FIREBARRIER Firestopping Materials

Index of Firestop Systems and Designs – by Trade

        HOME                                                                                                                                    GO UP ONE LEVEL

Quick Links to Head of Wall Applications

CONCRETE WALLS

GYPSUM BOARD WALLS

 

Head of Wall - Application Designs and Reference Guide

Movement Capabilities

Rating

 (h)

Max Size

Opening

Construction

Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System

No.

 

CONCRETE WALL CONSTRUCTION

Class II

20%

Compression or Extension

1 & 2

25mm (1”)

Floor - Concrete

 

A/D FIREBARRIER

Acrylic Sealant

_____________

Rock Wool Mfg

Delta Board or

Foam Backer rod

Min. 13mm (½”) thick, installed on each side of the wall. _____________

Min. 19mm (Ύ”) thick mineral wool to be compressed 50% & firmly packed in gap on top of wallboard & bottom of floor,

 on both sides

HW-D-0467

(cUL)

 

Class II

18.75% Compression or Extension

1 or 2

25mm (1”)

Floor  or Roof – Concrete on Steel Deck

 &

Wall –Concrete or Concrete Block

A/D FIREBARRIER

 Seal NS _____________

A/D FIREBARRIER

Mineral Wool

Min. 3.2mm (1/8”) wet thickness, sprayed or brushed on each side of the wall. Overlap a min. 13mm (½ “) onto concrete wall and steel deck.

_____________

Inserted into opening between the top of the wall and steel floor deck flush with both sides of wall.

HW47

 

Class II

14% Compression or Extension

1 or 2

89mm    (3½”)

Floor – Concrete

&

Wall – Concrete or Concrete Block

A/D FIREBARRIER

 Seal NS _____________

A/D FIREBARRIER

Mineral Wool

Min. 3.2mm (1/8”) wet thickness, sprayed or brushed on each side of the wall. Overlap a min. 13mm (½“) onto concrete wall and steel deck.

_____________

Inserted into opening between the top of the wall and steel floor deck flush with both sides of wall

HW38

 

Class II

20% Compression or Extension

3

84mm    (3-5/16”)

Floor – Concrete

&

Wall – Concrete or Concrete Block

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (Ό”) thick applied within the joint, flush with each surface of wall.

_____________

Inserted into opening between the top of the wall and underside of floor, recessed 6mm (Ό”) on both sides of wall

HW-D-1017

(cUL)

 

Class II & III

25% Compression or Extension

1 or 2

51mm (2”)

Floor – Concrete on Steel Deck

(Spray Fireproofing on Deck Optional) Wall – Concrete or Concrete Block

 

A/D FIREBARRIER

 Seal NS _____________

A/D FIREBARRIER

Mineral Wool

Min. 3.2mm (1/8”) wet thickness, sprayed or brushed on each side of the wall. Overlap a min. 13mm (½“) onto gypsum board and steel deck

 _____________

Inserted into opening between the top of the wall and floor  flush with both sides of wall

HW43

 

N/A

1-4

100mm

Floor – Concrete

Wall – Concrete or Concrete Block

Optional BlueSkin

A/D FIREBARRIER

 Seal NS _____________

A/D FIREBARRIER

Mineral Wool

Min. 3.2mm (1/8”) thick applied within the joint, flush with eithersurface of wall.

_____________

Inserted into opening between the top of the wall and underside of floor, recessed 3.2mm (1/8”) on either side of wall.

HW67

 

N/A

2

25mm

Floor – Concrete  Wall – Concrete or Concrete Block

Optional BlueSkin

A/D FIREBARRIER

 Silicone

_____________

Backer Rod

Min. 25mm (1”) thick applied within the joint, flush with each surface of wall.

_____________

Inserted into opening between the top of the wall and underside of floor, recessed 25mm (1”) on both sides of wall

HW65

 

 top of page

GYPSUM WALL BOARD PARTITIONS

N.A.

1 & 2

N.A.

Floor – Concrete

 &

Wall -Gypsum

Board

A/D FIREBARRIER

 Seal NS or Silicone

Min, bead diameter of 10mm (3/8”) caulked into the corner between ends of gypsum wallboard around the entire perimeter of the fire rated wall assembly.

AD/PHV 120-02

 

N.A.

1

16mm (5/8”)

Floor – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm ( Ό“) and 16mm (5/8”) thickness (see fire test design)

_____________

Fitted within fluted openings with a 6mm (Ό”) recess from the wall.

AD/PV 60-01

 

N.A.

2

16mm (5/8”)

Floor – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (Ό“) and 25mm (1” ) thickness

 (see fire test design) 

_____________

Fitted within fluted openings with a 6mm (Ό”) recess from the wall.

AD/PV 120-01

 

Class II

18.75% Compression or Extension

2

25mm (1”)

Floor  or Roof – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D FIREBARRIER

 Seal NS _____________

A/D FIREBARRIER

Mineral Wool

Min. 3.2mm (1/8”) wet thickness, sprayed or brushed on each side of the wall. Overlap a min. 13mm (½”) onto gypsum board and steel deck.

_____________

Length equal to the overall width of the wall. Additional 32mm (1Ό”) wide strips to fill gap between gypsum board & bottom of steel floor units on both sides of wall.

HW36

 

Class II

20% Compression or Extension

1

25mm (1”)

Floor – Concrete on Steel Deck

 &

Wall -Gypsum

Board

A/D FIREBARRIER

 Seal NS _____________

A/D FIREBARRIER

Mineral Wool

Min. 3.2mm (1/8”) wet thickness, sprayed or brushed on each side of the wall. Overlap a min. 13mm (½”) onto gypsum board and steel deck.

_____________

Length equal to the overall width of the wall. Additional 5/8 inch wide strips to fill gap between gypsum board & bottom of steel floor units on both sides of wall.

HW48

 

Class II & III

100% Compression or Extension

1, 2 and 3

76mm (3”)

Floor – Concrete on Steel Deck

(Spray Fireproofing on Deck Optional)

 &

Wall -Gypsum

Board

A/D FIREBARRIER

 Seal NS or Silicone

_____________

A/D FIREBARRIER

Mineral Wool

See fire test design.

(Sliding Gypsum Action)

HW-D-1012

(cUL)

 

Class II & III

100% Compression or Extension

2

76mm (3”)

Floor – Concrete on Steel Deck

(Spray Fireproofing on Deck Optional)

 &

Wall -Gypsum

Board

A/D FIREBARRIER

 Seal NS _____________

A/D FIREBARRIER

Mineral Wool

See fire test design.

(Sliding Gypsum Action)

HW-D-1020

cUL)

 

Class II & III

25% Compression or Extension

1&2

13mm (½”)

Floor – Concrete on Steel Deck

(Spray Fireproofing on Deck Optional)

 &

Wall -Gypsum

Board

Castellized  gypsum board edge

A/D FIREBARRIER

Acrylic Sealant _____________

Optional

Mineral Wool

or backer rod

Min. 16mm (5/8”) thickness, applied on each side of the wall.

_____________

Recess 16mm (5/8”) from both surfaces of wall

HW-D-0470

(cUL)

 

Class II & III

18.75% Compression or Extension

2

25mm

(1”)

Floor – Concrete on Steel Deck

(Spray Fireproofing on Deck Optional)

 &

Wall -Gypsum

Board

Beam & Joist penetrations

A/D FIREBARRIER

SprayAcrylic _____________

A/D FIREBARRIER

Mineral Wool

Min. 3.2mm (1/8”) wet thickness, sprayed or brushed on each side of the wall. Overlap a min. 25mm (1”) onto gypsum board and 51mm (2”) onto steel deck.

_____________

See design for installation requirements.

HW-D-0471