FIREBARRIER Firestopping Materials

Index of Firestop Systems and Designs for USA – by Penetration Type and Joints

 HOME                                                                                                                               GO UP ONE LEVEL

Quick Links to Penetration Types

 

Steel Pipe

Conduit and EMT

Iron Pipe

Cables

Copper Pipe or Tube

Multiple Penetrations

Insulated Pipe

Curtain Wall

Nonmetallic (plastic) Pipe and Conduit

Joints

Ducts

Blank Openings

  LEGEND
Max. Size Penetrant

Ratings / Listings

Construction Type Products

P = Pipe

Ca = Cables

CDI = Cast / Ductile

          Iron Pipe

CT = Cable Tray

Cond = Conduit

Cu = Copper

Ø = Diameter

 

USA : F and/or T

(See page 6 for description)

 

Testing Agencies

ULI - C-AJ, F-C, FF-D, FW-D,

 

ULC - SP, SPC, JF   & HW

ITS - AD/PHV, AD/PH  & AD/PV

FM -   FM #’s

F = Floor

W = Wall

Gyp = Gypsum WallBoard

C =    Concrete

CB =  Concrete Blocks

Cl =   Ceiling

PC =  Precast Hollow-core

SCI = Suspended Ceiling

 

AS = Acrylic Sealant

Collar

Inserts

IS = Intumescent Sealant

MW = Mineral Wool

Mortar

N = Seal

NS = Seal NS

Pillow

Putty

Putty Pads

S = Silicone

SL = Silicone SL

SA = SprayAcrylic

SM =SprayMastic

WS = Wrapstrip

CS = Collar Strip

 

Shading in table denotes A/D FIREBARRIER Optimum Systems – often the best system to select for the situation.

 

Steel Pipe

Max. Size Penetration

in., Sch.

Rating (h)

Max. Size Opening

Construction Type (s)

A/D FIREBARRIER Product Required

System No.

Testing

Agency

F

T

1¼, 5

3

¾

7/16”

nom. annulus

F- C

W -C or CB

Mortar & backer rod

CAJ-1126

ULI

1¼, 5

3

½

7/16”

nom. annulus

F- C

W -C or CB

MW & N or NS

C-AJ-1127

ULI

1¼, 5

3

¾

7/16”

nom. annulus

F- C

W -C or CB

MW & Mortar

C-AJ-1128

ULI

1¼, 5

1 & 2

1

¼”

nom. annulus

W - gyp

S

WL-1050

ULI

1½ & 3

¾”

nom. annulus

F- C

W -C or CB

MW & N

93

FM

2 & 3

¾”

nom. annulus

F- C

W -C or CB

Mortar & backer rod

92

FM

1-1/2, 10

3

3/4

0 - 1-7/8" annulus

F- C 

W -C or CB or PC

Putty II

C-AJ-1559

ULI

2, 10

2

0

0” – 1-7/8

annulus

W - C or CB

S

WJ-1085

ULI

2, 10

1 & 2

0

0” – 1-7/8”

annulus

W - gyp

S

WL-1198

ULI

2, 40

1 & 3

See system

48.3 in.²

F/W - C

MW & S or SL

AD/PHV 180-04

ITS

2, 40

3

1 & 2

19 in.²

F/W - C

MW & S or SL

AD/PHV 180-05

ITS

2, 40

3

1/2

0” – 1-13/16”

annulus

F- C

W -C or CB

Putty & backer rod

C-AJ-1461

ULI

2, 40

0 & 1½

½” – 2”

annulus

F- C

W -C or CB

MW & S or SL

83

FM

2

2

½”

nom. annulus

F- C

W -C or CB

S or SL

86

FM

2, 40

2

 

1”

nom. annulus

F/W - C

MW & S or SL

87

FM

3, 5

3

0

¾”

nom. annulus

F/W - C

MW & S or SL

C-AJ-1116

ULI

3, 5

3

0

¼” – 1-1/4”

annulus

F- C

W -C or CB

MW & S or SL

C-AJ-1117

ULI

3, 5

3

0

1” - 2-7/8”

annulus

F- C

W -C or CB

MW & S or SL

C-AJ-1129

ULI

3, 40

2 & 3

1”

nom. annulus

F/W - C

MW & S or SL

85

FM

3, 40

1

1”

nom. annulus

F- C

W -C or CB

MW & S or SL

236

FM

3⅛, 40

3

See design

1”

nom. annulus

F/W - C

MW & S or SL

AD/PHV 180-07

ITS

4, 10

1

1

1/8”

nom. annulus

F/CI -wood/gyp

S

F-C-1034

ULI

4, 10

1

1

0 - 7/8”

annulus

F-C

 W-gyp

chase wall

MW & IS or AS

F-C-1150

ULI

4, 10

3

0

¾”

nom. annulus

F- C

W -C or CB

Putty, opt backer rod

C-AJ-1460

ULI

6, 40

3

0

1” – 2-3/8

annulus

F- C

W -C or CB

MW & N or NS

C-AJ-1125

ULI

6, 10

3

0

2”

nom. annulus

F- C

W -C or CB

Mortar

C-AJ-1195

ULI

6, 40

1

0, ¾, 1

½”

nom. annulus

F/CI -wood/gyp

S

F-C-1011

ULI

6, 40

2

0

1”

nom. annulus

W - C or CB

MW & S

WJ-1064

ULI

6, 40

2

0

1”

nom. annulus

W - gyp

MW & S

WL-1151

ULI

8, 40

1 1/4

0 - 7/8”

annulus

F/CI-C/gyp

W-gyp

IS

opt backer rod

F-E-1021

ULI

8, 40

1, 2 1/4

0 - 7/8”

annulus

F-C

W-gyp

chase wall

IS

opt backer rod

F-C-1149

ULI

8, 40 opt galv. sleeve

1, 2

0

see design

W-gyp

MW & IS

W-L-1419

ULI

8, 40

2

0

0” – 3-7/8”

annulus

F/W - C or CB

MW & S

C-AJ-1229

ULI

8, 40

2

0

0” – 3-3/8”

annulus

F/W - C or CB

MW & NS

C-AJ-1450

ULI

8, 10

2

0

0 - 7/8”

annulus

W -C or CB

IS or AS

W-J-1203

ULI

8, 10

2

0

0 - 7/8”

annulus

W-gyp

MW & IS or AS

W-L-1417

ULI

1, 10

opt. sleeve

2

0

0 - 2”

annulus

W -C or CB

IS

W-J-1204

ULI

1, 10

opt. sleeve

3

1/4

0 - 1-7/8”

annulus

F-C

W-C, CB or PC

MW & IS

C-AJ-1561

ULI

10, 10

w / insulation

2

1

½” – 3/4”

annulus

W - gyp

2” WS

WL-5194

ULI

12, 10

opt galv. sleeve

1 & 2

0

0 - 1-7/8" annulus

W-gyp

IS

opt backer rod

W-L-1416

ULI

12, 10

2 &  3

0

see design

F-C

W-C, CB or PC

IS & MW

&/or Backer rod

C-AJ-1557

ULI

16, 40

2

0

0” – ¾”

annulus

F- C

W -C or CB

MW & S

C-AJ-1299

ULI

24, 10

3

0

2”

nom. annulus

F- C

W -C or CB

Mortar

C-AJ-1196

ULI

24, 40

2

0

0” – 7/8”

annulus

F- C

W -C or CB

MW & S

C-AJ-1322

ULI

24, 40

3

0

0” – 1-7/8”

annulus

F- C

W -C or CB

MW & S

C-AJ-1323

ULI

24, 40

3

0

½” – 1-3/8”

annulus

F- C

W -C or CB

MW & NS

C-AJ-1324

ULI

     top pf page

 

     Iron Pipe (Cast or Ductile)

Max. Size Penetration

in.

Rating (h)

Max. Size Opening

Construction Type (s)

A/D FIREBARRIER Product Required

System No.

Testing

Agency

F

T

2

2

0

0” – 1-7/8

annulus

W - C or CB

S

WJ-1085

ULI

2

1 & 2

0

0” – 1-7/8

annulus

W - gyp

S

WL-1198

ULI

2

3

1/2

0” – 1-13/16”

annulus

F- C

W -C or CB

Putty & backer rod

C-AJ-1461

ULI

3

3

0

¼” – 1-1/4”

annulus

F- C

W -C or CB

MW & S or SL

C-AJ-1117

ULI

4

1

1

0 - 7/8”

annulus

F-C

 W-gyp

chase wall

MW & IS or AS

F-C-1150

ULI

6

3

0

2”

nom. annulus

F- C

W -C or CB

Mortar

C-AJ-1195

ULI

6

2

0

½”

nom. annulus

F/CI -wood/gyp

S

F-C-1011

ULI

6

2

0

1”

nom. annulus

W - C or CB

MW & S

WJ-1064

ULI

6

2

0

1”

nom. annulus

W - gyp

MW & S

WL-1151

ULI

8

1 1/4

0 - 7/8”

annulus

F/CI-C/gyp

W-gyp

IS

opt backer rod

F-E-1021

ULI

8, 40 opt galv. sleeve

1, 2

0

see design

W-gyp

MW & IS

W-L-1419

ULI

8, 40

1, 2 1/4

0 - 7/8”

annulus

F-C

W-gyp

chase wall

IS

opt backer rod

F-C-1149

ULI

8

2

0

0 - 7/8”

annulus

W-C or CB

IS or AS

W-J-1203

ULI

8

2

0

0 - 7/8”

annulus

W-gyp

MW & IS or AS

W-L-1417

ULI

8

2

0

0” – 3-7/8”

annulus

F- C

W -C or CB

MW & S

CAJ-1229

ULI

8

opt. sleeve

2

0

0 - 2”

annulus

W -C or CB

IS

W-J-1204

ULI

8

2

0

0” – 3-3/8”

annulus

F/W - C or CB

MW & NS

CAJ-1450

ULI

8

opt. sleeve

3

1/4

0 - 1-7/8”

annulus

F-C

W-C, CB or PC

MW & IS

C-AJ-1561

ULI

12

opt galv. sleeve

1 & 2

0

0 - 1-7/8" annulus

W-gyp

IS

opt backer rod

W-L-1416

ULI

12

opt sleeve

2 &  3

0

see design

F-C

W-C, CB or PC

IS & MW

&/or Backer rod

C-AJ-1557

ULI

16

2

0

0” – ¾”

annulus

F- C

W -C or CB

MW & S

CAJ-1299

ULI

24

2

0

0” – 7/8”

annulus

F- C

W -C or CB

MW & S

CAJ-1322-

ULI

24

3

0

0” – 1-7/8”

annulus

F- C

W -C or CB

MW & S

C-AJ-1323

ULI

24

3

0

½” – 1-3/8”

annulus

F- C

W -C or CB

MW & NS

C-AJ-1324

ULI

 top of page

 

     Copper Pipe or Tube

Max. Size Penetration

in.

Rating (h)

Max. Size Opening

Construction Type (s)

A/D FIREBARRIER Product Required

System No.

Testing

Agency

F

T

½

3

3

2-3/4" max annulus

F-C

MW & S

AD/PH 180-03

ITS

½

3

see design

2-3/4" max annulus

F-C

MW & N or NS

AD/PHV18012

ITS

½

3

 

2-3/4" max annulus

F/W-C

MW & N

95

FM

2, L

2

0

0 - 1-7/8 annulus

W-C or CB

S

W-J-1085

ULI

2, L

1 & 2

0

0 - 1-7/8 annulus

W-gyp

S

W-L-1198

ULI

2

1,3

see design

1-7/32 max annulus

F/W-C

MW & S or SL

AD/PHV180-04

ITS

2

1-1/2 & 0

1/2 - 2" annulus

F-C

W-C or CB

MW & S or SL

83

FM

3, L or Reg

3

0

3/4" annulus

F-C

W-C or CB

MW & S or SL

C-AJ-1116

ULI

3, L or Reg

3

0

1-2-7/8" annulus

F-C

W-C or CB

MW & S or SL

C-AJ-1125

ULI

3, M or Reg 3 0

1-2-7/8" annulus

F-C

W-C or CB

MW & S or SL C-AJ-1129 ULI
3 3&2 3&2 1" nom. annulus F/W-C MW & S or SL 85 FM
3             1 1" nom. annulus

F-C

W-C or CB

MW & S or SL 236 FM
3-1/8 3 see design 1" max. annulus F/W-C MW & S or SL AD/PHV180-12 ITS

4, L or Reg

1

0

1/2" nom annulus

F/CI-C/gyp

W-gyp

S

F-C-1011

ULI

4, L or Reg

1 1/4

0 - 7/8”

annulus

F/CI-C/gyp

W-gyp

IS

opt backer rod

F-E-1021

ULI

4, L or Reg

1

1

1/8”

nom. annulus

F/CI -wood/gyp

S

F-C-1034

ULI

4, L or Reg

1

1

0 - 7/8”

annulus

F-C

 W-gyp

chase wall

MW & IS or AS

F-C-1150

ULI

4, L or Reg

opt galv. sleeve

1, 2

0

see design

W-gyp

MW & IS

W-L-1419

ULI

4, L or Reg

1, 2

1/4

0 - 7/8”

annulus

F-C

W-gyp

chase wall

IS

opt backer rod

F-C-1149

ULI

4, L or Reg

opt galv. sleeve

1 & 2

0

0 - 1-7/8" annulus

W-gyp

IS

opt backer rod

W-L-1416

ULI

4, L or Reg

2

0

0 - 7/8”

annulus

W-C or CB

IS or AS

W-J-1203

ULI

4, L or Reg

2

0

0 - 7/8”

annulus

W-gyp

MW & IS or AS

W-L-1417

ULI

4, L or Reg

opt. sleeve

2

0

0 - 2”

annulus

W -C or CB

IS

W-J-1204

ULI

4, L or Reg

opt. sleeve

3

1/4

0 - 1-7/8”

annulus

F-C

W-C, CB or PC

MW & IS

C-AJ-1561

ULI

6, L or Reg

opt. sleeve

2 &  3

0

see design

F-C

W-C, CB or PC

IS & MW

&/or Backer rod

C-AJ-1557

ULI

6, L or Reg

3

0

2”

nom. annulus

F- C

W -C or CB

Mortar

C-AJ-1195

ULI

6, K or Reg

2

0

0” – 7/8”

annulus

F- C

W -C or CB

MW & S

CAJ-1322-

ULI

6, L or Reg

3

0

0” – 1-7/8”

annulus

F- C

W -C or CB

MW & S

C-AJ-1323

ULI

6, K or Reg

3

0

½” – 1-3/8”

annulus

F- C

W -C or CB

MW & NS

C-AJ-1324

ULI

 

top of page

 

  Insulated Pipe

 

Max. Size Penetration

in., Type

Rating (h)

Max. Size Opening

Construction Type(s)

A/D FIREBARRIER Product Required

System

No.

Testing

Agency

F

T

2, Cu & steel

1

1

¼”

nom. annulus

F/CI -wood/gyp

S

F-C-5024

ULI

2, Cu & steel/iron

2

1

1/8 - 1/4" annulus

F-C

W-C or CB

MW & IS

C-AJ-5304

ULI

2, PVC & CPVC

2

1-1/4

see design

F-C

W-C or CB

MW & IS

C-AJ-5306

ULI

2, Cu

1

3/4 & 1

0 - 7/8" annulus

F/Cl-C/gyp

W-gyp

IS

opt backer rod

F-E-5011

ULI

3, Cu & steel

1 & 2

½

¼”

nom. annulus

W - gyp

S

WL-5031

ULI

3, Cu & steel

3

¾

¼”

nom. annulus

F- C

W -C or CB

MW & S or SL

C-AJ-5027

ULI

4, Cu & steel / iron

1

0

0” – 1-1/2”

annulus

F- C

W -C or CB

MW & S

C-AJ-5127

ULI

4, Cu & steel

1

¾

¼”

nom. annulus

F/CI -wood/gyp

S

F-C-5007

ULI

4, steel, iron

1

3/4 & 1

0 - 7/8" annulus

F/Cl-C/gyp

W-gyp

IS

opt backer rod

F-E-5011

ULI

4, Cu & steel / iron

1 & 2

1/2

0-1-3/8" annulus

W-gyp

IS

opt backer rod

W-L-5266

ULI

4, Cu

1-1/2 & 2

1 & 1/2

see design

F-C

W-C or CB

MW & IS or AS

C-AJ-5303

ULI

4, Cu

2

0 & 1

see design

W-gyp

IS, opt backer rod or MW & IS

W-L-5267

ULI

4, steel / iron

2

0” – 2-1/2”

annulus

F- C

W -C or CB

MW & Mortar

C-AJ-5095

ULI

4, Cu (L)

3

1

1/4 - 5/8" annulus

F-C

MW & S

F-A-5039

ULI

4, Cu

3

2

0 - 1" annulus

F-C

W-C or CB

MW & IS

C-AJ-1560

ULI

Cu & steel/iron

2 & 3

1, 1-1/4 & 1-1/2

see design

F- C

W -C or CB

MW & IS

C-AJ-5305

ULI

6, Cu & steel

1-1/2

1/2 & 3/4

0 - 4" annulus

F- C

W -C or CB

MW & S or SL

C-AJ-5064

ULI

8, steel / iron

1-1/2 & 2

1 & 1/2

see design

F- C

W -C or CB

MW & IS or AS

C-AJ-5303

ULI

8, steel / iron

2

0 & 1

see design

W-gyp

IS, opt backer rod or MW & IS

W-L-5267

ULI

8, steel / iron

3

1

1/4 - 5/8" annulus

F-C

MW & IS

F-A-5039

ULI

8, steel / iron

3

2

0 - 1" annulus

F-C

W-C or CB

MW & IS

C-AJ-1560

ULI

24, steel 2 1-1/2

1/4 - 1-1/2" annulus

W -C or CB

MW & IS W-J-5137 ULI

24, steel

2

1

0” – 4”

annulus

F- C

W -C or CB

MW & S or SL

C-AJ-5065

ULI

   top of page

 

     Plastic, PEX, Glass Pipe and Non-Metallic Conduit

Max. Size Penetration

in., Type

Rating (h)

Max. Size Opening

Construction Type (s)

A/D FIREBARRIER Product Required

System No.

Testing

Agency

F

T

3/4, PEX

2

1-1/2