____________ A/D Firebarrier Mineral Wool |
Min. 1/8 inch wet thickness, sprayed or brushed on each side of the wall. Overlap a min. ½ inch onto the bottom surface of the floor and each side of wall _____________ Inserted into opening between the top of the wall and floor flush with both sides of wall |
|
|