Plumbing - Application Designs and Reference Guide

STEEL & IRON PIPE

 

 

 

 

 

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE  CONSTRUCTION

12 " diameter or

Smaller - see system for options

3

0" to 2"

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D Firebarrier

 Intumescent Sealant

_____________

A/D Firebarrier

Mineral Wool

Min. 1/4 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 1/4 inch thick packed into opening  (wall both sides)

C-AJ- 1557

 

24 " diameter

or smaller

3

0" to 1 1/8”

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

Silicone

-----------------

A/D Firebarrier

Mineral Wool

Min. 1/2 inch thick within  annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening  (wall both sides)

C-AJ-1497

 

8 " diameter

or smaller

3

0" to 1 7/8”

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block

Precast  (hollow core) Conc.

 

A/D Firebarrier

 Intumescent  Sealant

_____________

A/D Firebarrier

Mineral Wool

Min. 1 inch thick within  annulus flush with both surfaces of  floor or wall

_____________

Min. 1” inch thick packed into each side of opening floor & wall, recessed to take sealant

C-AJ-1561

 

8 " diameter

or smaller

2

0" to 3 7/8"

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

Silicone

------------------

A/D Firebarrier

Mineral Wool

Min. 1/4 inch thick within  annulus flush with top or bottom  of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening  (wall both sides)

C-AJ-1229

 

GYPSUM WALLBOARD CONSTRUCTION

12 " diameter

or smaller

1 & 2

0" to 1 7/8"

annulus

Wall -Gypsum

Board as rated for 1 & 2 hr

A/D Firebarrier

 Intumescent Sealant

Min.1/2” or 5/8” inch thick within annulus, flush both surfaces of wall

Foam Bakker optional

W-L-1416

 

8 " diameter

or smaller

2

0" to 7/8”

annulus

Wall -Gypsum

Board

A/D Firebarrier

 Intumescent

Sealant or Acrylic

_____________

A/D Firebarrier

Mineral Wool

Min. 1/2 inch thick within annulus, flush both surfaces of wall

_____________

Min. 1/ 2 inch thick packed into opening both sides of wall

W-L-1417

 

2 " diameter

or smaller

1 & 2

0" to 1-7/8"

annulus

Wall -Gypsum

Board

A/D Firebarrier

Silicone

Min.5/8 inch thick within annulus, flush both surfaces of wall

W-L-1198

 

WOOD CONSTRUCTION

8 " diameter

or smaller

1 & 2

0" to 7/8"

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier

 Intumescent Sealant

Min.5/8 inch thick within annulus on top at floor

Min. 5/8 inch thick within annulus on bottom surface ceiling- ½” crown

F-C-1149

 

6 " diameter

or smaller

1

1/4"

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier

Silicone

Min.1 1/8 inch thick within annulus on top at floor

Min. 1/2 inch thick within annulus on bottom surface ceiling

F-C-1011

 

4 " diameter

or smaller

1

0” to 7/8”

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier Intumescent sealant

Foam Bakker Rod

Min.1/2 inch thick within annulus on top at floor

Min. 1/2 inch thick within annulus on bottom surface ceiling and Ό” at point of contact

Foam Bakker Rod

F-C-1150

 

                                  top of page

COPPER (Pipe & Tube)

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

6 " diameter or

Smaller - see system for options

3

0" to 2"

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D Firebarrier

 Intumescent Sealant

_____________

A/D Firebarrier

Mineral Wool

Min. 1/4 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 1/4 inch thick packed into opening  (wall both sides)

C-AJ-1557

 

6 " or

smaller

3

0" to 1 1/8”

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

Silicone

-----------------

A/D Firebarrier

Mineral Wool

Min. 1/2 inch thick within  annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening  (wall both sides)

C-AJ-1497

 

4” or

 smaller

3

0" to 2”

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

 

A/D Firebarrier

 Intumescent Sealant

_____________

A/D Firebarrier

Mineral Wool

Min. 3/4 inch thick within  annulus flush with top of  floor or both surfaces of wall

_____________

Min. 3 3/4 inch thick packed into opening  (wall both sides)

C-AJ-1557

 

4” or

       smaller

2

0" to 7/8 ”

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D Firebarrier

 Intumescent Sealant

Foam backer rod

 

Min. 1/2 inch thick within  annulus flush with top of  floor or both surfaces of wall

 

C-AJ-1557

 

GYPSUM WALLBOARD CONSTRUCTION

4 " or

smaller

1 & 2

0" to 1 7/8”

annulus

Wall -Gypsum

Board

As per F rating of wall

A/D Firebarrier

 Intumescent Sealant

Min.1/2” or 5/8” inch thick within annulus, flush both surfaces of wall and its rating

Foam Bakker Rod Optional

W-L-1416

 

4 " or

smaller

2

0" to 7/8"

annulus

Wall -Gypsum

Board

A/D Firebarrier

 Intumescent

Sealant and Acrylic

_____________

A/D Firebarrier

Mineral Wool 

Min. 1/2 inch thick within annulus, flush both surfaces of wall

_____________

Min. 1/2 inch thick packed into opening both sides of wall

W-L-1417

 

2 " or

smaller

1 & 2

0" to 1-7/8"

annulus

Wall -Gypsum

Board

A/D Firebarrier

Silicone

Min.5/8 inch thick within annulus, flush both surfaces of wall

W-L-1198

 

WOOD CONSTRUCTION

4 " or

smaller

1

1/4"

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier

Silicone

Min.1 1/8 inch thick within annulus on top at floor

Min. 1/2 inch thick within annulus on bottom surface ceiling

F-C-1011

 

4 " diameter

or smaller

1

0” to 7/8”

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier Intumescent sealant

Foam Bakker Rod

Min.1/2 inch thick within annulus on top at floor

Min. 1/2 inch thick within annulus on bottom surface ceiling and Ό” at point of contact

Foam Bakker Rod

F-C-1150

 

  top of page

PLASTIC & GLASS PIPE

Max. Size

Penetration

Diameter

Rating

(h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

3” PVC, CPVC

or smaller

2

3/4" to 7/8”

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D Firebarrier

Intumescent Sealant   _____________

Foam backer rod optional

Min. 2 inch thick within annulus flush with top of floor  or both surfaces of wall

_______________   

optional

C-AJ-2581

 

3/4 “ PEX

 

2

1/4 “ to 7/16”

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D Firebarrier

Intumescent Sealant    _____________

Foam backer rod optional

Min. 1/2 inch thick within annulus flush with both surfaces of floor or wall

_______________   

Foam backer rod optional

C-AJ-2582

 

6,PVC, CPVC

or smaller

2

0" to 3/8"

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

 Silicone ____________

A/D Firebarrier

Collar

Min. 3/8 inch thick within annulus flush with top of floor or both surfaces of wall

_______________   

 

C-AJ-2186

 

4,PVC, CPVC

or smaller

2

0"to 1/2"

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

 

A/D Firebarrier Collar

 

 

C-AJ-2187

 

2,PVC, CPVC

or smaller

2

3/4" to

1-3/8"

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

 Silicone _____________

A/D Firebarrier

Mineral Wool

Min. 1 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into  opening  (wall both sides)

C-AJ-2150

 

4,PVC, CPVC,

or smaller

1

0” to 11/2” nom.

annulus

Floor - Concrete

(4 1/2" min. thick Concrete)

 

A/D Firebarrier

Intumescent sealant

Foam Bakker optional  

 

Min. ½” inch thick within annulus flush with top of  floor  add ½” crown

Foam Bakker  Optional

 

F-A-2168

 

2. PVC, CPVC, ABS

 or smaller. 1" PEX or smaller

2

5/16" nom annulus

Wall - Concrete

 

A/D Firebarrier

Wrap Strip

1" wide Wrap Strip

W-J-2128

 

2. PVC, ABS

 or smaller

. 1” PEX or smaller

1 & 2

5/16” to 5/8” range of annular

Wall – Concrete

 

A/D Firebarrier

Wrap Strip

1)       0 to 2” PVC – 1” wide Wrap Strip- 2 layers, 2 hr rating

2) 0 to 1.5” PVC- 1” wide Wrap Strip – 1 layer, 1 hr rating

  3) 0 to 1” PEX – 1” Wrap Strip

      1 layer, 1 hr rating

   4) 2” ABS – 2” Wrap Strip

       2 hr fating

 

W-J-2141

 

 

PLASTIC & GLASS PIPE

 

Max. Size

Penetration

Diameter

Rating

(h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

GYPSUM WALLBOARD CONSTRUCTION

6, PVC, CPVC

or smaller

2

1/4"

annulus

Wall -Gypsum

Board

A/D Firebarrier

 Silicone ___________

A/D Firebarrier

Collar

Min.1 inch thick within annulus flush on  both surfaces of wall

_______________   

 

WL - 2155

 

2. PVC, CPVC, ABS

 or smaller.

 1" PEX or smaller

2” CPVC Flowguard Gold & Blazemaster

1 & 2

Ό” to 1 3/8” nom annulus

Wall -Gypsum

Board

 

A/D Firebarrier

Intumescent sealant

Min.5/8 inch thick within annulus flush on  both surfaces of wall

Plus a Ό” crown around  

 

W-L-2486

 

2,PVC, CPVC

or smaller

2

1/2" to

1-1/8"

nom annulus

 

Wall -Gypsum

Board

A/D Firebarrier

 Silicone _____________

A/D Firebarrier

Mineral Wool

Min. 3/4 inch thick within annulus, flush with both ends

_____________

Min. 2 inch thick packed into opening on each side of wall

W-L-2157

 

Ύ” PEX or smaller

1 & 2

Ό” to 3/8”

Wall -Gypsum

Board

A/D Firebarrier

Intumescent sealant

Min.1/2 inch thick within annulus flush on  both surfaces of wall

Foam Bakker Optional, required for 2 hr F

W-L-2487

 

2, PVC,

CPVC, ABS

 or smaller

3 & 4

½” to 1 5/8”

Wall -Gypsum

Board

As per rated wall system

A/D Firebarrier

 Intumescent sealant _____________

A/D Firebarrier

Mineral Wool

Min.2 inch thick within annulus flush on  both surfaces of wall

1 ½” Mineral Wool

 

W-L-2489

 

WOOD CONSTRUCTION

4,PVC, CPVC

ABS  or

smaller

1

1/2" nom annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier

 Silicone _____________

A/D Firebarrier

Collar

Fill annulus Space to max  extent & 1/4 " crown on top

F-C-2194

 

4, ABS, PVC, CPVC

** water closet

Config C

1

0” TO ½”

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier

 Intumescent Sealant & Acrylic

Foam Bakker Optional

Min. 1/2 inch thick within annulus  (top &  bottom) and Ό” crown

Foam Bakker Optional

F-C-2346

 

4, PVC,

CPVC, ABS

 or smaller

2” PEX

1

0” to 1/2"

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D Firebarrier

 Intumescent Sealant & Acrylic

Foam Bakker Optional

Min. 3/4 inch thick within annulus – top

Min. 5/8 inch thick within annulus - bottom

F-C-2347

 

  top of page

INSULATED  PIPE

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

6, Copper,

steel or smaller

1 1/2

0" to 4"

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

 Silicone or

Silicone S L

_____________

A/D Firebarrier

Mineral Wool

Min. 1/4 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening (wall both sides)

CAJ - 5064

 

8 “ Steel, Iron

4 “ copper or smaller

3

0" to 1”

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

 Intumescent Sealant

_____________

A/D Firebarrier

Mineral Wool

Min. 1/2 inch thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening (wall both sides)

C-AJ-1560

 

3” Copper,

steel or smaller

3   

Ό”

annulus

Floor – Concrete

Wall – Concrete

 or Concrete Block

A/D Firebarrier

 Silicone or

Silicone S L

A/D Firebarrier

Mineral Wool

Min. ½ inch thick within annulus flush with top of floor or both surfaces of wall

Min. 4 inch thick packed into opening (wall both sides)

C-AJ- 5027

 

8” Steel, Iron

4 “ Copper

2

Steel/iron

½” to 1”

Copper

3/8” to 1 ½”

 

 

 

Floor – Concrete

Wall – Concrete

 or Concrete Block

A/D Firebarrier

Intumescent or Acrylic

A/D Firebarrier

Mineral Wool

Min. 1/2 inch thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening (wall both sides)

C-AJ-5303

 

2 “ Steel, Iron

2 “ Copper

2

1/8 “ to Ό”

________

Flexible AB/PVC foam tube insulation

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D Firebarrier

 Intumescent Sealant

_____________

Foam backer rod

Min. 1 inch thick within annulus flush with top of floor or both surfaces of wall with Ό” crown

_____________

Foam backer rod firmly packed into opening

C-AJ- 5304

 

2”  PVC, CPVC or smaller

2

7/8”

1”  Insul ASJ

Floor – Concrete

Wall – Concrete

 or Concrete Block

A/D Firebarrier

 Intumescent Sealant

_____________

A/D Firebarrier

Mineral Wool

Min. 1 inch thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 3 ½” inch thick packed into opening (wall both sides)

C-AJ-5306

 

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

GYPSUM WALLBOARD & WOOD CONSTRUCTION

8” Steel, iron,

4” copper/tubing or smaller

Config A

2

Ό” to 1 Ό”

Wall -Gypsum

Board Wood

A/D Firebarrier

 Intumescent sealant

Foam Bakker Optional

Min 5/8 inch thick within annulus, flush both surfaces of wall plus a 3/8” crown

W-L - 5267

 

4” Steel

or smaller

4” Copper or smaller

Armaflex

1 & 2

0” to 1 3/8”

annulus

Wall -Gypsum

Board Wood

A/D Firebarrier

 Intumescent sealant

Min 5/8 inch thick within annulus, flush both surfaces of wall -  Ό” bead to pipe insulation/wallboard at point of contact

W-L-5266

 

3" Copper,

steel or smaller

1 & 2

1/4"

annulus

Wall -Gypsum

Board Wood

A/D Firebarrier

Silicone

1 hour rating

Min. 1/2 inch thick flush both surfaces of wall

_______________

2 hour rating

Min. 1 inch thick flush both  surfaces of wall

W-L-5031

 

WOOD CONSTRUCTION

1” Steel

and

Copper or smaller

+ ½” Armaflex

See Design re PVC, CPVC & cables

1 & 2

1/4” to 1 ½”

annulus

Floor/Wall-

 wood/gypsum

A/D Firebarrier

 Intumescent sealant

Foam Bakker Optional

(2 hr) Min 3/4 inch thick within annulus, flush with top of floor

 (1 hr) Min 5/8 inch thick within annulus, flush with top of floor –

Add material forced in annular space around penetrants & 3/16” crown 

F-C-8041

 

4" Copper,

steel or smaller

1   

1/4"

annulus

Floor/Wall-

 wood/gypsum

A/D Firebarrier

Silicone

Min.1 1/8 inch thick within  annulus on top at floor

Min. 1/2 inch thick within  annulus on bottom surface ceiling

F-C-5007

 

                                          top of page

DUCTS (Mechanical)

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

14" X 18 "

28 gauge or heavier

3

320 sq. in.-

max dimension

20"

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

Intumescent

Sealant

_____________

Foam backer rod (optional)

Min. 1/2 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 3 1/2 inch thick packed into opening (wall both sides)

C-AJ-7124

 

18 “ X 6”

min. 28 gauge or heavier

2

160 sq. in.-

max dimension

20”

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

Intumescent

Sealant

_____________

A/D Firebarrier

Mineral Wool

Min. 1 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 1 inch thick packed into opening (wall both sides)

C-AJ-7125

 

8” diameter or smaller

Steel vent duct, 26 gauge or heavier

2

Ό”

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

Intumescent sealant or Acrylic

_____________

A/D Firebarrier

Mineral Wool

Min. 1/4 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 Ό”  inch thick packed into opening (wall both sides)

C-AJ-7126

 

GYPSUM WALLBOARD CONSTRUCTION

38" X 12"

min. 24 gauge

2

800 sq. in.-

max dimension

40"

Wall -Gypsum

Board

A/D Firebarrier

Silicone

Min. 1/4 inch thick within annulus flush both surfaces of wall

W-L-7073

 

30” X 30”

min 24 gauge

 

1 & 2

992 sq in – max dimension 32 “

Wall-gypsum Board

A/D Firebarrier

Intumescent sealant & Acrylic

Min 5/8” thick both sides of wall,

Foam Bakker Rod for 2 hr F

W-L-7166

 

16 “ Diameter or smaller

 Galv  Steel Duct

24 Gauge or

Heavier

8” X 8” Rectangular

1 & 2

0” to 1 “ annulus

-------------

½” for rectangular

Wall gypsum Board

A/D Firebarrier

Intumescent sealant

Min 1/2” thick caulk within annulus, flush both surfaces of wall – when annular exceeds ½”  fill with min. thickness of 5/8”.

 For round ducts add 3/8” crown around.

W-L-7165

 

WOOD CONSTRUCTION

4” diameter duct

30 ga or heavier

2

Max 6” opening, nom. Annular 1”

Floor/Wall-

 wood/gypsum

A/D Firebarrier

 Intumescent sealant

 

5/8” thick flush with top of floor and bottom surface of ceiling

F-C-7044

 

                                                         top of page

MULTIPLE PENETRATIONS

Type of

Penetration

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

3 “Steel, Iron, Copper,

 1” Pipe Insulation

Cables & cable tray 24” X 4”

3

288 sq/in

Floor - Concrete

Wall - Concrete

 or Concrete Block

Pre-cast concrete

A/D Firebarrier

Mortar

Min. 3 inch thick flush with top of

floor & both sides of wall

C-AJ-8029

 

3 “Steel, Iron, Copper,

 1” Pipe Insulation

Cables & cable tray 24” X 4”

3

288 sq/in

Floor - Concrete

Wall - Concrete

 or Concrete Block

Pre-cast concrete

A/D Firebarrier

 Silicone or Silicone SL

_____________

A/D Firebarrier

Mineral Wool      

Min. 1/4 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening  (wall both sides)

C-AJ-8028

 

Copper &

Insulated

2

128 sq/in

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D Firebarrier

 Silicone or Silicone SL

_____________

A/D Firebarrier

Mineral Wool      

 

Min. 1/4 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening  (wall both sides)

C-AJ-8080

 

   

 

4” Steel,iron,

Conduit

2” Copper pipe & tubing

  

 

 

 

3

  112.5 sq/in

_________

Annulus non-insul

0” to 3 3/8” & periphery

Annulus for

Insulated

½” to 1”

Annulus between  all penetrants ½” to 5/”

   

 

 

Floor - Concrete

Wall - Concrete

 or Concrete Block

 

A/D Firebarrier

Intumescent  sealant

_____________

A/D Firebarrier

Mineral Wool

 

 

 

Min. 1/2 inch thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 4 inch thick packed into opening  (wall both sides)

 

 

 

C-AJ-8184

 

 

Steel or Copper Pipe

  

3

  

24 sq. ft.

 Floor / Wall /

Concrete

  A/D Firebarrier

Mortar

  Fill opening to min. depth 3 inches

AD/PHV

180-01

 

 

 

Ύ” Steel, iron,conduit, copper & copper tubing & cables

(foam insul on one pipe or tube)

 

 

2

 

 

 

3 ½” max opening with ½” between pipes & cables

 

 

 

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

 

 

A/D Firebarrier

Intumescent Sealant

A/D Firebarrier Mineral Wool

Min 1 inch thick within annulus, flush top of floor, both surfaces of wall-force sealant  into interstices to max possible, when floor hollow core, fill both sides of floor flush

Min 3 1/2" inch thick packed into opening and into interstices, with hollow core pack both surfaces of floor

 

 

 

 

 

C-AJ-8183

 

CONCRETE CONSTRUCTION

 

Type of

Penetration

Rating

 (h)

Max Size

Opening

Floor or Wall

System

A/D Firebarrier

Product Required

Application

Thickness

System No.

 

 

 

1” PEX- max 5 tubes bundled

 

 

2

 

 

0” to

2  7/8”

 

 

Floor - Concrete

Wall - Concrete

 or Concrete Block

 

A/D Firebarrier

Intumescent Sealant

A/D Firebarrier Mineral Wool

 

Min 1 inch thick within annulus, flush top of floor, both surfaces of wall-force sealant  around tubing to max possible, point of contact, ½” bead at tubing & concrete

 

Min 3 ½” thick packed into

opening ( wall both sides)

 

 

 

C-AJ-2583

 

GYPSUM WALLBOARD CONSTRUCTION

1” Steel , iron, copper

+3/4” Armaflex

(foam Insul)

+ cables

1 & 2

½” to Ύ”

Wall -Gypsum

Board

 

 

A/D Firebarrier

Intumescent Sealant

 

Min. 1/2 inch flush with

 both surfaces of wall added material into intersties with a1/4” crown

 

W-L-8075

 

4" Steel, Iron, Copper or smaller

Cables & cable tray max

18” X 3.5 “

1 & 2

1.9 sq. ft.

Wall -Gypsum

Board

A/D Firebarrier

Mortar &

A/D Firebarrier Silicone

2 hr- min.4 1/2 inch flush with

 both surfaces of wall

__________________

1 hr - min. 3 1/2 inch flush with

both surfaces of wall

WL - 8005

 

 

 

 

 

 

 

 

 

 

 

  top of page