Quick Links to Penetration Types

|
Max. Size Penetration in., Sch. |
Rating (h) |
Max. Size Opening |
Construction Type (s) |
A/D FIREBARRIER Product Required |
System No. |
Testing Agency |
|
|
F |
T |
||||||
|
1¼, 5 |
3 |
¾ |
7/16” nom. annulus |
F- C W -C or CB |
Mortar & backer rod |
ULI |
|
|
1¼, 5 |
3 |
½ |
7/16” nom. annulus |
F- C W -C or CB |
MW & N or NS |
ULI |
|
|
1¼, 5 |
3 |
¾ |
7/16” nom. annulus |
F- C W -C or CB |
MW & Mortar |
ULI |
|
|
1¼, 5 |
1 & 2 |
1 |
¼” nom. annulus |
W - gyp |
S |
ULI |
|
|
1¼ |
1½ & 3 |
¾” nom. annulus |
F- C W -C or CB |
MW & N |
FM |
||
|
1½ |
2 & 3 |
¾” nom. annulus |
F- C W -C or CB |
Mortar & backer rod |
FM |
||
|
1-1/2, 10 |
3 |
3/4 |
0 - 1-7/8" annulus |
F- C W -C or CB or PC |
Putty II |
ULI |
|
|
2, 10 |
2 |
0 |
0” – 1-7/8 annulus |
W - C or CB |
S |
ULI |
|
2, 10 |
1 & 2 |
0 |
0” – 1-7/8” annulus |
W - gyp |
S |
ULI |
|
|
2, 40 |
1 & 3 |
See system |
48.3 in.² |
F/W - C |
MW & S or SL |
ITS |
|
|
2, 40 |
3 |
1 & 2 |
19 in.² |
F/W - C |
MW & S or SL |
ITS |
|
|
2, 40 |
3 |
1/2 |
0” – 1-13/16” annulus |
F- C W -C or CB |
Putty & backer rod |
ULI |
|
|
2, 40 |
0 & 1½ |
½” – 2” annulus |
F- C W -C or CB |
MW & S or SL |
FM |
||
|
2 |
2 |
½” nom. annulus |
F- C W -C or CB |
S or SL |
FM |
||
|
2, 40 |
2 |
|
1” nom. annulus |
F/W - C |
MW & S or SL |
FM |
|
|
3, 5 |
3 |
0 |
¾” nom. annulus |
F/W - C |
MW & S or SL |
ULI |
|
|
3, 5 |
3 |
0 |
¼” – 1-1/4” annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
|
3, 5 |
3 |
0 |
1” - 2-7/8” annulus |
F- C W -C or CB |
MW & S or SL |
ULI |
|
|
3, 40 |
2 & 3 |
1” nom. annulus |
F/W - C |
MW & S or SL |
FM |
||
|
3, 40 |
1 |
1” nom. annulus |
F- C W -C or CB |
MW & S or SL |
FM |
||
|
3⅛, 40 |
3 |
See design |
1” nom. annulus |
F/W - C |
MW & S or SL |
ITS |
|
|
4, 10 |
1 |
1 |
1/8” nom. annulus |
F/CI -wood/gyp |
S |
ULI |
|
4, 10 |
1 |
1 |
0 - 7/8” annulus |
F-C W-gyp chase wall |
MW & IS or AS |
||