FIREBARRIER Firestopping Materials

Index of Firestop Systems and Designs – by Trade

        HOME                                                                                                                                    GO UP ONE LEVEL

Quick Links to Sprinkler Trade Applications

STEELand IRON PIPE

PLASTIC and GLASS PIPE

 

Sprinkler - Application Designs and Reference Guide

STEEL & IRON PIPE

 

 

 

 

 

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Construction Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

610mm (24")

diameter

or smaller

3

0 to 28mm ( 1-1/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

Silicone or

 Silicone SL

-----------------

A/D FIREBARRIER

Mineral Wool

Min. 13mm (½”)  thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 102mm (4”)  thick packed into opening (wall both sides)

SP880

 

305mm (12") diameter or

Smaller - see system for options

3

0 to 51mm (2")

annulus

Floor - Concrete

Wall - Concrete

Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall

_____________

Min. 114mm (4¼”) thick packed into opening (wall both sides)

C-AJ-1557

(cUL)

 

203mm (8") diameter

or smaller

2

0 to 98mm

(3-7/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block or precast hollow core

A/D FIREBARRIER

Silicone or

Silicone SL

-----------------

A/D FIREBARRIER

Mineral Wool

Min. 6mm (¼”)  thick within annulus flush with top or bottom of floor slab

or both surfaces of wall

_____________

Min. 100mm (4”)  thick packed into opening (wall both sides)

C-AJ-1229  (cUL)

 

203mm (8") diameter

or smaller

3

0 to 48mm

(1-7/8”)

annulus

Floor - Concrete

Wall - Concrete

Concrete Block

Precast  (hollow core) Conc.

A/D FIREBARRIER Intumescent Sealant

_____________

A/D FIREBARRIER

Mineral Wool

Min. 25mm (1”) thick within annulus flush with both surfaces of floor or wall

_____________

Min. 25mm (1”) thick packed into each side of opening floor & wall, recessed to take sealant

C-AJ-1561

(cUL)

 

GYPSUM WALL BOARD CONSTRUCTION

305mm (12") diameter

or smaller

1 & 2

0 to 48mm

(1-7/8")

annulus

Wall - Gypsum

Board as rated for 1 & 2 hr

A/D FIREBARRIER

Intumescent Sealant

Min. 13mm or 16mm (½” or 5/8”) inch thick within annulus, flush both surfaces of wall

Foam Backer optional

W-L-1416

(cUL)

 

275mm (11“)

diameter or smaller

2

6mm (¼”)

annulus

Wall – Gypsum

Board

A/D FIREBARRIER

Silicone

Min. 25mm (1”) thick within annulus, flush both surfaces of wall

SP324

 

203mm (8") diameter

or smaller

2

0 to 22mm

(7/8”)

annulus

Wall - Gypsum

Board

A/D FIREBARRIER

Intumescent

Sealant or Acrylic

_____________

A/D FIREBARRIER

Mineral Wool

Min. 13mm (½”) thick within annulus, flush both surfaces of wall

_____________

Min. 13mm (½”) thick packed into opening both sides of wall

W-L-1417

(cUL)

 

51mm (2") diameter or

smaller

1 & 2

0 to

48mm

(1-7/8")

annulus

Wall -Gypsum

Board

A/D FIREBARRIER

Silicone

Min.16mm (5/8”) inch thick

within annulus, flush both surfaces of wall

SP926

 

Max. Size

Penetration

Diameter

Rating

 (h)

Max Size

Opening

Construction Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

WOOD CONSTRUCTION

203mm (8") diameter

or smaller

1 & 2

0 to 22mm

(7/8")

annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant

Min.16mm (5/8”) thick within annulus on top at floor

Min. 16mm (5/8”) thick within annulus on bottom surface ceiling- 13mm (½”) crown

F-C-1149

(cUL)

 

169mm (6.5") or

smaller

1

6mm (¼")

annulus

Floor - Lumber

Ceiling - Gypsum

Board (chase wall optional)

A/D FIREBARRIER

Silicone

Min. 29mm (1-1/8”) thick

 within annulus on top of floor

Min. 13mm (½”)  thick

within annulus on bottom surface of ceiling

SP365

 

102mm (4") diameter

or smaller

1

0 to 22mm

(7/8”)

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

Intumescent sealant

Foam Backer Rod

Min. 13mm (½”) thick within annulus on top at floor

Min. 13mm (½“) thick within annulus on bottom surface ceiling and 6mm (¼”) at point of contact

Foam Backer Rod

F-C-1150

(cUL)

 

 top of page

PLASTIC & GLASS PIPE (50 Pa testing required for dry system)

 

 

Max. Size

Penetration

Diameter

Rating

(h)

Max Size

Opening

Construction Type(s)

A/D FIREBARRIER

Product Required

Application

Thickness

System No.

 

CONCRETE CONSTRUCTION

167mm (6”), PVC, CPVC

or smaller Not 50 Pa tested

2

0 to 10mm (0" to 3/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone ____________

A/D FIREBARRIER

Collar

Min. 10mm ( 3/8”) thick within annulus flush with top of floor or both surfaces of wall

_______________   

 

C-AJ-2186 (cUL)

 

102mm (4”), PVC, CPVC,

or smaller

Not 50 Pa tested

1

0 to 38mm

(1½”) nom.

annulus

Floor - Concrete

(4½" min. thick Concrete)

 

A/D FIREBARRIER

Intumescent Sealant

Foam Backer optional

Min. 13mm (½”) thick within annulus flush with top of floor add

13mm (½”) crown

Foam Backer optional

F-A-2168

(cUL)

 

76mm (3”), PVC, CPVC

or smaller

Not 50 Pa tested

2

19mm to 22mm

(¾" to 7/8”)

annulus

Floor - Concrete

Wall - Concrete

  Concrete Block or Precast  (hollow core) Conc.

A/D FIREBARRIER

Intumescent Sealant   _____________

Foam backer rod optional

Min. 51mm (2”) thick within annulus flush with top of floor or both surfaces of wall

_______________   

optional

C-AJ-2581

(cUL)

 

51mm (2”),PVC, CPVC

or smaller   Not 50 Pa tested

2

19mm to 35mm (¾" to 1-3/8")

annulus

Floor - Concrete

Wall - Concrete

 or Concrete Block

A/D FIREBARRIER

 Silicone or

Silicone SL

_____________

A/D FIREBARRIER

Mineral Wool

Min. 25mm (1”) thick within annulus flush with top of  floor or both surfaces of wall

_____________

Min. 102mm (4”) inch thick packed into  opening  (wall both sides)

C-AJ-2150 (cUL)

 

102mm (4”), PVC, CPVC,

ABS or smaller 

Not 50 Pa tested

2

19mm (¾") nom.

annulus

Floor - Concrete

( 65mm (2½)" min. thick Concrete)

 

A/D FIREBARRIER

Wrap Strip  

 

51mm (2") wide Wrap Strip

(3 layers of ¼” wrap strip to make ¾” annular)

F-A-2112

(cUL)

 

51mm (2”) PVC,  ABS

 or smaller 25mm (1") PEX or smaller

50 Pa tested

2

8 to 16 mm (5/16" to 5/8”) nom annulus

Wall - Concrete

 

A/D FIREBARRIER

Wrap Strip

25mm or 50mm (1” or 2") wide Wrap Strip (see fire test design for further details) Applied both sides of wall

W-J-2141 (cUL)

 

51mm (2”) PVC, CPVC, ABS or smaller 25mm (1") PEX or smaller

Not 50 Pa tested

2

8 mm (5/16") nom annulus

Wall - Concrete

 

A/D FIREBARRIER

Wrap Strip

25 mm (1") wide Wrap Strip. Applied both sides of wall.

W-J-2128 (cUL)

 

GYPSUM WALL BOARD CONSTRUCTION

167 mm (6”), PVC, CPVC

or smaller  Not 50 Pa tested

2

6mm (¼")

annulus

Wall -Gypsum

Board

A/D FIREBARRIER

 Silicone ___________

A/D FIREBARRIER

Collar

Min. 25mm (1”) thick within annulus flush on  both surfaces of wall

_______________   

 

W-L-2155 (cUL)

 

51mm (2)” PVC, CPVC, ABS

 or smaller.

2mm (1") PEX or smaller

51mm (2”) CPVC Flowguard Gold & Blazemaster

1 & 2

6mm to 35mm

(¼” to

1-3/8”) nom annulus

Wall -Gypsum

Board

A/D FIREBARRIER

Intumescent Sealant

Min.16mm (5/8”) thick within annulus flush on both surfaces of wall

Plus a 6mm (¼”) crown around  

 

W-L-2486

(cUL)

 

51mm (2”). PVC, CPVC, ABS

 or smaller. 25mm (1") PEX or smaller

Not 50 Pa tested

1 & 2

8mm (5/16") nom annulus

Wall -Gypsum

Board

 

A/D FIREBARRIER

Wrap Strip

25mm (1") wide Wrap Strip on both sides of wall.

W-L-2350 (cUL)

 

51mm (2”)., ABS or smaller.  38mm (1½”) PVC or 25mm (1") PEX or smaller

 50 Pa tested

1 & 2

8mm to 10mm (5/16 to 13/32") nom annulus

Wall -Gypsum

Board

 

A/D FIREBARRIER

Wrap Strip

51mm (2") wide Wrap Strip on both sides of wall.

W-L-2372 (cUL)

 

51 mm (2”),PVC, CPVC

or smaller Not  50 Pa tested

2

13mm to 29mm

(½" to

1-1/8")

nom annulus

Wall -Gypsum

Board (sleeved)

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Mineral Wool

Min. 19mm (¾”) thick within annulus, flush with both ends

_____________

Min. 51mm (2”) thick packed into opening on each side of wall

W-L-2157 (cUL)

 

WOOD CONSTRUCTION

169mm (6”),PVC, CPVC

 or Smaller

50 Pa tested

1

7 mm (¼") nom annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Collar

Fill annulus Space to 32mm & 6.4mm (¼") crown on top

SPC59

 

115mm (4”),PVC, CPVC

ABS  or

Smaller

50 Pa tested

1

12mm (½") nom annulus

Floor - Lumber

Ceiling - Gypsum

Board

A/D FIREBARRIER

 Silicone _____________

A/D FIREBARRIER

Collar

Fill annulus Space to 32mm & 6.4mm (¼") crown on top

SPC56

 
                 

  top of page