FIREBARRIER Firestopping Materials

Index of Firestop Systems and Designs for Canada – by Penetration Type and Joints

HOME                                                                                                                               GO UP ONE LEVEL

Quick Links to Penetration Types

steel Conduit and EMT
Iron Pipe cables
copper Multiple Penetrations
insulated pipe joints
Nonmetallic (plastic) Pipe and Conduit Blank Openings
ducts  

 

 

 

 

 

 

 

 

 

 

    Steel Pipe

Max. Size Penetration

mm (in.), sch.

Rating (h)

Max. Size Opening

Construction

Type (s)

A/D FIREBARRIER Product Required

System

No.

Testing

Agency

F

FH

FT

FTH

50 (2), 40

1 & 3

0 & 2

See design

F/W - C

MW & S or SL

SP159

ULC

50 (2), 40

3

1 & 2

120 x 120 mm

F/W - C

MW & S or SL

SP160

ULC

51 (2), 10

2

0

0 - 47.5 mm

annulus

W - gyp

S

SP926

ULC

75 (3), 10

2

0

0 - 44.5 mm

annulus

W - gyp

INT

SP964

ULC

76 (3), 10

2

0

0 - 47.5 mm

annulus

W - gyp

S

SP927

ULC

76 (3), 10

2

0

0 - 47.5 mm

annulus

W - gyp

MW & S

SP928

ULC

90 (3½), 40

3

0,1,2 & 3

25 mm

nom. annulus

F/W - C

MW & S or SL

SP162

ULC

100 (4), 40

2

0 - 64 mm

annulus

F/W - C

Mortar

SP765

ULC

102 (4), 10

1

0

0 - 13 mm

annulus

F – lumber

Cl - gyp

INT

SP1002

ULC

102 (4), 40

0

19 mm

nom. annulus

W - gyp

S

SP625

ULC

152 (6), 10

3

0

0 - 28 mm

annulus

F- C

W -C or CB

MW & S or SL

SP880

ULC

169 (6⅝), 40

1

¾

6.4 mm

nom. annulus

F - wood/gyp

S

SP365

ULC

169 (6⅝), 40

2

0

6.4 mm

nom. annulus

F - C or PC

S

SP421

ULC

180 (7), 40

3

0 & 3

25 mm

nom. annulus

F - C

MW & S, SL,

N or NS

SP219

ULC

200 (8), 40

opt. sleeve

2

0

0 - 85 mm

annulus

F- C or PC

W - CB

MW & S

SP760

ULC

200 (8),

 Sch 5

1 & 2 0

0 - 38 mm

annulus

W - gyp INT SP1090 ULC

204 (8), 40

opt. sleeve

2

0

0 - 85 mm

annulus

F/W - C

MW & NS

SP759

ULC

250 (10), 40

2

0

0

0 - 64 mm

annulus

FW - C or CB

MW & S

SP763

ULC

250 (10), 10

1 & 2

0

0 - 44.5 mm

annulus

W - gyp

INT

SP966

ULC

254 (10), 40

2

0

See design

W - gyp

MW & S

SP624

ULC

Max. Size Penetration

mm (in.), sch

Rating (h)

Max. Size Opening

Construction

Type (s)

A/D FIREBARRIER Product Required

System

No.

Testing

Agency

F

FH

FT

FTH

275 (10¾), 40

2

0

6.4 mm

nom. annulus

W - gyp

S

SP324

ULC

275 (10¾), 40

2

0

6.4 mm

nom. annulus

F- C

W -C or CB

S

SP394

ULC

400 (15¾), 40

2

0

0 - 102 mm

annulus

F- C

W -C or CB

MW & S

SP762

ULC

600 (24), 10

1 & 2

0

0 – 25.4 mm

annulus

W - gyp

MW & NS

SP1080

ULC

610 (24), 10

1

0

6.4 - 12.7 mm

annulus

W - gyp

INT

SP989

ULC

610 (24), 10

1

0

0 - 32 mm

annulus

W - gyp

INT

SP984

ULC

610 (24), 10

2

0

0 -28 mm

annulus

F- C

W -C or CB

S or SL & backer rod

SP930

ULC

610 (24), 10

2

0

0 -51 mm

annulus

F- C

W -C or CB

S or SL & backer rod

SP931

ULC

610 (24), 10

2

0

0 - 13 mm

annulus

W - gyp

INT

SP968

ULC

600 (24), 10

2

0

0 - 22 mm

annulus

F- C or PC

W -C or CB

INT

SP1077

ULC

610 (24), 10

2

0

0 - 38 mm

annulus

W - gyp

MW & INT

SP967

ULC

600 (24), 10

opt. sleeve

2

0

0 - 56 mm

annulus

F- C or PC

W -C or CB

MW & INT

SP1076

ULC

610 (24), 10

3

0

0 -25 mm

annulus

F/W - C

MW & INT

SP956

ULC

610 (24), 10

3

0

13 - 35 mm

annulus

F- C

W -C or CB

MW & NS

SP882

ULC

610 (24), 10

3

0

0 -51 mm

annulus

F- C

W -C or CB

MW & S or SL

SP929

ULC

610 (24), 10

3

0

0 -50 mm

annulus

F/W - C

MW & INT

& backer rod

SP957

ULC

610 (24), 10

3

0

0 -51 mm

annulus

F/W - C

MW & INT

SP961

ULC

  Steel Pipe - cUL Systems                                                             top of page

Max. Size Penetration

mm (in.) sch.

Rating (h)

Max. Size Opening

Construction

Type (s)

A/D FIREBARRIER Product Required

System

No.

Testing

Agency

F

T

51 (2) 40

3

1/2

0 – 1-13/16 in. annulus

F- C

W -C or CB

Putty

CAJ1461

cUL

102 (4), 10

1

1

0 -1/2 in. annulus

F- C

Cl - gyp

INT

FE1014

cUL

102 (4) 10

3

0

3/4 in. annulus

F- C

W -C or CB

Putty

CAJ1460

cUL

152 (6), 10

1

1

1/4 in. nom. annulus

F- C

Cl - gyp

S

FE1015

cUL

204 (8), 40

2

0

0 – 3-7/8 in. annulus

F- C or PC

W -C or CB

MW & S

CAJ1229

cUL

610 (24), 10

3

0

2 in. annulus

F- C

W -C or CB

Mortar

CAJ1196

cUL

      Iron Pipe (Cast or Ductile)                                                                  top of page

Max. Size Penetration

mm (in.)

Rating (h)

Max. Size Opening

Construction

Type (s)

A/D FIREBARRIER Product Required

System

No.

Testing

Agency

F

FH

FT

FTH

50 (2),

Min. 1.9 mm wall thickness

3

1 & 2

13 mm

nom. annulus

F/W - C

S or SL

SP161

ULC

50 (2)

1 & 3

0 &2

See design

F/W - C

MW & S or SL

SP159

ULC

50 (2)

3

1 & 2

120 x 120 mm

F/W - C

MW & S or SL

SP160

ULC

51 (2)

1 or 2

0

0 - 47.5 mm

annulus

W - gyp

S

SP926

ULC

76 (3)

2

0

0 - 47.5 mm

annulus

W - gyp

S

SP927

ULC

76 (3)

2

0

0 - 47.5 mm

annulus

W - gyp

MW & S

SP928

ULC

90 (3½)

3

0,1,2&3

25 mm

nom. annulus

F/W - C

MW & S or SL

SP162

ULC

102 (4)

1

0

0 - 13 mm

annulus

F – lumber

Cl - gyp

INT

SP1002

ULC

152 (6)

3

0

0 - 28 mm

annulus

F- C

W -C or CB

MW & S or SL

SP880

ULC

169 (6⅝),

1

¾

6.4 mm

nom. annulus

F - wood/gyp

S

SP365

ULC

180 (7),

 opt. sleeve

3

0 & 3

25 mm

nom. annulus

F- C

MW & S, SL,

N or NS

SP219

ULC

200 (8),

 opt. sleeve

2

0

0 - 85 mm

annulus

F- C, P or PM

W - CB

MW & S

SP760

ULC

200 (8),

1 & 2 0

0 - 38 mm

annulus

W - gyp

INT

SP1090 ULC

204 (8)

opt. sleeve

2

0

0 - 85 mm

annulus

F/W - C

MW & NS

SP759

ULC

250 (10)

1 & 2

0

0 - 44.5 mm

annulus

W - gyp

INT

SP966

ULC

275 (10)

2

0

6.4 mm

nom. annulus

W - gyp

S

SP324

ULC

400 (15¾)

opt. sleeve

2

0

0 - 102 mm

annulus

F/W - C or CB

MW & S

SP762

ULC

610 (24)

1

0

6.4 – 12.7 mm

annulus

W - gyp

INT

SP989

ULC

600 (24)

1 & 2

0

0 – 25.4 mm

annulus

W - gyp

MW & NS

SP1080

ULC

610 (24),

2

0

1

0

0 - 152 mm

annulus

F/W - C

MW & S or SL

SP383

ULC

610 (24)

1

0

0 - 32 mm

annulus

W - gyp

INT

SP984

ULC

610 (24)

2

0

0 -28 mm

annulus

F- C

W -C or CB

S or SL & backer rod

SP930

ULC

610 (24)

2

0

0 -51 mm

annulus

F- C

W -C or CB

S or SL & backer rod

SP931

ULC

610 (24)

2

0

0 - 13 mm

annulus

W - gyp

INT

SP968

ULC

600 (24),

2

0

0 - 22 mm

annulus

F- C or PC

W -C or CB

INT

SP1077

ULC

610 (24)

2

0

0 - 38 mm

annulus

W - gyp

MW & INT

SP967

ULC

600 (24)

opt. sleeve

2

0

0 - 56 mm

annulus

F- C or PC

W -C or CB

MW & INT

SP1076

ULC

610 (24)

3

0

13 - 35 mm

annulus

F- C

W -C or CB

MW & NS

SP882

ULC

610 (24)

3

0

0 -51 mm

annulus

F- C

W -C or CB

MW & S or SL

SP929

ULC

610 (24)

3

0

0 -25 mm

annulus

F/W - C

MW & INT

SP956

ULC

610 (24)

3

0

0 -50 mm

annulus

F/W - C

MW & INT

& backer rod

SP957

ULC

610 (24)

3

0

0 -51 mm

annulus

F/W - C

MW & INT

SP961

ULC

  Iron Pipe (Cast or Ductile) - cUL Systems                                      top of page

Max. Size Penetration

mm (in.)

Rating (h)

Max. Size Opening

Construction

Type (s)

A/D FIREBARRIER Product Required

System

No.

Testing

Agency

F

T

51 (2)

3

1/2

0 – 1-13/16 in. annulus

F- C

W -C or CB

Putty

CAJ1461

cUL

102 (4)

1

1

0 -1/2 in. annulus

F- C

Cl - gyp

INT

FE1014

cUL

152 (6)

1

1

1/4 in. nom. annulus

F- C

Cl - gyp

S

FE1015

cUL

204 (8)

2

0

0 – 3-7/8 in. annulus

F- C or PC

W -C or CB

MW & S

CAJ1229

cUL

      Copper Pipe or Tube                                                                          top of page

Max. Size Penetration

mm (in.), sch.

Rating (h)

Max. Size Opening

Construction

Type (s)

A/D FIREBARRIER Product Required

System

No.

Testing

Agency

F

FH

FT

FTH

13.9 (½)

3

0 & 3

See design

F - C

MW & S, SL,

N or NS

SP221

ULC

50 (2), 1.6 mm wall thickness

opt. sleeve

1-1/2

0

0, 3/4

0

See design

F- C

W -C or CB

MW & NS

SP761

ULC

51 (2)

1 & 3

0 & 2

See design

F/W - C

MW & S or SL

SP159

ULC

51 (2), L

2

0

0 - 47.5 mm

annulus

W - gyp

S

SP926

ULC

75 (3), L

2

0

0 - 44.5 mm

annulus

W - gyp

INT

SP964

ULC

76 (3), L

2

0

0 - 47.5 mm

annulus

W - gyp

S

SP927

ULC

76 (3), L

2

0

0 - 47.5 mm

annulus

W - gyp

MW & S

SP928

ULC

80 (3⅛)

2

0

6.4 mm

nom. annulus

F - C or P

S

SP421

ULC

90 (3½)

3

0,1,2& 3

25 mm

nom. annulus

F/W - C

MW & S or SL

SP162

ULC

102 (4)

1

0

6.4 mm

nom. annulus

F - wood/gyp

S

SP365

ULC

102 (4), L

1

0

0 - 13 mm

annulus

F – lumber

Cl - gyp

INT

SP1002

ULC

105 (4¼)

2

0

6.4 mm

nom. annulus

W - gyp

S

SP324

ULC

100 (4), L or reg or heavier

1 & 2 0

0 - 38 mm

annulus

W - gyp INT SP1090 ULC

105 (4¼)

2

0

6.4 mm

nom. annulus

W/F - C or CB

S

SP394

ULC

105 (4¼)

2

0

6.4 mm

nom. annulus

F - C or P

S

SP421

ULC

152 (6), L

1

0

6.4 – 12.7 mm

annulus

W - gyp

INT

SP989

ULC

152 (6), L

1

0

0 - 32 mm

annulus

W - gyp

INT

SP984

ULC

150 (6), L

1 & 2

0

0 – 25.4 mm

annulus

W - gyp

MW & NS

SP1080

ULC

150 (6), L

2

0

0 - 22 mm

annulus

F- C or PC

W -C or CB

INT

SP1077

ULC

150 (6), M

opt. sleeve

2

0

0 - 56 mm