Quick Links to Plumbing Trade Applications
Plumbing - Application Designs and Reference Guide |
|||||||
STEEL & IRON PIPE |
|
|
|
|
|
||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
CONCRETE CONSTRUCTION |
|||||||
|
610mm (24") diameter or smaller |
3 |
0 to 28mm (1-1/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL ----------------- A/D FIREBARRIER Mineral Wool |
Min. 13mm (½ ”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
|
|
|
305mm (12") diameter or Smaller - see system for options |
3 |
0 to 51mm (2") annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top or bottom of floor slab or both surfaces of wall _____________ Min. 114mm (4¼”) thick packed into opening (wall both sides) |
(cUL) |
|
|
203mm (8") diameter or smaller |
3 |
0 to 98mm (3-7/8”) annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant _____________ Mineral Wool |
Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall. _____________ Min. 102mm (4”) thick packed into opening recessed 13mm (½”) from surface(s). |
C-AJ-1558 (cUL) |
|
|
203mm (8") diameter or smaller |
2 |
0 to 98mm (3-7/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block or precast hollow core |
A/D FIREBARRIER Silicone or Silicone SL ----------------- A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top or bottom of floor slab or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
C-AJ-1229 (cUL) |
|
|
203mm (8") diameter or smaller |
3 |
0 to 48mm (1-7/8”) annulus |
Floor - Concrete Wall - Concrete Concrete Block Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 25mm (1”) thick within annulus flush with both surfaces of floor or wall _____________ Min. 25mm (1”) thick packed into each side of opening floor & wall, recessed to take sealant |
(cUL) |
|
|
|
|||||||
|
GYPSUM WALL BOARD CONSTRUCTION |
|||||||
|
305mm (12") diameter or smaller |
1 & 2 |
0 to 48mm (1-7/8") annulus |
Wall - Gypsum Board as rated for 1 & 2 hr |
A/D FIREBARRIER Intumescent Sealant |
Min. 13mm or 16mm (½” or 5/8”) inch thick within annulus, flush both surfaces of wall Foam Backer optional |
(cUL) |
|
|
275mm (11“) diameter or smaller |
2 |
6mm (¼”) annulus |
Wall – Gypsum Board |
A/D FIREBARRIER Silicone |
Min. 25mm (1”) thick within annulus, flush both surfaces of wall |
|
|
|
203mm (8") diameter or smaller |
2 |
0 to 22mm (7/8”) annulus |
Wall - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant or Acrylic _____________ A/D FIREBARRIER Mineral Wool |
Min. 13mm (½”) thick within annulus, flush both surfaces of wall _____________ Min.13mm (½”) thick packed into opening both sides of wall |
(cUL) |
|
|
51mm (2") diameter or smaller |
1 & 2 |
0 to 48mm (1- 7/8") annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone |
Min.16mm (5/8”) inch thick within annulus, flush both surfaces of wall |
|
|
|
WOOD CONSTRUCTION |
|||||||
|
203mm (8") diameter or smaller |
1 & 2 |
0 to 22mm (7/8") annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant |
Min.16mm (5/8”) thick within annulus on top at floor Min. 16mm (5/8”) thick within annulus on bottom surface ceiling- 13mm (½”) crown |
(cUL) |
|
|
169mm (6.5") or smaller |
1 |
6mm (¼") annulus |
Floor - Lumber Ceiling - Gypsum Board (chase wall optional) |
A/D FIREBARRIER Silicone |
Min. 29mm (1-1/8”) thick within annulus on top of floor Min. 13mm (½”) thick within annulus on bottom surface of ceiling |
|
|
|
102mm (4") diameter or smaller |
1 |
0 to 22mm (7/8”) |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant Foam Backer Rod |
Min. 13mm (½“) thick within annulus on top at floor Min. 13mm (½”) thick within annulus on bottom surface ceiling and 6mm (¼”) at point of contact Foam Backer Rod |
(cUL) |
|
top of page |
|||||||
Plumbing - Application Designs and Reference Guide |
|||||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
CONCRETE CONSTRUCTION |
|||||||
|
152mm (6") diameter or smaller |
3 |
0 to 28mm (1-1/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL ----------------- A/D FIREBARRIER Mineral Wool |
Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102 mm (4”) thick packed into opening (wall both sides) |
|
|
|
152mm (6") diameter or Smaller - see system for options |
3 |
0 to 51mm (2") annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼“) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 114mm (4¼”) thick packed into opening (wall both sides) |
(cUL) |
|
|
102mm (4”) or smaller |
3 |
0 to 51mm (2”) annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 19mm (¾”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 95mm (3¾”) thick packed into opening (wall both sides) |
(cUL) |
|
|
102mm (4”) or smaller |
2 |
0 to 22mm (7/8”) annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Foam Backer optional |
Min. 51m (½“) thick within annulus flush with top of floor or both surfaces of wall |
(cUL) |
|
|
|
|||||||
|
GYPSUM WALL BOARD CONSTRUCTION |
|||||||
|
102mm (4") or smaller diagonal pipe penetration |
1 & 2 |
0 to 48mm (1-7/8”) annulus |
Wall - Gypsum Board As per F rating of wall |
A/D FIREBARRIER Intumescent Sealant ____________ Foam Backer optional |
Min. 13mm or 16mm (½” or 5/8”) thick within annulus, flush both surfaces of wall and its rating Foam Backer Rod optional |
(cUL) |
|
|
102mm (4") or smaller |
2 |
0 to 22mm (7/8") annulus |
Wall - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant and Acrylic Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 51mm (½”) thick within annulus, flush both surfaces of wall _____________ Min. 13mm (½”) thick packed into Opening both sides of wall |
(cUL) |
|
|
102mm (4“) diameter or smaller |
2 |
6mm (¼”) annulus |
Wall – Gypsum Board |
A/D FIREBARRIER Silicone |
Min. 25mm (1”) thick within annulus, flush both surfaces of wall |
|
|
|
51mm (2") diameter or smaller |
1 & 2 |
0 to 48mm (1-7/8") annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone |
Min.16mm (5/8”) inch thick within annulus, flush both surfaces of wall |
|
|
|
Plumbing - Application Designs and Reference Guide |
|||||||
|
PLASTIC & GLASS PIPE (50 Pa testing required for drain, waste & vent) |
|
|
|||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
WOOD CONSTRUCTION |
|||||||
|
102mm (4") or smaller |
1 |
6mm (¼") annulus |
Floor - Lumber Ceiling - Gypsum Board (chase wall optional) |
A/D FIREBARRIER Silicone |
Min. 29 mm (1 1/8”) thick within annulus on top of floor Min. 13 mm (1/2”) thick within annulus on bottom surface of ceiling |
|
|
|
102mm (4") diameter or smaller |
1 |
0 to 22mm (7/8”) |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant Foam Backer Rod |
Min.13mm (½”) thick within annulus on top at floor Min. 13mm (½”) thick within annulus on bottom surface ceiling and 6mm (¼”) at point of contact Foam Backer Rod |
(cUL) |
|
|
CONCRETE CONSTRUCTION |
|||||||
|
167 mm (6”), PVC, CPVC or smaller Not 50 Pa tested |
2 |
0 to 10mm (0" to 3/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone ____________ A/D FIREBARRIER Collar |
Min. 10mm ( 3/8”) thick within annulus flush with top of floor or both surfaces of wall _______________
|
C-AJ-2186 (cUL) |
|
|
102m (4”), PVC, CPVC, or smaller Not 50 Pa tested |
1 |
0 to 38mm (1½”) nom. annulus |
Floor - Concrete (4½ " min. thick Concrete) |
A/D FIREBARRIER Intumescent Sealant Foam Backer optional |
Min. 13mm (½”) thick within annulus flush with top of floor add 13mm (½”) crown Foam Backer Optional |
|
|
|
100 mm (4”), PVC, CPVC, ABS or smaller Not 50 Pa tested |
2 |
19mm (3/4") nom. annulus |
Floor - Concrete ( 65mm (2½)" min. thick Concrete) |
A/D FIREBARRIER Wrap Strip
|
50mm (2") wide Wrap Strip (3 layers of ¼” wrap strip to make ¾” annular) |
F-A-2112 (cUL) |
|
|
89 mm (3”), PVC, CPVC or smaller 50 Pa tested |
3 |
0 to 13mm (0" to ½") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Collar |
|
|
|
|
76mm (3”) PVC, CPVC or smaller Not 50 Pa tested |
2 |
19mm to 22mm (¾" to 7/8”) annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Foam Backer optional |
Min. 51mm (2”) thick within annulus flush with top of floor or both surfaces of wall _______________ Foam Backer Optional |
|
|
|
50 mm (2”),PVC, CPVC or smaller Not 50 Pa tested |
2 |
19mm to 35mm (¾” to 1-3/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. 25mm (1”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 100mm (4”) inch thick packed into opening (wall both sides) |
C-AJ-2150 (cUL) |
|
|
50mm (2”) PVC, ABS or smaller 25mm (1") PEX or smaller 50 Pa tested |
2 |
8 to 16mm (5/16" to 5/8”) nom annulus |
Wall - Concrete |
A/D FIREBARRIER Wrap Strip |
25mm or 50mm (1” or 2") wide Wrap Strip (see fire test design for further details) Applied both sides of wall |
W-J-2141 (cUL) |
|
|
50mm (2”) PVC, CPVC, ABS or smaller 25mm (1") PEX or smaller Not 50 Pa tested |
2 |
8mm (5/16") nom annulus |
Wall - Concrete |
A/D FIREBARRIER Wrap Strip |
25mm (1") wide Wrap Strip. Applied both sides of wall. |
W-J-2128 (cUL) |
|
|
19mm (¾“) PEX Not 50 Pa tested |
2 |
6mm to 11mm (¼“ to 7/16”) annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Foam Backer optional |
Min. 13mm (½”) thick within annulus flush with both surfaces of floor or wall _______________ Foam Backer Optional |
|
|
|
|
|||||||
|
GYPSUM WALL BOARD CONSTRUCTION |
|||||||
|
167mm (6”), PVC, CPVC or smaller Not 50 Pa tested |
2 |
6mm (¼") annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone ___________ A/D FIREBARRIER Collar |
Min. 25 mm (1”) thick within annulus flush on both surfaces of wall _______________
|
W-L- 2155 (cUL) |
|
|
152mm (6”), PVC, CPVC or smaller Not 50 Pa tested |
2 |
6mm (¼") annulus |
Wall - Gypsum Board |
A/D FIREBARRIER Silicone ___________ A/D FIREBARRIER Collar |
Min.1” thick within annulus flush on both surfaces of wall _______________
|
(cUL) |
|
|
50 mm (2”). PVC, CPVC, ABS or smaller. 25 mm (1") PEX or smaller Not 50 Pa tested |
1 & 2 |
8mm (5/16") nom annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Wrap Strip |
25mm (1") wide Wrap Strip on both sides of wall. |
W-L-2350 (cUL) |
|
|
|
|
|
|
|
|
|
|
|
51mm (2”), PVC, CPVC, ABS or smaller. 25mm (1") PEX or smaller 51mm (2”) CPVC Flowguard Gold & Blazemaster Not 50 Pa tested |
1 & 2 |
6mm to 35mm (¼” - 1-3/8”) nom annulus |
Wall - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant |
Min.16mm (5/8”) thick within annulus flush on both surfaces of wall Plus a 6mm (¼”) crown around |
(cUL) |
|
|
50 mm (2”)., ABS or smaller. 38mm (1 ½”) PVC or 25 mm (1") PEX or smaller 50 Pa tested |
1 & 2 |
8mm to 10mm (5/16” to 13/32") nom annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Wrap Strip |
51mm (2") wide Wrap Strip on both sides of wall. |
W-L-2372 (cUL) |
|
|
50 mm (2”),PVC, CPVC or smaller Not 50 Pa tested |
2 |
13mm to 29mm (½" - 1-1/8") nom annulus |
Wall -Gypsum Board (sleeved) |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Mineral Wool |
Min. 19mm (¾”) thick within annulus, flush with both ends _____________ Min. 51mm (2”) thick packed into opening on each side of wall |
W-L-2157 (cUL) |
|
|
|
|||||||
Plumbing - Application Designs and Reference Guide |
|||||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Construction Type (s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
WOOD CONSTRUCTION |
|||||||
|
169mm (6”),PVC, CPVC or Smaller 50 Pa tested |
1 |
7mm (¼") nom annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Collar |
Fill annular space to 32mm & 6.4mm (¼ ") crown on top |
|
|
|
102mm (4”), ABS, PVC, CPVC ** water closet Config C Not 50 Pa tested |
1 |
0 to 13mm (½”) |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant & Acrylic _____________ Foam Backer optional |
Min. ½” thick within annulus (top & bottom) and ¼” crown Foam Backer Optional |
(cUL) |
|
|
102mm (4”), PVC, CPVC, ABS or smaller 51mm (2”) PEX Not 50 Pa tested |
1 |
0 to 13mm (½”) annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant & Acrylic Foam Backer Optional |
Min. ¾” thick within annulus – top Min. 5/8” thick within annulus - bottom |
(cUL) |
|
|
102mm (4”),PVC, CPVC ABS or Smaller 50 Pa tested |
1 |
12mm (½") nom annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Collar |
Fill annular space to 32mm & 6.4mm (¼") crown on top |
|
|
|
CONCRETE CONSTRUCTION |
|||||||
|
610mm (24") diameter or smaller (19mm to 76mm insulation) |
2 |
0 to 114mm (0" to 4½") annulus |
Floor - Concrete Wall - Concrete or Concrete Block or precast hollow core |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
|
|
|
203mm (8“) Steel, Iron 102mm (4“) copper or smaller |
3 |
0" to 1” annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
(cUL) |
|
|
203mm (8”) Steel, Iron 102mm (4“) Copper |
2 |
Steel/iron 13mm to 25mm (½” to 1”) Copper 9.5mm to 38mm (3/8” to 1½”) |
Floor – Concrete Wall – Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant or Acrylic Sealant ____________ A/D FIREBARRIER Mineral Wool |
Min. 51mm (½”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
(cUL) |
|
|
152mm (6”) Copper, steel or smaller (13mm to 19mm insulation) |
1½ |
0 to 80mm (0" to 3¼”) annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
|
|
|
75mm (3") Copper, steel or smaller (25 mm insulation) |
3 |
6mm (¼") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
(cUL) |
|
|
51mm (2“) Steel, Iron or Copper Flexible AB/PVC foam tube insulation |
2 |
1/8“ to ¼” |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Foam backer rod |
Min. 25mm (1”) thick within annulus flush with top of floor or both surfaces of wall with 6mm (¼”) crown _____________ Foam backer rod firmly packed into opening |
(cUL) |
|
|
51mm (2“) Steel, Iron or Copper Flexible AB/PVC foam tube insulation |
2 |
13mm to 25mm (½” - 1”) annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Mineral wool |
Min 25mm (1”) thick within annulus, flush top of floor, both surfaces of wall-force sealant into interstices to max possible, when floor hollow core, fill both sides of floor flush __________________ Min 89mm (3½") thick packed into opening and into interstices, with hollow core pack both surfaces of floor |
(cUL) |
|
|
51mm (2”) PVC, CPVC or smaller |
2 |
22mm (7/8”) ________ 25mm (1”) Insul ASJ |
Floor – Concrete Wall – Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 25mm (1”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 89mm (3½”) thick packed into opening (wall both sides) |
(cUL) |
|
|
GYPSUM WALL BOARD CONSTRUCTION |
|||||||
|
203mm (8”) Steel, iron, 102mm (4”) copper/tubing or smaller Config A |
2 |
6mm to 32mm (¼” to 1¼”) |
Wall - Gypsum Board Wood |
A/D FIREBARRIER Intumescent Sealant _____________ Foam Backer optional |
Min 16mm (5/8”) thick within annulus, flush both surfaces of wall plus a 9.5mm (3/8”) crown |
(cUL) |
|
|
4” Steel or smaller 4” Copper or smaller Armaflex |
1 & 2 |
0” to 1-3/8” annulus |
Wall - Gypsum Board Wood |
A/D FIREBARRIER Intumescent Sealant |
Min 5/8” thick within annulus, flush both surfaces of wall - ¼” bead to pipe insulation/wallboard at point of contact |
(cUL) |
|
|
75 mm (3") Copper, steel or smaller (25 mm insulation) |
1 & 2 |
6 mm (¼") annulus |
Wall -Gypsum Board Wood |
A/D FIREBARRIER Silicone |
1 hour rating Min. 13mm (½”) thick flush both surfaces of wall _______________ 2 hour rating Min. 25mm (1”) thick flush both surfaces of wall |
W-L-5031 (cUL) |
|
|
WOOD CONSTRUCTION |
|||||||
|
102mm (4") Copper, steel or smaller |
1 |
6mm (¼") annulus |
Floor - Lumber Ceiling - Gypsum Board (chase wall optional) |
A/D FIREBARRIER Silicone |
Min 29mm (1 1/8”) thick within annulus on top at floor Min. 13mm (1/2”) thick within annulus on bottom surface ceiling |
|
|
|
25mm (1”) Steel and Copper or smaller + 13mm (½”) Flexible AB/PVC insulation See Design re PVC, CPVC & cables |
1 & 2 |
6mm to 38mm (¼” to 1½”) annulus |
Floor/Wall- wood/gypsum |
A/D FIREBARRIER Intumescent Sealant ___________ Foam Backer optional |
(2 hr) Min. 19mm (¾”) thick within annulus, flush with top of floor (1 hr) Min 16mm (5/8”) thick within annulus, flush with top of floor – Add material forced in annular space around penetrants & 5mm (3/16”) crown |
(cUL) |
|
Plumbing - Application Designs and Reference Guide |
|||||||
|
|
|
|
|
||||
|
Type of Penetration |
Rating (h) |
Max Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
CONCRETE CONSTRUCTION |
|||||||
|
102 (4”) Steel, iron, Conduit 51mm (2”) Copper pipe & tubing |
3 |
112.5 sq/in _________ Annulus non-insul 0” to 3-3/8” & periphery _________ Annulus for Insulated ½” to 1” _________ Annulus between all penetrants ½” to 5/8” |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 51mm (½”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102 (4”) thick packed into opening (wall both sides) |
(cUL) |
|
|
19mm (¾”) Steel, iron, conduit, copper & copper tubing & cables (Flexible AB/PVC foam insul on one pipe or tube) |
2 |
89mm (3½”) max opening with ½” between pipes & cables |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant ______________ A/D FIREBARRIER Mineral Wool |
Min 25mm (1”) thick within annulus, flush top of floor, both surfaces of wall-force sealant into interstices to max possible, when floor hollow core, fill both sides of floor flush __________________ Min 89mm (3½") thick packed into opening and into interstices, with hollow core pack both surfaces of floor |
(cUL) |
|
|
25mm (1”) PEX- max 5 tubes bundled |
2 |
0 to 73mm (2-7/8”) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Intumescent Sealant ______________ A/D FIREBARRIER Mineral Wool |
Min 25mm (1”) thick within annulus, flush top of floor, both surfaces of wall-force sealant around tubing to max possible, point of contact, 13mm (½”) bead at tubing & concrete __________________ Min. 3½” thick packed into opening ( wall both sides) |
(cUL) |
|
|
Steel, Iron, Copper, Insulated Pipe |
3 |
280mm by 660mm (288 sq/in) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 100mm (4”) thick packed into opening (wall both sides) |
|
|
|
Copper, & Copper Insulated Pipes |
2 |
216mm by 406 mm (8.5” x 16”) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 100mm (4”) thick packed into opening (wall both sides) |
|
|
|
2 - 13mm (1/2”) Copper Pipes |
3 |
227mm diameter (9”) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone SL, Silicone, Seal or Seal NS _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 100mm (4”) thick packed into opening (wall both sides) |
|
|
|
Steel or Copper Pipe |
3 |
1460mm by 1525mm (24 sq. ft.) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Mortar |
Fill opening to min. depth 75mm (3”) Inches |
|
|
|
Steel, Iron, Copper Pipe |
3 |
280mm by 660mm (288 sq/in) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Seal or Seal NS _____________ A/D FIREBARRIER Mineral Wool |
Min. 5mm (13/64”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 100mm (4”) thick packed into opening (wall both sides) |
|
|
|
Copper, Insulated Pipes |
1 1/2 |
305mm by 610mm (12”x24”) |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Seal NS _____________ A/D FIREBARRIER Mineral Wool |
Min. 5mm (13/64”) thick within annulus flush with bottom of floor or both surfaces of wall _____________ Min. 100mm (4”) thick packed into opening (wall both sides) |
|
|
|
GYPSUM WALL BOARD CONSTRUCTION |
|||||||
|
102mm (4") Steel, Iron, Copper or smaller |
1 & 2 |
300mm by 600mm (1.9 sq. ft.) |
Wall -Gypsum Board |
A/D FIREBARRIER Mortar (design allows use of Silicone and Mineral Wool sleeves) |
2 hr- min 114mm (4½”) flush with both surfaces of wall __________________ 1 hr - min.88mm (3½”) flush with both surfaces of wall |
W-L-8005 (cUL) |
|
|
102mm (4") Steel, Iron, Copper or smaller |
1 1/2 |
300mm by 600mm (1.9 sq. ft.) |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone or _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with both surfaces of wall _____________ Min. 100mm (4”) thick packed into opening |
|
|
|
25mm (1”) Steel, iron, copper + 19mm (¾”) (Flexible AB/PVC foam Insul) + cables |
1 & 2 |
13mm to 19mm (½” to ¾”) |
Wall - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant |
Min. 13mm (½”) flush with both surfaces of wall added material into intersties with a 6mm (¼”) crown |
(cUL) |
|