Quick Links to Sprinkler Trade Applications
Sprinkler - Application Designs and Reference Guide |
||||||||
STEEL & IRON PIPE |
|
|
|
|
|
|||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
|
|
|
CONCRETE CONSTRUCTION |
||||||||
|
610mm (24") diameter or smaller |
3 |
0 to 28mm ( 1-1/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL ----------------- A/D FIREBARRIER Mineral Wool |
Min. 13mm (½”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) thick packed into opening (wall both sides) |
|||
|
305mm (12") diameter or Smaller - see system for options |
3 |
0 to 51mm (2") annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 114mm (4¼”) thick packed into opening (wall both sides) |
(cUL) |
||
|
203mm (8") diameter or smaller |
2 |
0 to 98mm (3-7/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block or precast hollow core |
A/D FIREBARRIER Silicone or Silicone SL ----------------- A/D FIREBARRIER Mineral Wool |
Min. 6mm (¼”) thick within annulus flush with top or bottom of floor slab or both surfaces of wall _____________ Min. 100mm (4”) thick packed into opening (wall both sides) |
C-AJ-1229 (cUL) |
||
|
203mm (8") diameter or smaller |
3 |
0 to 48mm (1-7/8”) annulus |
Floor - Concrete Wall - Concrete Concrete Block Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ A/D FIREBARRIER Mineral Wool |
Min. 25mm (1”) thick within annulus flush with both surfaces of floor or wall _____________ Min. 25mm (1”) thick packed into each side of opening floor & wall, recessed to take sealant |
(cUL) |
||
|
GYPSUM WALL BOARD CONSTRUCTION |
||||||||
|
305mm (12") diameter or smaller |
1 & 2 |
0 to 48mm (1-7/8") annulus |
Wall - Gypsum Board as rated for 1 & 2 hr |
A/D FIREBARRIER Intumescent Sealant |
Min. 13mm or 16mm (½” or 5/8”) inch thick within annulus, flush both surfaces of wall Foam Backer optional |
(cUL) |
||
|
275mm (11“) diameter or smaller |
2 |
6mm (¼”) annulus |
Wall – Gypsum Board |
A/D FIREBARRIER Silicone |
Min. 25mm (1”) thick within annulus, flush both surfaces of wall |
|||
|
203mm (8") diameter or smaller |
2 |
0 to 22mm (7/8”) annulus |
Wall - Gypsum Board |
A/D FIREBARRIERIntumescent Sealant or Acrylic _____________ A/D FIREBARRIER Mineral Wool |
Min. 13mm (½”) thick within annulus, flush both surfaces of wall _____________ Min. 13mm (½”) thick packed into opening both sides of wall |
(cUL) |
||
|
51mm (2") diameter or smaller |
1 & 2 |
0 to 48mm (1-7/8") annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone |
Min.16mm (5/8”) inch thick within annulus, flush both surfaces of wall |
|||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
||
|
WOOD CONSTRUCTION |
||||||||
|
203mm (8") diameter or smaller |
1 & 2 |
0 to 22mm (7/8") annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent Sealant |
Min.16mm (5/8”) thick within annulus on top at floor Min. 16mm (5/8”) thick within annulus on bottom surface ceiling- 13mm (½”) crown |
(cUL) |
||
|
169mm (6.5") or smaller |
1 |
6mm (¼") annulus |
Floor - Lumber Ceiling - Gypsum Board (chase wall optional) |
A/D FIREBARRIER Silicone |
Min. 29mm (1-1/8”) thick within annulus on top of floor Min. 13mm (½”) thick within annulus on bottom surface of ceiling |
|||
|
102mm (4") diameter or smaller |
1 |
0 to 22mm (7/8”) |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Intumescent sealant Foam Backer Rod |
Min. 13mm (½”) thick within annulus on top at floor Min. 13mm (½“) thick within annulus on bottom surface ceiling and 6mm (¼”) at point of contact Foam Backer Rod |
(cUL) |
||
top of page |
||||||||
|
PLASTIC & GLASS PIPE (50 Pa testing required for dry system) |
|
|
||||||
|
Max. Size Penetration Diameter |
Rating (h) |
Max Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
Application Thickness |
System No. |
||
|
CONCRETE CONSTRUCTION |
||||||||
|
167mm (6”), PVC, CPVC or smaller Not 50 Pa tested |
2 |
0 to 10mm (0" to 3/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone ____________ A/D FIREBARRIER Collar |
Min. 10mm ( 3/8”) thick within annulus flush with top of floor or both surfaces of wall _______________
|
C-AJ-2186 (cUL) |
||
|
102mm (4”), PVC, CPVC, or smaller Not 50 Pa tested |
1 |
0 to 38mm (1½”) nom. annulus |
Floor - Concrete (4½" min. thick Concrete) |
A/D FIREBARRIER Intumescent Sealant Foam Backer optional |
Min. 13mm (½”) thick within annulus flush with top of floor add 13mm (½”) crown Foam Backer optional |
(cUL) |
||
|
76mm (3”), PVC, CPVC or smaller Not 50 Pa tested |
2 |
19mm to 22mm (¾" to 7/8”) annulus |
Floor - Concrete Wall - Concrete Concrete Block or Precast (hollow core) Conc. |
A/D FIREBARRIER Intumescent Sealant _____________ Foam backer rod optional |
Min. 51mm (2”) thick within annulus flush with top of floor or both surfaces of wall _______________ optional |
(cUL) |
||
|
51mm (2”),PVC, CPVC or smaller Not 50 Pa tested |
2 |
19mm to 35mm (¾" to 1-3/8") annulus |
Floor - Concrete Wall - Concrete or Concrete Block |
A/D FIREBARRIER Silicone or Silicone SL _____________ A/D FIREBARRIER Mineral Wool |
Min. 25mm (1”) thick within annulus flush with top of floor or both surfaces of wall _____________ Min. 102mm (4”) inch thick packed into opening (wall both sides) |
C-AJ-2150 (cUL) |
||
|
102mm (4”), PVC, CPVC, ABS or smaller Not 50 Pa tested |
2 |
19mm (¾") nom. annulus |
Floor - Concrete ( 65mm (2½)" min. thick Concrete) |
A/D FIREBARRIER Wrap Strip
|
51mm (2") wide Wrap Strip (3 layers of ¼” wrap strip to make ¾” annular) |
(cUL) |
||
|
51mm (2”) PVC, ABS or smaller 25mm (1") PEX or smaller 50 Pa tested |
2 |
8 to 16 mm (5/16" to 5/8”) nom annulus |
Wall - Concrete |
A/D FIREBARRIER Wrap Strip |
25mm or 50mm (1” or 2") wide Wrap Strip (see fire test design for further details) Applied both sides of wall |
W-J-2141 (cUL) |
||
|
51mm (2”) PVC, CPVC, ABS or smaller 25mm (1") PEX or smaller Not 50 Pa tested |
2 |
8 mm (5/16") nom annulus |
Wall - Concrete |
A/D FIREBARRIER Wrap Strip |
25 mm (1") wide Wrap Strip. Applied both sides of wall. |
W-J-2128 (cUL) |
||
|
GYPSUM WALL BOARD CONSTRUCTION |
||||||||
|
167 mm (6”), PVC, CPVC or smaller Not 50 Pa tested |
2 |
6mm (¼") annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Silicone ___________ A/D FIREBARRIER Collar |
Min. 25mm (1”) thick within annulus flush on both surfaces of wall _______________
|
W-L-2155 (cUL) |
||
|
51mm (2)” PVC, CPVC, ABS or smaller. 2mm (1") PEX or smaller 51mm (2”) CPVC Flowguard Gold & Blazemaster |
1 & 2 |
6mm to 35mm (¼” to 1-3/8”) nom annulus |
Wall -Gypsum Board |
A/D FIREBARRIERIntumescent Sealant |
Min.16mm (5/8”) thick within annulus flush on both surfaces of wall Plus a 6mm (¼”) crown around
|
(cUL) |
||
|
51mm (2”). PVC, CPVC, ABS or smaller. 25mm (1") PEX or smaller Not 50 Pa tested |
1 & 2 |
8mm (5/16") nom annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Wrap Strip |
25mm (1") wide Wrap Strip on both sides of wall. |
W-L-2350 (cUL) |
||
|
51mm (2”)., ABS or smaller. 38mm (1½”) PVC or 25mm (1") PEX or smaller 50 Pa tested |
1 & 2 |
8mm to 10mm (5/16 to 13/32") nom annulus |
Wall -Gypsum Board |
A/D FIREBARRIER Wrap Strip |
51mm (2") wide Wrap Strip on both sides of wall. |
W-L-2372 (cUL) |
||
|
51 mm (2”),PVC, CPVC or smaller Not 50 Pa tested |
2 |
13mm to 29mm (½" to 1-1/8") nom annulus |
Wall -Gypsum Board (sleeved) |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Mineral Wool |
Min. 19mm (¾”) thick within annulus, flush with both ends _____________ Min. 51mm (2”) thick packed into opening on each side of wall |
W-L-2157 (cUL) |
||
|
WOOD CONSTRUCTION |
||||||||
|
169mm (6”),PVC, CPVC or Smaller 50 Pa tested |
1 |
7 mm (¼") nom annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Collar |
Fill annulus Space to 32mm & 6.4mm (¼") crown on top |
|||
|
115mm (4”),PVC, CPVC ABS or Smaller 50 Pa tested |
1 |
12mm (½") nom annulus |
Floor - Lumber Ceiling - Gypsum Board |
A/D FIREBARRIER Silicone _____________ A/D FIREBARRIER Collar |
Fill annulus Space to 32mm & 6.4mm (¼") crown on top |
|||