HVAC - Application Designs and Reference Guide |
|||||||
|
DUCTS (All ULC and UL Fire Tests for Ducts are tested without dampers) |
|
|
|||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size of Perimeter Gap |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
CONCRETE CONSTRUCTION |
|||||||
|
203mm (8”) diameter or smaller Steel vent duct, 26 gauge or heavier |
2 |
6mm (1/4”) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent sealant or Acrylic _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 114mm(4¼”) thick packed into opening (wall both sides) |
cUL |
|
|
356mm x 457mm (14" X 18") 28 gauge or heavier |
3 |
19 to 32mm
(3/4’’) to (1 ¼ ‘’) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant _____________ Foam backer rod (optional) |
Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 89mm (3½”) thick packed into opening (wall both sides) |
cUL |
|
|
457mm x 152mm (18“ X 6”) min. 28 gauge or heavier |
2 |
25mm (1’’) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 25mm (1”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 25mm (1”) thick packed into opening (wall both sides) |
cUL |
|
|
457mm x 965mm (18” x 38”) |
2 |
0 to 5mm (0 to 2”)
|
Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone |
Min. 6mm (¼”) bead on each leg of steel angle and compressed between angle and duct and angle and wall. |
||
|
305mm x 305mm (12" X 12") |
2 |
25mm (1”) |
Wall -Concrete or Concrete Block |
A/D FIREBARRIER Silicone |
Min. 16mm (5/8”) thick within annulus flush both surfaces of wall |
||
|
GYPSUM WALL BOARD CONSTRUCTION |
|||||||
|
457mm x 965mm (18” x 38”) |
1 & 2 |
0 to 51mm (0 to 2”)
|
Wall -Gypsum Board |
A/D FIREBARRIER Silicone |
Min. 6mm (¼”) bead on each leg of steel angle and compressed between angle and duct and angle and wall. |
||
|
305mm x 305mm (12" X 12") |
1 & 2 |
25mm (1’) |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone |
Min. 16mm (5/8”) thick within annulus flush both surfaces of wall |
||
|
WOOD CONSTRUCTION |
|||||||
|
Round 100mm (4’’) |
2 |
25mm (1’’) annulus |
Floor – Lumber Ceiling- Gypsum Boards |
A/D FIREBARRIER Intumescent Sealant |
Min. 16mm (5/8”) to match gypsum board, then shape to form a crown bead. Backer Rod forming Optional |
cUL |
|
|
*** Specific Notes: Proprietary Duct Construction or Regular Duct with Duct Blanket Wrapping Required. See Designs for Details.
|
|||||||