Quick Links to Penetration Types
| steel | Conduit and EMT |
| Iron Pipe | cables |
| copper | Multiple Penetrations |
| insulated pipe | joints |
| Nonmetallic (plastic) Pipe and Conduit | Blank Openings |
| ducts |

Steel Pipe |
||||||||||
Max. Size Penetration mm (in.), sch. |
Rating (h) |
Max. Size Opening |
ConstructionType (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
||||
|
F |
FH |
FT |
FTH |
|||||||
|
50 (2), 40 |
1 & 3 |
0 & 2 |
See design |
F/W - C |
MW & S or SL |
ULC |
||||
|
50 (2), 40 |
3 |
1 & 2 |
120 x 120 mm |
F/W - C |
MW & S or SL |
ULC |
||||
|
51 (2), 10 |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
S |
ULC |
||||
|
75 (3), 10 |
2 |
0 |
0 - 44.5 mm annulus |
W - gyp |
INT |
ULC |
||||
|
76 (3), 10 |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
S |
ULC |
||||
|
76 (3), 10 |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
MW & S |
ULC |
||||
|
90 (3½), 40 |
3 |
0,1,2 & 3 |
25 mm nom. annulus |
F/W - C |
MW & S or SL |
ULC |
||||
|
100 (4), 40 |
2 |
1½ |
0 - 64 mm annulus |
F/W - C |
Mortar |
ULC |
||||
|
102 (4), 10 |
1 |
0 |
0 - 13 mm annulus |
F – lumber Cl - gyp |
INT |
ULC |
||||
|
102 (4), 40 |
1½ |
0 |
19 mm nom. annulus |
W - gyp |
S |
ULC |
||||
|
152 (6), 10 |
3 |
0 |
0 - 28 mm annulus |
F- C W -C or CB |
MW & S or SL |
ULC |
||||
|
169 (6⅝), 40 |
1 |
¾ |
6.4 mm nom. annulus |
F - wood/gyp |
S |
ULC |
||||
|
169 (6⅝), 40 |
2 |
0 |
6.4 mm nom. annulus |
F - C or PC |
S |
ULC |
||||
|
180 (7), 40 |
3 |
0 & 3 |
25 mm nom. annulus |
F - C |
MW & S, SL, N or NS |
ULC |
||||
|
200 (8), 40 opt. sleeve |
2 |
0 |
0 - 85 mm annulus |
F- C or PC W - CB |
MW & S |
ULC |
||||
|
200 (8), Sch 5 |
1 & 2 | 0 |
0 - 38 mm annulus |
W - gyp | INT | SP1090 | ULC | |||
|
204 (8), 40 opt. sleeve |
2 |
0 |
0 - 85 mm annulus |
F/W - C |
MW & NS |
ULC |
||||
|
250 (10), 40 |
2 |
0 |
1½ |
0 |
0 - 64 mm annulus |
FW - C or CB |
MW & S |
ULC |
||
|
250 (10), 10 |
1 & 2 |
0 |
0 - 44.5 mm annulus |
W - gyp |
INT |
ULC |
||||
|
254 (10), 40 |
2 |
0 |
See design |
W - gyp |
MW & S |
ULC |
||||
|
Max. Size Penetration mm (in.), sch |
Rating (h) |
Max. Size Opening |
ConstructionType (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
||||
|
F |
FH |
FT |
FTH |
|||||||
|
275 (10¾), 40 |
2 |
0 |
6.4 mm nom. annulus |
W - gyp |
S |
ULC |
||||
|
275 (10¾), 40 |
2 |
0 |
6.4 mm nom. annulus |
F- C W -C or CB |
S |
ULC |
||||
|
400 (15¾), 40 |
2 |
0 |
0 - 102 mm annulus |
F- C W -C or CB |
MW & S |
ULC |
||||
|
600 (24), 10 |
1 & 2 |
0 |
0 – 25.4 mm annulus |
W - gyp |
MW & NS |
ULC |
||||
|
610 (24), 10 |
1 |
0 |
6.4 - 12.7 mm annulus |
W - gyp |
INT |
ULC |
||||
|
610 (24), 10 |
1 |
0 |
0 - 32 mm annulus |
W - gyp |
INT |
ULC |
||||
|
610 (24), 10 |
2 |
0 |
0 -28 mm annulus |
F- C W -C or CB |
S or SL & backer rod |
ULC |
||||
|
610 (24), 10 |
2 |
0 |
0 -51 mm annulus |
F- C W -C or CB |
S or SL & backer rod |
ULC |
||||
|
610 (24), 10 |
2 |
0 |
0 - 13 mm annulus |
W - gyp |
INT |
ULC |
||||
600 (24), 10 |
2 |
0 |
0 - 22 mm annulus |
F- C or PC W -C or CB |
INT |
ULC |
||||
|
610 (24), 10 |
2 |
0 |
0 - 38 mm annulus |
W - gyp |
MW & INT |
ULC |
||||
|
600 (24), 10 opt. sleeve |
2 |
0 |
0 - 56 mm annulus |
F- C or PC W -C or CB |
MW & INT |
ULC |
||||
|
610 (24), 10 |
3 |
0 |
0 -25 mm annulus |
F/W - C |
MW & INT |
ULC |
||||
|
610 (24), 10 |
3 |
0 |
13 - 35 mm annulus |
F- C W -C or CB |
MW & NS |
ULC |
||||
|
610 (24), 10 |
3 |
0 |
0 -51 mm annulus |
F- C W -C or CB |
MW & S or SL |
ULC |
||||
|
610 (24), 10 |
3 |
0 |
0 -50 mm annulus |
F/W - C |
MW & INT & backer rod |
ULC |
||||
610 (24), 10 |
3 |
0 |
0 -51 mm annulus |
F/W - C |
MW & INT |
ULC |
||||
Steel Pipe - cUL Systems top of page |
||||||||||
|
Max. Size Penetration mm (in.) sch. |
Rating (h) |
Max. Size Opening |
ConstructionType (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
||||
|
F |
T |
|||||||||
|
51 (2) 40 |
3 |
1/2 |
0 – 1-13/16 in. annulus |
F- C W -C or CB |
Putty |
cUL |
||||
|
102 (4), 10 |
1 |
1 |
0 -1/2 in. annulus |
F- C Cl - gyp |
INT |
cUL |
||||
|
102 (4) 10 |
3 |
0 |
3/4 in. annulus |
F- C W -C or CB |
Putty |
cUL |
||||
|
152 (6), 10 |
1 |
1 |
1/4 in. nom. annulus |
F- C Cl - gyp |
S |
cUL |
||||
|
204 (8), 40 |
2 |
0 |
0 – 3-7/8 in. annulus |
F- C or PC W -C or CB |
MW & S |
cUL |
||||
|
610 (24), 10 |
3 |
0 |
2 in. annulus |
F- C W -C or CB |
Mortar |
cUL |
||||
|
Max. Size Penetration mm (in.) |
Rating (h) |
Max. Size Opening |
ConstructionType (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|||||||
|
F |
FH |
FT |
FTH |
||||||||||
50 (2), Min. 1.9 mm wall thickness |
3 |
1 & 2 |
13 mm nom. annulus |
F/W - C |
S or SL |
ULC |
|||||||
|
50 (2) |
1 & 3 |
0 &2 |
See design |
F/W - C |
MW & S or SL |
ULC |
|||||||
|
50 (2) |
3 |
1 & 2 |
120 x 120 mm |
F/W - C |
MW & S or SL |
ULC |
|||||||
|
51 (2) |
1 or 2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
S |
ULC |
|||||||
|
76 (3) |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
S |
ULC |
|||||||
|
76 (3) |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
MW & S |
ULC |
|||||||
|
90 (3½) |
3 |
0,1,2&3 |
25 mm nom. annulus |
F/W - C |
MW & S or SL |
ULC |
|||||||
|
102 (4) |
1 |
0 |
0 - 13 mm annulus |
F – lumber Cl - gyp |
INT |
ULC |
|||||||
|
152 (6) |
3 |
0 |
0 - 28 mm annulus |
F- C W -C or CB |
MW & S or SL |
ULC |
|||||||
|
169 (6⅝), |
1 |
¾ |
6.4 mm nom. annulus |
F - wood/gyp |
S |
ULC |
|||||||
|
180 (7), opt. sleeve |
3 |
0 & 3 |
25 mm nom. annulus |
F- C |
MW & S, SL, N or NS |
ULC |
|||||||
|
200 (8), opt. sleeve |
2 |
0 |
0 - 85 mm annulus |
F- C, P or PM W - CB |
MW & S |
ULC |
|||||||
|
200 (8), |
1 & 2 | 0 |
0 - 38 mm annulus |
W - gyp |
INT |
SP1090 | ULC | ||||||
|
204 (8) opt. sleeve |
2 |
0 |
0 - 85 mm annulus |
F/W - C |
MW & NS |
ULC |
|||||||
|
250 (10) |
1 & 2 |
0 |
0 - 44.5 mm annulus |
W - gyp |
INT |
ULC |
|||||||
|
275 (10) |
2 |
0 |
6.4 mm nom. annulus |
W - gyp |
S |
ULC |
|||||||
|
400 (15¾) opt. sleeve |
2 |
0 |
0 - 102 mm annulus |
F/W - C or CB |
MW & S |
ULC |
|||||||
|
610 (24) |
1 |
0 |
6.4 – 12.7 mm annulus |
W - gyp |
INT |
ULC |
|||||||
|
600 (24) |
1 & 2 |
0 |
0 – 25.4 mm annulus |
W - gyp |
MW & NS |
ULC |
|||||||
|
610 (24), |
2 |
0 |
1 |
0 |
0 - 152 mm annulus |
F/W - C |
MW & S or SL |
ULC |
|||||
|
610 (24) |
1 |
0 |
0 - 32 mm annulus |
W - gyp |
INT |
ULC |
|||||||
|
610 (24) |
2 |
0 |
0 -28 mm annulus |
F- C W -C or CB |
S or SL & backer rod |
ULC |
|||||||
|
610 (24) |
2 |
0 |
0 -51 mm annulus |
F- C W -C or CB |
S or SL & backer rod |
ULC |
|||||||
|
610 (24) |
2 |
0 |
0 - 13 mm annulus |
W - gyp |
INT |
ULC |
|||||||
|
600 (24), |
2 |
0 |
0 - 22 mm annulus |
F- C or PC W -C or CB |
INT |
ULC |
|||||||
|
610 (24) |
2 |
0 |
0 - 38 mm annulus |
W - gyp |
MW & INT |
ULC |
|||||||
|
600 (24) opt. sleeve |
2 |
0 |
0 - 56 mm annulus |
F- C or PC W -C or CB |
MW & INT |
ULC |
|||||||
|
610 (24) |
3 |
0 |
13 - 35 mm annulus |
F- C W -C or CB |
MW & NS |
ULC |
|||||||
|
610 (24) |
3 |
0 |
0 -51 mm annulus |
F- C W -C or CB |
MW & S or SL |
ULC |
|||||||
|
610 (24) |
3 |
0 |
0 -25 mm annulus |
F/W - C |
MW & INT |
ULC |
|||||||
|
610 (24) |
3 |
0 |
0 -50 mm annulus |
F/W - C |
MW & INT & backer rod |
ULC |
|||||||
610 (24) |
3 |
0 |
0 -51 mm annulus |
F/W - C |
MW & INT |
ULC |
|||||||
Iron Pipe (Cast or Ductile) - cUL Systems top of page |
|||||||||||||
|
Max. Size Penetration mm (in.) |
Rating (h) |
Max. Size Opening |
ConstructionType (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|||||||
|
F |
T |
||||||||||||
|
51 (2) |
3 |
1/2 |
0 – 1-13/16 in. annulus |
F- C W -C or CB |
Putty |
cUL |
|||||||
|
102 (4) |
1 |
1 |
0 -1/2 in. annulus |
F- C Cl - gyp |
INT |
cUL |
|||||||
|
152 (6) |
1 |
1 |
1/4 in. nom. annulus |
F- C Cl - gyp |
S |
cUL |
|||||||
|
204 (8) |
2 |
0 |
0 – 3-7/8 in. annulus |
F- C or PC W -C or CB |
MW & S |
cUL |
|||||||
|
Max. Size Penetration mm (in.), sch. |
Rating (h) |
Max. Size Opening |
ConstructionType (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|||
|
F |
FH |
FT |
FTH |
||||||
|
13.9 (½) |
3 |
0 & 3 |
See design |
F - C |
MW & S, SL, N or NS |
ULC |
|||
|
50 (2), 1.6 mm wall thickness opt. sleeve |
1-1/2 |
0 |
0, 3/4 |
0 |
See design |
F- C W -C or CB |
MW & NS |
ULC |
|
|
51 (2) |
1 & 3 |
0 & 2 |
See design |
F/W - C |
MW & S or SL |
ULC |
|||
|
51 (2), L |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
S |
ULC |
|||
|
75 (3), L |
2 |
0 |
0 - 44.5 mm annulus |
W - gyp |
INT |
ULC |
|||
|
76 (3), L |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
S |
ULC |
|||
|
76 (3), L |
2 |
0 |
0 - 47.5 mm annulus |
W - gyp |
MW & S |
ULC |
|||
|
80 (3⅛) |
2 |
0 |
6.4 mm nom. annulus |
F - C or P |
S |
ULC |
|||
|
90 (3½) |
3 |
0,1,2& 3 |
25 mm nom. annulus |
F/W - C |
MW & S or SL |
ULC |
|||
|
102 (4) |
1 |
0 |
6.4 mm nom. annulus |
F - wood/gyp |
S |
ULC |
|||
|
102 (4), L |
1 |
0 |
0 - 13 mm annulus |
F – lumber Cl - gyp |
INT |
ULC |
|||
|
105 (4¼) |
2 |
0 |
6.4 mm nom. annulus |
W - gyp |
S |
ULC |
|||
|
100 (4), L or reg or heavier |
1 & 2 | 0 |
0 - 38 mm annulus |
W - gyp | INT | SP1090 | ULC | ||
|
105 (4¼) |
2 |
0 |
6.4 mm nom. annulus |
W/F - C or CB |
S |
ULC |
|||
|
105 (4¼) |
2 |
0 |
6.4 mm nom. annulus |
F - C or P |
S |
ULC |
|||
|
152 (6), L |
1 |
0 |
6.4 – 12.7 mm annulus |
W - gyp |
INT |
ULC |
|||
|
152 (6), L |
1 |
0 |
0 - 32 mm annulus |
W - gyp |
INT |
ULC |
|||
|
150 (6), L |
1 & 2 |
0 |
0 – 25.4 mm annulus |
W - gyp |
MW & NS |
ULC |
|||
|
150 (6), L |
2 |
0 |
0 - 22 mm annulus |
F- C or PC W -C or CB |
INT |
ULC |
|||
|
150 (6), M opt. sleeve |
2 |
0 |
0 - 56 mm | ||||||