FIREBARRIER Firestopping Materials

Index of Firestop Systems and Designs – by Trade

        HOME                                                                                                                                    GO UP ONE LEVEL

Quick Links to Plumbing Trade Applications

STEEL & IRON PIPE

COPPER (Pipe & Tube)

PLASTIC & GLASS PIPE

INSULATED  PIPE

MULTIPLE PENETRATIONS

 

Plumbing - Application Designs and Reference Guide

STEEL & IRON PIPE

 

 

 

 

 

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Construction Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

610mm (24") diameter

or smaller

3

0 to 28mm (1-1/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

Silicone or

Silicone SL

-----------------

A/D FIREBARRIER

Mineral Wool

Min. 13mm (½ ”)  thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102mm (4”)  thick packed into opening (wall both sides)

SP880

 

 

305mm (12") diameter or

Smaller - see system for options

3

0 to 51mm (2")

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

 Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”) thick within annulus flush with  top or bottom of floor slab

or both surfaces of wall

_____________

Min. 114mm (4¼”) thick packed into opening (wall both sides)

C-AJ-1557

(cUL)

 

203mm (8") diameter

or smaller

3

0 to 98mm

(3-7/8”)

annulus

Floor - Concrete 

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Intumescent Sealant

_____________

Mineral Wool

Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall.

_____________

Min. 102mm (4”) thick packed into opening recessed 13mm (½”) from surface(s).

C-AJ-1558  (cUL)

 

203mm (8") diameter

or smaller

2

0 to 98mm (3-7/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block or precast hollow core

A/D FIREBARRIER

Silicone or

Silicone SL

-----------------

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”)  thick within annulus flush with top or bottom of floor slab

or both surfaces of wall

_____________

Min. 102mm (4”)  thick packed into opening (wall both sides)

C-AJ-1229  (cUL)

 

203mm (8") diameter

or smaller

3

0 to 48mm

(1-7/8”)

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block

Precast  (hollow core) Conc.

 

A/D FIREBARRIER

Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. 25mm (1”) thick within annulus flush with both surfaces of floor or wall

_____________

Min. 25mm (1”) thick packed into each side of opening floor & wall, recessed to take sealant

C-AJ-1561

(cUL)

 

 

GYPSUM WALL BOARD CONSTRUCTION

305mm (12") diameter

or smaller

1 & 2

0 to 48mm

(1-7/8")

annulus

Wall - Gypsum

Board as rated for 1 & 2 hr

A/D FIREBARRIER

Intumescent Sealant

Min. 13mm or 16mm (½” or 5/8”) inch thick within annulus, flush both surfaces of wall

Foam Backer optional

W-L-1416

(cUL)

 

275mm (11“)

diameter or smaller

2

6mm (¼”)

annulus

Wall – Gypsum

Board

A/D FIREBARRIER

Silicone

Min. 25mm (1”) thick within annulus, flush both surfaces of wall

SP324

 

203mm (8") diameter

or smaller

2

0 to 22mm

(7/8”)

annulus

Wall - Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant or Acrylic

_____________

A/D FIREBARRIER

Mineral Wool

Min. 13mm (½”) thick within annulus, flush both surfaces of wall

_____________

Min.13mm (½”) thick packed into opening both sides of wall

W-L-1417

(cUL)

 

51mm (2") diameter or

smaller

1 & 2

0 to

48mm

(1- 7/8")

annulus

Wall -Gypsum

Board

A/D FIREBARRIER

Silicone

Min.16mm (5/8”) inch thick

within annulus, flush both surfaces of wall

SP926

 

 

WOOD CONSTRUCTION

203mm (8") diameter

or smaller

1 & 2

0 to 22mm

(7/8")

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant

Min.16mm (5/8”) thick within annulus on top at floor

Min. 16mm (5/8”) thick within annulus on bottom surface ceiling- 13mm (½”) crown

F-C-1149

(cUL)

 

169mm (6.5") or

smaller

1

6mm (¼")

annulus

Floor - Lumber

Ceiling - Gypsum

Board (chase wall optional)

A/D FIREBARRIER

Silicone

Min. 29mm (1-1/8”) thick

 within annulus on top of floor

Min. 13mm (½”)  thick

within annulus on bottom surface of ceiling

SP365

 

102mm (4") diameter

or smaller

1

0 to 22mm

(7/8”)

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant

Foam Backer Rod

Min. 13mm (½“) thick within annulus on top at floor

Min. 13mm (½”) thick within annulus on bottom surface ceiling and 6mm (¼”) at point of contact

Foam Backer Rod

F-C-1150

(cUL)

 

 top of page

Plumbing - Application Designs and Reference Guide

COPPER (Pipe & Tube)

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Construction Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

152mm (6") diameter

or smaller

3

0 to 28mm (1-1/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

Silicone or

Silicone SL

-----------------

A/D FIREBARRIER

Mineral Wool

Min. 13mm (½”)  thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102 mm (4”)  thick packed into opening (wall both sides)

SP880

 

152mm (6") diameter or

Smaller - see system for options

3

0 to 51mm

(2")

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼“) thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 114mm (4¼”) thick packed into opening  (wall both sides)

C-AJ-1557

(cUL)

 

102mm (4”)

 or smaller

3

0 to 51mm

(2”)

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

 

A/D FIREBARRIER

Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. 19mm (¾”) thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 95mm (3¾”) thick packed into opening  (wall both sides)

C-AJ-1557

(cUL)

 

102mm (4”)

or smaller

2

0 to 22mm

(7/8”)

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant

_____________

Foam Backer optional

Min. 51m (½“) thick within annulus flush with top of floor or both surfaces of wall

C-AJ-1557

(cUL)

 

 

GYPSUM WALL BOARD CONSTRUCTION

102mm (4")

or smaller

diagonal pipe penetration

1 & 2

0 to 48mm

(1-7/8”)

annulus

Wall - Gypsum

Board

As per F rating of wall

A/D FIREBARRIER

Intumescent Sealant

____________

Foam Backer optional

Min. 13mm or 16mm (½” or 5/8”) thick within annulus, flush both surfaces of wall and its rating

Foam Backer Rod optional

W-L-1416

(cUL)

 

102mm (4")

or smaller

2

0 to 22mm

(7/8")

annulus

Wall - Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant

and Acrylic Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. 51mm (½”) thick within annulus, flush both surfaces of wall

_____________

Min. 13mm (½”) thick packed into

Opening both sides of wall

W-L-1417

(cUL)

 

102mm (4“)

diameter

or smaller

2

6mm (¼”)

annulus

Wall – Gypsum

Board

A/D FIREBARRIER

Silicone

Min. 25mm (1”) thick within annulus, flush both surfaces of wall

SP324

 

51mm (2") diameter or

smaller

1 & 2

0 to

48mm

(1-7/8")

annulus

Wall -Gypsum

Board

A/D FIREBARRIER

Silicone

Min.16mm (5/8”) inch thick

within annulus, flush both surfaces of wall

SP926

 

 top of page

Plumbing - Application Designs and Reference Guide

PLASTIC & GLASS PIPE (50 Pa testing required for drain, waste & vent)

 

 

Max. Size

Penetration

Diameter

Rating

(h)

Max Size

Opening

Construction Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

WOOD CONSTRUCTION

102mm (4") or

smaller

1

6mm (¼")

annulus

Floor - Lumber

Ceiling - Gypsum

Board (chase wall optional)

A/D FIREBARRIER

 Silicone

Min. 29 mm (1 1/8”) thick

 within annulus on top of floor

Min. 13 mm (1/2”)  thick

within annulus on bottom surface of ceiling

SP365

 

102mm (4") diameter

or smaller

1

0 to 22mm

(7/8”)

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant

Foam Backer Rod

Min.13mm (½”) thick within annulus on top at floor

Min. 13mm (½”) thick within annulus on bottom surface ceiling and 6mm (¼”) at point of contact

Foam Backer Rod

F-C-1150

(cUL)

 

 

CONCRETE CONSTRUCTION

167 mm (6”), PVC, CPVC

or smaller Not 50 Pa tested

2

0 to 10mm (0" to 3/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone ____________

A/D FIREBARRIER

Collar

Min. 10mm ( 3/8”) thick within annulus flush with top of floor or both surfaces of wall

_______________   

 

C-AJ-2186 (cUL)

 

102m (4”), PVC, CPVC,

or smaller

Not 50 Pa tested

1

0 to 38mm

(1½”) nom.

annulus

Floor - Concrete

(4½ " min. thick Concrete)

A/D FIREBARRIER

Intumescent Sealant

Foam Backer optional

Min. 13mm (½”) thick within annulus flush with top of floor add 13mm (½”) crown

Foam Backer Optional

F-A-2168

 

100 mm (4”), PVC, CPVC,

ABS or smaller 

Not 50 Pa tested

2

19mm (3/4") nom.

annulus

Floor - Concrete

( 65mm (2½)" min. thick Concrete)

 

A/D FIREBARRIER

Wrap Strip  

 

50mm (2") wide Wrap Strip

(3 layers of ¼” wrap strip to make ¾” annular)

F-A-2112 (cUL)

 

89 mm (3”), PVC, CPVC

or smaller   50 Pa tested

3

0 to 13mm (0" to ½")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

 

A/D FIREBARRIER Collar

 

 

SPC52

 

76mm (3”) PVC, CPVC

or smaller

Not 50 Pa tested

2

19mm to 22mm

(¾" to 7/8”)

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant   _____________

Foam Backer optional

Min. 51mm (2”) thick within annulus flush with top of floor or both surfaces of wall

_______________

Foam Backer Optional

C-AJ-2581

 

50 mm (2”),PVC, CPVC

or smaller   Not 50 Pa tested

2

19mm to 35mm

(¾” to

1-3/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. 25mm (1”) thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 100mm (4”) inch thick packed into  opening  (wall both sides)

C-AJ-2150 (cUL)

 

50mm (2”) PVC,  ABS

 or smaller

25mm (1") PEX or smaller

50 Pa tested

2

8 to 16mm (5/16" to 5/8”) nom annulus

Wall - Concrete

 

A/D FIREBARRIER

Wrap Strip

25mm or 50mm (1” or 2") wide Wrap Strip (see fire test design for further details) Applied both sides of wall

W-J-2141 (cUL)

 

50mm (2”) PVC, CPVC, ABS

 or smaller

25mm (1") PEX or smaller

Not 50 Pa tested

2

8mm (5/16") nom annulus

Wall - Concrete

 

A/D FIREBARRIER

Wrap Strip

25mm (1") wide Wrap Strip. Applied both sides of wall.

W-J-2128 (cUL)

 

19mm (¾“) PEX

Not 50 Pa tested

2

6mm to 11mm

(¼“ to 7/16”)

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant    _____________

Foam Backer optional

Min. 13mm (½”) thick within annulus flush with both surfaces of floor or wall

_______________

Foam Backer Optional

C-AJ-2582

 

 

GYPSUM WALL BOARD CONSTRUCTION

167mm (6”), PVC, CPVC

or smaller  Not 50 Pa tested

2

6mm (¼")

annulus

Wall -Gypsum

Board

A/D FIREBARRIER

 Silicone ___________

A/D FIREBARRIER

Collar

Min. 25 mm (1”) thick within annulus flush on  both surfaces of wall

_______________   

 

W-L- 2155 (cUL)

 

152mm (6”), PVC, CPVC

or smaller

Not 50 Pa tested

2

6mm (¼")

annulus

Wall - Gypsum

Board

A/D FIREBARRIER Silicone

___________

A/D FIREBARRIER Collar

Min.1” thick within annulus flush on both surfaces of wall

_______________

 

W-L-2155

(cUL)

 

50 mm (2”). PVC, CPVC, ABS

 or smaller. 25 mm (1") PEX or smaller

Not 50 Pa tested

1 & 2

8mm (5/16") nom annulus

Wall -Gypsum

Board

 

A/D FIREBARRIER

Wrap Strip

25mm (1") wide Wrap Strip on both sides of wall.

W-L-2350 (cUL)

 

 

 

 

 

 

 

 

 

51mm (2”), PVC, CPVC, ABS

or smaller.

25mm (1") PEX or smaller

51mm (2”) CPVC Flowguard Gold & Blazemaster

Not 50 Pa tested

1 & 2

6mm to 35mm

(¼” -

1-3/8”) nom annulus

Wall - Gypsum

Board

A/D FIREBARRIER Intumescent Sealant

Min.16mm (5/8”) thick within annulus flush on both surfaces of wall

Plus a 6mm (¼”) crown around

W-L-2486

(cUL)

 

50 mm (2”)., ABS or smaller.  38mm (1 ½”) PVC or 25 mm (1") PEX or smaller

 50 Pa tested

1 & 2

8mm to 10mm (5/16” to 13/32") nom annulus

Wall -Gypsum

Board

 

A/D FIREBARRIER

Wrap Strip

51mm (2") wide Wrap Strip on both sides of wall.

W-L-2372 (cUL)

 

50 mm (2”),PVC, CPVC

or smaller Not  50 Pa tested

2

13mm to 29mm

(½" -

1-1/8")

nom annulus

Wall -Gypsum

Board (sleeved)

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Mineral Wool

Min. 19mm (¾”) thick within annulus, flush with both ends

_____________

Min. 51mm (2”) thick packed into opening on each side of wall

W-L-2157 (cUL)

 

   top of page  

 

Plumbing - Application Designs and Reference Guide

INSULATED  PIPE

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Construction Type (s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

WOOD CONSTRUCTION

169mm (6”),PVC, CPVC

 or Smaller

50 Pa tested

1

7mm (¼") nom annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Collar

Fill annular space to 32mm &  6.4mm (¼ ") crown on top

SPC59

 

102mm (4”), ABS, PVC, CPVC

** water closet

Config C

Not 50 Pa tested

1

0 to 13mm

(½”)

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER Intumescent Sealant & Acrylic

_____________

Foam Backer optional

Min. ½” thick within annulus  (top & bottom) and ¼” crown

Foam Backer Optional

F-C-2346

(cUL)

 

102mm (4”), PVC,

CPVC, ABS

 or smaller

51mm (2”) PEX

Not 50 Pa tested

1

0 to 13mm

(½”)

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER Intumescent Sealant & Acrylic

Foam Backer Optional

Min. ¾” thick within annulus – top

Min. 5/8” thick within annulus - bottom

F-C-2347

(cUL)

 

102mm (4”),PVC, CPVC

ABS  or

Smaller

50 Pa tested

1

12mm (½") nom annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Collar

Fill annular space to 32mm & 6.4mm (¼") crown on top

SPC56

 

  

CONCRETE CONSTRUCTION

610mm (24") diameter

or smaller

(19mm to 76mm  insulation)

2

0 to 114mm

 (0" to 4½")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block or precast hollow core

A/D FIREBARRIER

 Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”)  thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102mm (4”)  thick packed into opening (wall both sides)

SP386

 

203mm (8“) Steel, Iron

102mm (4“) copper or smaller

3

0" to 1”

annulus

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER Intumescent Sealant

_____________

A/D FIREBARRIER Mineral Wool

Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102mm (4”) thick packed into opening (wall both sides)

C-AJ-1560

(cUL)

 

203mm (8”) Steel, Iron

102mm (4“) Copper

2

Steel/iron

13mm to 25mm

(½” to 1”)

Copper

9.5mm to 38mm

(3/8” to 1½”)

Floor – Concrete

Wall – Concrete

or Concrete Block

A/D FIREBARRIER Intumescent Sealant or Acrylic Sealant

____________

A/D FIREBARRIER Mineral Wool

Min. 51mm (½”) thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102mm (4”) thick packed into opening (wall both sides)

C-AJ-5303

(cUL)

 

152mm (6”) Copper,

steel or smaller (13mm to 19mm  insulation)

0 to 80mm (0" to 3¼”)

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”)  thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102mm (4”)  thick packed into opening (wall both sides)

SP384

 

75mm (3") Copper,

steel or smaller      (25 mm insulation)

3   

6mm (¼")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. 13mm (½”)  thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102mm (4”)  thick packed into opening (wall both sides)

C-AJ–5027

(cUL)

 

51mm (2“) Steel, Iron or

Copper Flexible AB/PVC foam tube insulation

2

1/8“ to ¼”

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER Intumescent Sealant

_____________

Foam backer rod

Min. 25mm (1”) thick within annulus flush with top of floor or both surfaces of wall with 6mm (¼”) crown

_____________

Foam backer rod firmly packed into opening

C-AJ-5304

(cUL)

 

51mm (2“) Steel, Iron or

Copper Flexible AB/PVC foam tube insulation

2

13mm to 25mm

(½” - 1”)

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER Intumescent Sealant

_____________

Mineral wool

Min 25mm (1”) thick within annulus, flush top of floor, both surfaces of wall-force sealant into interstices to max possible, when floor hollow core, fill both sides of floor flush

__________________

Min 89mm (3½") thick packed into opening and into interstices, with hollow core pack both surfaces of floor

C-AJ-8183

(cUL)

 

51mm (2”) PVC, CPVC or smaller

2

22mm

(7/8”)

________

25mm (1”) Insul ASJ

Floor – Concrete

Wall – Concrete

 or Concrete Block

A/D FIREBARRIER Intumescent Sealant

_____________

A/D FIREBARRIER Mineral Wool

Min. 25mm (1”) thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 89mm (3½”) thick packed into opening (wall both sides)

C-AJ-5306

(cUL)

 

GYPSUM WALL BOARD CONSTRUCTION

203mm (8”) Steel, iron,

102mm (4”) copper/tubing or smaller

Config A

2

6mm to 32mm

(¼” to 1¼”)

Wall - Gypsum

Board Wood

A/D FIREBARRIER Intumescent Sealant

_____________

Foam Backer optional

Min 16mm (5/8”) thick within annulus, flush both surfaces of wall plus

a 9.5mm (3/8”) crown

W-L-5267

(cUL)

 

4” Steel

or smaller

4” Copper or smaller

Armaflex

1 & 2

0” to 1-3/8”

annulus

Wall - Gypsum

Board Wood

A/D FIREBARRIER Intumescent Sealant

Min 5/8” thick within annulus, flush both surfaces of wall -

¼” bead to pipe insulation/wallboard at point

of contact

W-L-5266

(cUL)

 

75 mm (3") Copper,

steel or smaller      (25 mm insulation)

1 & 2

6 mm (¼")

annulus

Wall -Gypsum

Board Wood

A/D FIREBARRIER

Silicone

1 hour rating

Min. 13mm (½”) thick flush both surfaces of wall

_______________

2 hour rating

Min. 25mm (1”) thick flush both  surfaces of wall

W-L-5031 (cUL)

 

WOOD CONSTRUCTION

102mm (4") Copper,

steel or smaller

1   

6mm (¼")

annulus

Floor - Lumber

Ceiling - Gypsum

Board (chase wall optional)

A/D FIREBARRIER

Silicone

Min 29mm (1 1/8”) thick within  annulus on top at floor

Min. 13mm (1/2”) thick within  annulus on bottom surface ceiling

SP365

 

25mm (1”) Steel and

Copper or smaller

+ 13mm (½”) Flexible AB/PVC insulation

See Design re PVC, CPVC & cables

1 & 2

6mm to 38mm

(¼” to 1½”)

annulus

Floor/Wall-

wood/gypsum

A/D FIREBARRIER Intumescent Sealant

___________

Foam Backer optional

(2 hr) Min. 19mm (¾”) thick within annulus, flush with top of floor

(1 hr) Min 16mm (5/8”) thick within annulus, flush with top of floor –

Add material forced in annular space around penetrants & 5mm (3/16”) crown

F-C-8041

(cUL)

 

      

 top of page

 

Plumbing - Application Designs and Reference Guide

MULTIPLE PENETRATIONS

 

 

 

 

Type of

Penetration

Rating

 (h)

Max Size

Opening

Construction Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

102 (4”) Steel, iron,

Conduit

51mm (2”) Copper pipe & tubing

3

112.5 sq/in

_________

Annulus

non-insul

0” to 3-3/8” & periphery

_________

Annulus for

Insulated

½” to 1”

_________

Annulus between all penetrants ½” to 5/8”

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER Intumescent Sealant

_____________

A/D FIREBARRIER Mineral Wool

Min. 51mm (½”) thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102 (4”) thick packed into opening  (wall both sides)

C-AJ-8184

(cUL)

 

19mm (¾”) Steel, iron, conduit, copper & copper tubing & cables

(Flexible AB/PVC foam insul on one pipe or tube)

2

89mm (3½”) max opening with ½” between pipes & cables

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER Intumescent Sealant

______________

A/D FIREBARRIER Mineral Wool

Min 25mm (1”) thick within annulus, flush top of floor, both surfaces of wall-force sealant into interstices to max possible, when floor hollow core, fill both sides of floor flush

__________________

Min 89mm (3½") thick packed into opening and into interstices, with hollow core pack both surfaces of floor

C-AJ-8183

(cUL)

 

25mm (1”) PEX- max 5 tubes bundled

2

0 to 73mm

(2-7/8”)

Floor - Concrete

Wall - Concrete

or Concrete Block

A/D FIREBARRIER Intumescent Sealant

______________

A/D FIREBARRIER Mineral Wool

Min 25mm (1”) thick within annulus, flush top of floor, both surfaces of wall-force sealant around tubing to max possible, point of contact, 13mm (½”) bead at tubing & concrete

__________________

Min. 3½” thick packed into

opening ( wall both sides)

C-AJ-2583

(cUL)

 

Steel, Iron, Copper, Insulated Pipe

3

280mm by 660mm (288 sq/in)

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”) thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min.  100mm (4”) thick packed into opening  (wall both sides)

SP163

 

Copper, & Copper Insulated Pipes

2

216mm by 406 mm (8.5” x 16”)

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”) thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min.  100mm (4”) thick packed into opening  (wall both sides)

SP916

 

2  - 13mm (1/2”) Copper Pipes

3

227mm diameter (9”)

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone SL,  

Silicone, Seal or Seal NS

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”) thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min.  100mm (4”) thick packed into opening  (wall both sides)

SP221

 

Steel or Copper Pipe

3

1460mm by 1525mm (24 sq. ft.)

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

Mortar

Fill opening to min. depth 75mm (3”) Inches

SP341

 

Steel, Iron, Copper Pipe

3

280mm by 660mm (288 sq/in)

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Seal or Seal NS

_____________

A/D FIREBARRIER

Mineral Wool

Min. 5mm (13/64”) thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min.  100mm (4”) thick packed into opening  (wall both sides)

SP218

 

Copper, Insulated Pipes

1 1/2

305mm by 610mm (12”x24”)

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

Seal NS

_____________

A/D FIREBARRIER

Mineral Wool

Min. 5mm (13/64”) thick within annulus flush with bottom of  floor or both surfaces of wall

_____________

Min.  100mm (4”) thick packed into opening  (wall both sides)

SP761

 

GYPSUM WALL BOARD CONSTRUCTION

102mm (4") Steel, Iron, Copper or smaller

1 & 2

300mm by 600mm (1.9 sq. ft.)

Wall -Gypsum

Board

A/D FIREBARRIER

Mortar (design allows use of Silicone and Mineral Wool sleeves)

2 hr- min 114mm (4½”) flush with

 both surfaces of wall

__________________

1 hr - min.88mm (3½”) flush with

both surfaces of wall

W-L-8005 (cUL)

 

102mm (4") Steel, Iron, Copper or smaller

1 1/2

300mm by 600mm (1.9 sq. ft.)

Wall -Gypsum

Board

A/D FIREBARRIER

 Silicone or

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”)  thick within annulus flush with  both surfaces of wall

_____________

Min. 100mm (4”)  thick packed into opening

SP325

 

25mm (1”) Steel, iron, copper

+ 19mm (¾”) (Flexible AB/PVC

foam Insul)

+ cables

1 & 2

13mm to 19mm

(½” to ¾”)

Wall - Gypsum

Board

A/D FIREBARRIER Intumescent Sealant

Min. 13mm (½”) flush with

both surfaces of wall added material into intersties with a

6mm (¼”) crown

W-L-8075

(cUL)

 

 

 

 top of page