Quick Links to Penetration Types
| LEGEND | |||||||
| Max. Size Penetrant |
Ratings / Listings |
Construction Type | Products | ||||
|
P =
Pipe
Ca =
Cables
CDI =
Cast / Ductile
Iron Pipe
CT =
Cable Tray
Cond
= Conduit
Cu =
Copper
Ø =
Diameter
|
USA :
F
and/or T
(See
page 6 for description)
Testing Agencies
ULI
- C-AJ, F-C, FF-D, FW-D,
ULC
- SP, SPC, JF & HW
ITS
- AD/PHV, AD/PH
& AD/PV
FM
- FM #’s |
F =
Floor
W =
Wall
Gyp =
Gypsum
C =
Concrete
CB =
Concrete Blocks
Cl =
Ceiling
PC =
Precast Hollow-core
SCI =
Suspended Ceiling
|
AS = Acrylic Sealant
Collar
Inserts
IS =
Intumescent Sealant
MW =
Mineral Wool Mortar N = Seal
NS =
Seal NS
Pillow
Putty Putty Pads S = Silicone SL = Silicone SL SA = SprayAcrylic
SM
=SprayMastic
WS =
Wrapstrip CS = Collar Strip |
||||
|
Shading in table denotes A/D FIREBARRIER Optimum Systems – often the best system to select for the situation.
|
|||||||
|
Max. Size Penetration in., Sch. |
Rating (h) |
Max. Size Opening |
Construction Type (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|
|
F |
T |
||||||
|
1¼, 5 |
3 |
¾ |
7/16” nom. annulus |
F- C W -C or CB |
Mortar & backer rod |
ULI |
|
|
1¼, 5 |
3 |
½ |
7/16” nom. annulus |
F- C W -C or CB |
MW & N or NS |
ULI |
|
|
1¼, 5 |
3 |
¾ |
7/16” nom. annulus |
F- C W -C or CB |
MW & Mortar |
ULI |
|
|
1¼, 5 |
1 & 2 |
1 |
¼” nom. annulus |
W - gyp |
S |
ULI |
|
|
1¼ |
1½ & 3 |
¾” nom. annulus |
F- C W -C or CB |
MW & N |
FM |
||
|
1½ |
2 & 3 |
¾” nom. annulus |
F- C W -C or CB |
Mortar & backer rod |
FM |
||
|
1-1/2, 10 |
3 |
3/4 |
0 - 1-7/8" annulus |
F- C W -C or CB or PC |
Putty II |
ULI |
|
|
2, 10 |
2 |
0 |
0” – 1-7/8 annulus |
W - C or CB |
S |
ULI |
|
2, 10 |
1 & 2 |
0 |
0” – 1-7/8” annulus |
W - gyp |
S |
ULI |
|
|
2, 40 |
1 & 3 |
See system |
48.3 in.² |
F/W - C |
MW & S or SL |
ITS |
|
|
2, 40 |
3 |
1 & 2 |
19 in.² |
F/W - C |
MW & S or SL |
ITS |
|
|
2, 40 |
3 |
1/2 |
0” – 1-13/16” annulus |
F- C W -C or CB |
Putty & backer rod |
ULI |
|
|
2, 40 |
0 & 1½ |
½” – 2” annulus |
F- C W -C or CB |
MW & S or SL |
FM |
||
|
2 |
2 |
½” nom. annulus |
F- C W -C or CB |
S or SL |
FM |
||
|
2, 40 |
2 |
|
1” nom. annulus |
F/W - C |
MW & S or SL |
FM |
|
|
3, 5 |
3 |
0 |
¾” nom. annulus |
F/W - C |
MW & S or SL |
ULI |
|
|
3, 5 |
3 |
0 |
¼” – 1-1/4” annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
|
3, 5 |
3 |
0 |
1” - 2-7/8” annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
|
3, 40 |
2 & 3 |
1” nom. annulus |
F/W - C |
MW & S or SL |
FM |
||
|
3, 40 |
1 |
1” nom. annulus |
F- C W -C or CB |
MW & S or SL |
FM |
||
|
3⅛, 40 |
3 |
See design |
1” nom. annulus |
F/W - C |
MW & S or SL |
ITS |
|
|
4, 10 |
1 |
1 |
1/8” nom. annulus |
F/CI -wood/gyp |
S |
ULI |
|
4, 10 |
1 |
1 |
0 - 7/8” annulus |
F-C W-gyp chase wall |
MW & IS or AS |
ULI |
|
|
4, 10 |
3 |
0 |
¾” nom. annulus |
F- C W -C or CB |
Putty, opt backer rod |
ULI |
|
|
6, 40 |
3 |
0 |
1” – 2-3/8 annulus |
F- C W -C or CB |
MW & N or NS |
ULI |
|
|
6, 10 |
3 |
0 |
2” nom. annulus |
F- C W -C or CB |
Mortar |
ULI |
|
6, 40 |
1 |
0, ¾, 1 |
½” nom. annulus |
F/CI -wood/gyp |
S |
ULI |
|
|
6, 40 |
2 |
0 |
1” nom. annulus |
W - C or CB |
MW & S |
ULI |
|
|
6, 40 |
2 |
0 |
1” nom. annulus |
W - gyp |
MW & S |
ULI |
|
8, 40 |
1 | 1/4 |
0 - 7/8” annulus |
F/CI-C/gyp W-gyp |
IS opt backer rod |
ULI |
|
|
8, 40 |
1, 2 | 1/4 |
0 - 7/8” annulus |
F-C W-gyp chase wall |
IS opt backer rod |
ULI |
|
|
8, 40 opt galv. sleeve |
1, 2 |
0 |
see design |
W-gyp |
MW & IS |
ULI |
|
8, 40 |
2 |
0 |
0” – 3-7/8” annulus |
F/W - C or CB |
MW & S |
ULI |
|
|
8, 40 |
2 |
0 |
0” – 3-3/8” annulus |
F/W - C or CB |
MW & NS |
ULI |
|
|
8, 10 |
2 |
0 |
0 - 7/8” annulus |
W -C or CB |
IS or AS |
ULI |
|
|
8, 10 |
2 |
0 |
0 - 7/8” annulus |
W-gyp |
MW & IS or AS |
ULI |
|
|
1, 10 opt. sleeve |
2 |
0 |
0 - 2” annulus |
W -C or CB |
IS |
ULI |
|
|
1, 10 opt. sleeve |
3 |
1/4 |
0 - 1-7/8” annulus |
F-C W-C, CB or PC |
MW & IS |
ULI |
|
|
10, 10 w / insulation |
2 |
1 |
½” – 3/4” annulus |
W - gyp |
2” WS |
ULI |
|
|
12, 10 opt galv. sleeve |
1 & 2 |
0 |
0 - 1-7/8" annulus |
W-gyp |
IS opt backer rod |
ULI |
|
|
12, 10 |
2 & 3 |
0 |
see design |
F-C W-C, CB or PC |
IS & MW &/or Backer rod |
ULI |
|
|
16, 40 |
2 |
0 |
0” – ¾” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
24, 10 |
3 |
0 |
2” nom. annulus |
F- C W -C or CB |
Mortar |
ULI |
|
24, 40 |
2 |
0 |
0” – 7/8” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
24, 40 |
3 |
0 |
0” – 1-7/8” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
24, 40 |
3 |
0 |
½” – 1-3/8” annulus |
F- C W -C or CB |
MW & NS |
ULI |
|
|
Max. Size Penetration in. |
Rating (h) |
Max. Size Opening |
Construction Type (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|
|
F |
T |
||||||
|
2 |
2 |
0 |
0” – 1-7/8 annulus |
W - C or CB |
S |
ULI |
|
|
2 |
1 & 2 |
0 |
0” – 1-7/8 annulus |
W - gyp |
S |
ULI |
|
|
2 |
3 |
1/2 |
0” – 1-13/16” annulus |
F- C W -C or CB |
Putty & backer rod |
ULI |
|
|
3 |
3 |
0 |
¼” – 1-1/4” annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
4 |
1 |
1 |
0 - 7/8” annulus |
F-C W-gyp chase wall |
MW & IS or AS |
ULI |
|
|
6 |
3 |
0 |
2” nom. annulus |
F- C W -C or CB |
Mortar |
ULI |
|
6 |
2 |
0 |
½” nom. annulus |
F/CI -wood/gyp |
S |
ULI |
|
|
6 |
2 |
0 |
1” nom. annulus |
W - C or CB |
MW & S |
ULI |
|
|
6 |
2 |
0 |
1” nom. annulus |
W - gyp |
MW & S |
ULI |
|
8 |
1 | 1/4 |
0 - 7/8” annulus |
F/CI-C/gyp W-gyp |
IS opt backer rod |
ULI |
|
|
8, 40 opt galv. sleeve |
1, 2 |
0 |
see design |
W-gyp |
MW & IS |
ULI |
|
|
8, 40 |
1, 2 | 1/4 |
0 - 7/8” annulus |
F-C W-gyp chase wall |
IS opt backer rod |
ULI |
|
|
8 |
2 |
0 |
0 - 7/8” annulus |
W-C or CB |
IS or AS |
ULI |
|
|
8 |
2 |
0 |
0 - 7/8” annulus |
W-gyp |
MW & IS or AS |
ULI |
|
8 |
2 |
0 |
0” – 3-7/8” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
8 opt. sleeve |
2 |
0 |
0 - 2” annulus |
W -C or CB |
IS |
ULI |
|
|
8 |
2 |
0 |
0” – 3-3/8” annulus |
F/W - C or CB |
MW & NS |
ULI |
|
|
8 opt. sleeve |
3 |
1/4 |
0 - 1-7/8” annulus |
F-C W-C, CB or PC |
MW & IS |
ULI |
|
|
12 opt galv. sleeve |
1 & 2 |
0 |
0 - 1-7/8" annulus |
W-gyp |
IS opt backer rod |
ULI |
|
|
12 opt sleeve |
2 & 3 |
0 |
see design |
F-C W-C, CB or PC |
IS & MW &/or Backer rod |
ULI |
|
16 |
2 |
0 |
0” – ¾” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
24 |
2 |
0 |
0” – 7/8” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
24 |
3 |
0 |
0” – 1-7/8” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
24 |
3 |
0 |
½” – 1-3/8” annulus |
F- C W -C or CB |
MW & NS |
ULI |
|
|
Max. Size Penetration in. |
Rating (h) |
Max. Size Opening |
Construction Type (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|
|
F |
T |
||||||
|
½ |
3 |
3 |
2-3/4" max annulus |
F-C |
MW & S |
ITS |
|
|
½ |
3 |
see design |
2-3/4" max annulus |
F-C |
MW & N or NS |
ITS |
|
|
½ |
3
|
2-3/4" max annulus |
F/W-C |
MW & N |
FM |
||
|
2, L |
2 |
0 |
0 - 1-7/8 annulus |
W-C or CB |
S |
ULI |
|
|
2, L |
1 & 2 |
0 |
0 - 1-7/8 annulus |
W-gyp |
S |
ULI |
|
|
2 |
1,3 |
see design |
1-7/32 max annulus |
F/W-C |
MW & S or SL |
ITS |
|
|
2 |
1-1/2 & 0 |
1/2 - 2" annulus |
F-C W-C or CB |
MW & S or SL |
FM |
||
|
3, L or Reg |
3 |
0 |
3/4" annulus |
F-C W-C or CB |
MW & S or SL |
ULI |
|
|
3, L or Reg |
3 |
0 |
1-2-7/8" annulus |
F-C W-C or CB |
MW & S or SL |
ULI |
|
| 3, M or Reg | 3 | 0 |
1-2-7/8" annulus |
F-C W-C or CB |
MW & S or SL | C-AJ-1129 | ULI |
| 3 | 3&2 | 3&2 | 1" nom. annulus | F/W-C | MW & S or SL | 85 | FM |
| 3 | 1 | 1" nom. annulus |
F-C W-C or CB |
MW & S or SL | 236 | FM | |
| 3-1/8 | 3 | see design | 1" max. annulus | F/W-C | MW & S or SL | AD/PHV180-12 | ITS |
|
4, L or Reg |
1 |
0 |
1/2" nom annulus |
F/CI-C/gyp W-gyp |
S |
ULI |
|
4, L or Reg |
1 | 1/4 |
0 - 7/8” annulus |
F/CI-C/gyp W-gyp |
IS opt backer rod |
ULI |
|
|
4, L or Reg |
1 |
1 |
1/8” nom. annulus |
F/CI -wood/gyp |
S |
ULI |
|
|
4, L or Reg |
1 |
1 |
0 - 7/8” annulus |
F-C W-gyp chase wall |
MW & IS or AS |
ULI |
|
|
4, L or Reg opt galv. sleeve |
1, 2 |
0 |
see design |
W-gyp |
MW & IS |
ULI |
|
|
4, L or Reg |
1, 2 |
1/4 |
0 - 7/8” annulus |
F-C W-gyp chase wall |
IS opt backer rod |
ULI |
|
|
4, L or Reg opt galv. sleeve |
1 & 2 |
0 |
0 - 1-7/8" annulus |
W-gyp |
IS opt backer rod |
ULI |
|
|
4, L or Reg |
2 |
0 |
0 - 7/8” annulus |
W-C or CB |
IS or AS |
ULI |
|
|
4, L or Reg |
2 |
0 |
0 - 7/8” annulus |
W-gyp |
MW & IS or AS |
ULI |
|
|
4, L or Reg opt. sleeve |
2 |
0 |
0 - 2” annulus |
W -C or CB |
IS |
ULI |
|
|
4, L or Reg opt. sleeve |
3 |
1/4 |
0 - 1-7/8” annulus |
F-C W-C, CB or PC |
MW & IS |
ULI |
|
|
6, L or Reg opt. sleeve |
2 & 3 |
0 |
see design |
F-C W-C, CB or PC |
IS & MW &/or Backer rod |
ULI |
|
|
6, L or Reg |
3 |
0 |
2” nom. annulus |
F- C W -C or CB |
Mortar |
ULI |
|
6, K or Reg |
2 |
0 |
0” – 7/8” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
6, L or Reg |
3 |
0 |
0” – 1-7/8” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
6, K or Reg |
3 |
0 |
½” – 1-3/8” annulus |
F- C W -C or CB |
MW & NS |
ULI |
|
Insulated Pipe
|
Max. Size Penetration in., Type |
Rating (h) |
Max. Size Opening |
Construction Type(s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|
|
F |
T |
||||||
|
2, Cu & steel |
1 |
1 |
¼” nom. annulus |
F/CI -wood/gyp |
S |
ULI |
|
| 2, Cu & steel/iron |
2 |
1 |
1/8 - 1/4" annulus |
F-C W-C or CB |
MW & IS |
ULI |
|
| 2, PVC & CPVC |
2 |
1-1/4 |
see design |
F-C W-C or CB |
MW & IS |
ULI |
|
| 2, Cu |
1 |
3/4 & 1 |
0 - 7/8" annulus |
F/Cl-C/gyp W-gyp |
IS opt backer rod |
ULI |
|
|
3, Cu & steel |
1 & 2 |
½ |
¼” nom. annulus |
W - gyp |
S |
ULI |
|
|
3, Cu & steel |
3 |
¾ |
¼” nom. annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
|
4, Cu & steel / iron |
1 |
0 |
0” – 1-1/2” annulus |
F- C W -C or CB |
MW & S |
ULI |
|
|
4, Cu & steel |
1 |
¾ |
¼” nom. annulus |
F/CI -wood/gyp |
S |
ULI |
|
| 4, steel, iron |
1 |
3/4 & 1 |
0 - 7/8" annulus |
F/Cl-C/gyp W-gyp |
IS opt backer rod |
ULI |
|
|
4, Cu & steel / iron |
1 & 2 |
1/2 |
0-1-3/8" annulus |
W-gyp |
IS opt backer rod |
ULI |
|
|
4, Cu |
1-1/2 & 2 |
1 & 1/2 |
see design |
F-C W-C or CB |
MW & IS or AS |
ULI |
|
|
4, Cu |
2 |
0 & 1 |
see design |
W-gyp |
IS, opt backer rod or MW & IS |
ULI |
|
|
4, steel / iron |
2 |
1½ |
0” – 2-1/2” annulus |
F- C W -C or CB |
MW & Mortar |
ULI |
|
|
4, Cu (L) |
3 |
1 |
1/4 - 5/8" annulus |
F-C |
MW & S |
ULI |
|
|
4, Cu |
3 |
2 |
0 - 1" annulus |
F-C W-C or CB |
MW & IS |
ULI |
|
|
Cu & steel/iron |
2 & 3 |
1, 1-1/4 & 1-1/2 |
see design |
F- C W -C or CB |
MW & IS |
ULI |
|
|
6, Cu & steel |
1-1/2 |
1/2 & 3/4 |
0 - 4" annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
|
8, steel / iron |
1-1/2 & 2 |
1 & 1/2 |
see design |
F- C W -C or CB |
MW & IS or AS |
ULI |
|
|
8, steel / iron |
2 |
0 & 1 |
see design |
W-gyp |
IS, opt backer rod or MW & IS |
ULI |
|
|
8, steel / iron |
3 |
1 |
1/4 - 5/8" annulus |
F-C |
MW & IS |
ULI |
|
|
8, steel / iron |
3 |
2 |
0 - 1" annulus |
F-C W-C or CB |
MW & IS |
ULI |
|
| 24, steel | 2 | 1-1/2 |
1/4 - 1-1/2" annulus |
W -C or CB |
MW & IS | W-J-5137 | ULI |
24, steel |
2 |
1 |
0” – 4” annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
Plastic, PEX, Glass Pipe and Non-Metallic Conduit
|
Max. Size Penetration in., Type |
Rating (h) |
Max. Size Opening |
Construction Type (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|
|
F |
T |
||||||
|
3/4, PEX |
2 |
1-1/2 |
|||||