Joints Floors |
|||||||
|
Movement Capabilities |
Rating (h) |
Max Size Joint |
Floor or Wall System |
A/D Firebarrier Product Required |
Application Thickness |
System No. |
|
CONCRETE CONSTRUCTION |
|||||||
|
Class II 20% Compression or Extension |
3 |
Nom. 3 5/16” |
Floor Concrete |
A/D Firebarrier Silicone A/D Firebarrier Mineral Wool |
Min 1/4 inch thick applied within joint, flush with top surface of floor Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 33% recessed from top surface of floor |
|
|
|
Class II 14% Compression or Extension |
2 |
Nom. 3 ½” |
Floor Concrete |
A/D Firebarrier Seal NS A/D Firebarrier Mineral Wool |
Min 1/8 inch wet thickness sprayed or brush on top surface of floor covering mineral wool & lapping a min ½ “ onto concrete floor Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 30% recessed from top surface of floor |
|
|
|
|
2 |
2”.
|
Floor Concrete |
A/D Firebarrier Silicone or Silicone S/L A/D Firebarrier Mineral Wool |
Min 1/4 inch thick applied within the joint, flush with top surface of floor Min. 4 inch thick mineral wool installed edge first into joint, compressed min 30% recessed from top surface of floor |
|
|
|
|
1 |
Max 1” |
Floor Concrete |
A/D Firebarrier Silicone or Silicone S/L Polyurethane foam Backer Rod |
Min 1 inch thick applied within the joint, flush with top surface of floor Min. 1 inch diameter open or closed cell polyurethane foam backer rod , recessed from top surface to assure required thickness of caulk |
|
|
| Joints Walls | |||||||
|
Class II 20% Compression or Extension |
3 |
Nom. 3 5/16” |
Wall / Floor Concrete |
A/D Firebarrier Silicone A/D Firebarrier Mineral Wool |
Min 1/4 inch thick applied within joint, flush with top surface of floor Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 33% recessed from top surface of floor |
||
|
Class II 14% Compression or Extension |
2 |
Nom. 3 1/2” |
Wall / Floor Concrete |
A/D Firebarrier Silicone A/D Firebarrier Mineral Wool |
Min 1/4 inch thick applied within joint, flush with top surface of floor Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 33% recessed from top surface of floor |
||
|
|
1 |
Max 2” |
Wall / Floor Concrete |
A/D Firebarrier Seal NS A/D Firebarrier Mineral Wool |
Min 1/8 inch thick sprayed or brushed to bottom or top surface of joint, cover mineral wool & overlap onto concrete surface a min of ½” on each side of joint Min 2 1/2 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 30% flush with top surface of floor |
||