A/D FIREFILMĀ® III

Fire Test Design Summary

Construction TypeMinimum W/D (M/D) for Indicated RatingsDesign No.
3/4, h 1, h 1-1/2, h 2, h 3, h UL ULC ITS FM
Columns - W Shapes 0.43 (24) 0.43 (24) 0.92 (53) 1.63 (94) - X641 Z610 AD/IMF 120-02
(Formerly AD/CA 120-03)
-
- - 0.66 (38) 1.64 (95) - X643 Z612 -
0.84 (49) 0.59 (34) - - - X669 Z626 - Method 6
- - - - 1.28 (74) X670 Z627 - Method 7
- - - - 2.26 (130) X639 Z608 AD/IMF 180-01
(Formerly AD/CA 180-01)
-
Columns - HSS Shapes A/P >= 0.22(44) A/P >= 0.22(44) - - - X673 Z630 - Method 10
- - A/P >= 0.30(59) A/P >= 0.30(59) - X671 Z628 - Method 8
A/P >= 0.18(36) A/P >= 0.27(54) A/P >= 0.30(60) A/P >= 0.47(93) - X642 Z611 AD/IMF 90-01
(Formerly AD/CA 90-02)
-
A/P >= 0.46(90) A/P >= 0.46(90) A/P >= 0.46(90) A/P >= 0.46(90) A/P >= 0.46(90) X672 Z629 - Method 9
Beams / Floors B - 0.51(30) B - 0.51(30) R - 0.51(30) R - 0.51(30) - - F906 AD/IMF 120-01
(Formerly AD/CA 120-01)
-
- B - 0.82(48) R - 0.82(48) R - 0.82(48) R - 0.82(48) D948 F910 -
- - U - 0.80(46) R - 0.80(46)
B - 0.84(48)
- D941 F912 - No. 31
R = Restrained Assembly, B = Restrained Assembly + Unrestrained Assembly and Beam, U = Unrestrained Assembly and Beam

This summary contains information we believe to be accurate and current as of April 8, 2015.
Please contact your A/D representative for the latest design information.