FIREFILM®III  

FIRE TEST DESIGN SUMMARY

Construction Type

Ratings, hours

Minimum

W/D (M/D)

Design No.

3/4

1

1.5

2

3

ULI

ULC

ITS FM
Columns - W Shapes X X - - - 0.59 (34) X669 Z626 - Method 6
Columns - W Shapes - - - - X 1.28 (74) X670 Z627 - Method 7
Columns - W Shapes - - - - X 2.26 (130) X639 Z608 AD/CA 180-01 -
Columns - W Shapes X X X X - refer to design X641 Z610 AD/CA 120-03 -

Columns - W Shapes

-

 

-

 

X

 

-

X

-

 

0.66 (38)

1.64 (95.2)

X643 Z612 -
Columns - W Shapes - - - X - 1.28 (74) X645***

Z617

***

AD/CA 120-04

***

Method 5

***

Columns - HSS Shapes - - X X - A/P≥0.30 (59) X671 Z628 - Method 8
Columns - HSS Shapes X X X X - refer to design X642 Z611 AD/CA 90-02 -
Columns - HSS Shapes X X X X X A/P≥0.46 (90) X672 Z629 - Method 9
Columns - HSS Shapes X X - - - A/P≥0.22 (44) X673 Z630 - Method 10

Columns ***

 HSS Shapes - - - X - A/P≥0.57 (113.9) X645***

Z617

***

AD/CA 120-04

***

Method 5

***

Beams / Floors B B R R - 0.51 (30) - F906 AD/FCA 120-01 -
Beams / Floors - B R R - 0.82 (48) D948 F910 -

Beams / Floors

-

 

-

 

U

 

R

B

-

 

0.80 (46)

0.84 (48)

D941

F912

-

No. 31

R = Restrained Assembly     U = Unrestrained Beam + Unrestrained Assembly Rating     B = Restrained Assembly +Unrestrained Assembly and Beam


      ***X645, Z617 and AD/CA 120-04 and Method 5 require glass cloth.

ITS = Intertek Testing Services (Warnock Hersey) UL = Underwriters Laboratories Inc.
ULC = Underwriters' Laboratories of Canada FM = Factory Mutual Research

This summary contains information we believe to be accurate and current as of June 11, 2007. New designs are being developed and existing designs are being updated continuously. Please contact your A/D FIREFILM III representative for the latest design information.

HOME                                                                                                       BACK