A/D FIREBARRIER FIRESTOP SYSTEMS

Joints Floor - Application Designs and Reference Guide

Movement Capabilities

Rating

 (h)

Max Size

Joint

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE  CONSTRUCTION

Class II

20%

Compression or Extension

3

Nom.

3 5/16”

Floor Concrete

A/D Firebarrier

Silicone

A/D Firebarrier

Mineral Wool

Min 1/4 inch thick applied within joint, flush with top surface of floor

Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 33% recessed from top surface of floor

FF-D- 1023

 

Class II

14%

Compression or Extension

2

Nom.

3 ½”

Floor Concrete

A/D Firebarrier

Seal NS

A/D Firebarrier

Mineral Wool

Min 1/8 inch wet thickness sprayed or brush on top surface of floor covering mineral wool & lapping a min ½ “ onto concrete floor

Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 30% recessed from top surface of floor

FF-D- 1032

 

 

2

2”.

 

Floor Concrete

A/D Firebarrier

Silicone or Silicone S/L

A/D Firebarrier

Mineral Wool

Min 1/4 inch thick applied within the joint, flush with top surface of floor

Min. 4 inch thick mineral wool installed edge first into joint, compressed min 30% recessed from top surface of floor

FF-S-0031

 

 

1

Max

1”

Floor Concrete

A/D Firebarrier

Silicone or Silicone S/L

Polyurethane foam Backer Rod

Min 1 inch thick applied within the joint, flush with top surface of floor

Min. 1 inch diameter open or closed cell polyurethane foam backer rod , recessed from top surface to assure required thickness of caulk

FF-S-0032

 

 

 

 

 

 

 

 

 

 

  

 

A/D FIREBARRIER FIRESTOP SYSTEMS

Joints Wall- Application Designs and Reference Guide

Movement Capabilities

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

Class II

20%

Compression or Extension

3

Nom.

3 5/16”

Wall / Floor Concrete

A/D Firebarrier

Silicone

A/D Firebarrier

Mineral Wool

Min 1/4 inch thick applied within joint, flush with top surface of floor

Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 33% recessed from top surface of floor

FW-D- 1019

 

Class II

14%

Compression or Extension

2

Nom.

3 1/2”

Wall / Floor Concrete

A/D Firebarrier

Silicone

A/D Firebarrier

Mineral Wool

Min 1/4 inch thick applied within joint, flush with top surface of floor

Min 4 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 33% recessed from top surface of floor

FW-D- 1029

 

 

1

Max

2”

Wall / Floor Concrete

A/D Firebarrier

Seal NS

A/D Firebarrier

Mineral Wool

Min 1/8 inch thick sprayed or brushed to bottom or top surface of joint, cover mineral wool & overlap onto concrete surface a min of ½” on each side of joint

Min 2 1/2 inch thick mineral wool installed edge first into joint, parallel with joint direction compressed min 30% flush with  top surface of floor

FW-S-0005

 

               

  