A/D FIREBARRIER FIRESTOP SYSTEMS |
|||||||||
Sprinkler - Application Designs and Reference Guide |
|||||||||
STEEL & IRON PIPE |
|
|
|
|
|
||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
||
|
CONCRETE CONSTRUCTION |
|||||||||
|
12" diameter or Smaller - see system for options |
3 |
0" to 2" annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. ¼” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4¼” thick packed into opening (wall both sides) |
|
|||
|
24" diameter or smaller |
3 |
0" to 1-1/8” annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Mineral Wool |
Min. ½” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
|
|||
|
8" diameter or smaller |
3 |
0" to 1-7/8” annulus |
Floor - Concrete Wall - Concrete Concrete Block Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 1” thick within annulus flush with both surfaces of floor or wall _____________ Min. 1” thick packed into each side of opening floor & wall, recessed to take sealant |
|
|||
|
8" diameter or smaller |
2 |
0" to 3-7/8" annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone ______________ A/D FIREBARRIER Mineral Wool |
Min. ¼” thick within annulus flush with top or bottom of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
|
|||
|
GYPSUM WALLBOARD CONSTRUCTION |
|||||||||
|
8" diameter or smaller |
2 |
0" to 7/8” annulus |
Wall -Gypsum Board |
A/D FIREBARRIERIntumescent Sealant or Acrylic _____________ A/D FIREBARRIER Mineral Wool |
Min. ½” thick within annulus, flush both surfaces of wall _____________ Min. ½” thick packed into opening both sides of wall |
|
|||
|
2" diameter or smaller |
1 & 2 |
0" to 1-7/8" annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone |
Min.5/8” thick within annulus, flush both surfaces of wall |
|
|||
|
12" diameter or smaller |
1 & 2 |
0" to 1-7/8" annulus |
Wall -Gypsum Board as rated for 1 & 2 hr |
A/D FIREBARRIER Intumescent Sealant |
Min. ½” or 5/8” inch thick within annulus, flush both surfaces of wall Foam Backer optional |
|
|||
|
|
|||||||||
WOOD CONSTRUCTION |
|||||||||
|
6" diameter or smaller |
1 |
1/4" annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Silicone |
Min.1-1/8” thick within annulus on top at floor Min. ½” thick within annulus on bottom surface ceiling |
|
|||
|
8" diameter or smaller |
1 & 2 |
0" to 7/8" annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant |
Min.5/8” thick within annulus on top at floor Min. 5/8” thick within annulus on bottom surface ceiling- ½” crown |
|
|||
|
4" diameter or smaller |
1 |
0” to 7/8” |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent sealant Foam Backer Rod |
Min. ½” thick within annulus on top at floor Min. ½“ thick within annulus on bottom surface ceiling and ¼” at point of contact Foam Backer Rod |
|
|||
A/D FIREBARRIER FIRESTOP SYSTEMS |
|||||||
Sprinkler - Application Designs and Reference Guide |
|||||||
PLASTIC PIPE |
|
|
|
|
|
|
|
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Floor or Wall System |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
CONCRETE CONSTRUCTION |
|||||||
|
3”, PVC, CPVC or smaller |
2 |
¾" to 7/8” annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Foam backer rod optional |
Min. 2” thick within annulus flush with top of floor or both surfaces of wall _______________ optional |
|
|
|
6”, PVC, CPVC or smaller |
2 |
0" to 3/8" annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Collar |
Min. 3/8 inch thick within annulus flush with top of floor or both surfaces of wall _______________
|
|
|
|
4”, PVC, CPVC or smaller |
2 |
0"to ½" annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Collar |
|
|
|
|
2”, PVC, CPVC or smaller |
2 |
¾" to 1-3/8" annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Mineral Wool |
Min. 1” thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 4” thick packed into opening (wall both sides) |
|
|
|
4”, PVC, CPVC, or smaller |
1 |
0” to 1½” nom. annulus |
Floor - Concrete (4½" min. thick Concrete) |
A/D FIREBARRIER Intumescent Sealant Foam Backer optional |
Min. ½” inch thick within annulus flush with top of floor add ½” crown Foam Backer optional |
|
|
|
|
|
|
|
|
|
|
|
GYPSUM WALLBOARD CONSTRUCTION |
|||||||
|
2” PVC, CPVC, ABS or smaller. 1" PEX or smaller 2” CPVC Flowguard Gold & Blazemaster |
1 & 2 |
¼” to 1 3/8” nom annulus |
Wall -Gypsum Board |
A/D FIREBARRIERIntumescent Sealant |
Min.5/8” thick within annulus flush on both surfaces of wall Plus a ¼” crown around
|
|
|
|
6”, PVC, CPVC or smaller |
2 |
¼" annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIERCollar |
Min.1” thick within annulus flush on both surfaces of wall _______________
|
|
|
|
2”, PVC, CPVC or smaller |
2 |
½" to 1-1/8" nom annulus
|
Wall -Gypsum Board |
A/D FIREBARRIERSilicone _____________ A/D FIREBARRIER Mineral Wool |
Min. ¾” thick within annulus, flush with both ends _____________ Min. 2” thick packed into opening on each side of wall |
|
|
WOOD CONSTRUCTION |
|||||||
|
4”, PVC, CPVC ABS or smaller |
1 |
½" nom annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Collar |
Fill annulus space to max extent & ¼" crown on top |
|
|
|
4”, PVC, CPVC, ABS or smaller 2” PEX |
1 |
0” to ½" annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant & Acrylic Sealant Foam Backer Optional |
Min. ¾” thick within annulus – top Min. 5/8” thick within annulus - bottom |
|
|